| 1 | L1₹47.1 LAccepted-AOC NEAR PAYAL CINEMA P O SEVOKE ROAD SILIGURI 734 001 | DARJEELING | WEST BENGAL | 734001 | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹50.1 L+₹1.9 L (3.86%)Rejected-Finance RABINDRA NAGAR P O RABINDRA SARANI SILIGURI 734 006 DIST DARJEELING W B | JALPAIGURI | WEST BENGAL | 734006 | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹50.2 L+₹1.9 L (3.94%)Rejected-Finance 30 HAREN MUKHERJEE ROAD HAKIMPARA SILIGURI 734 001 DARIEELING WB | DARJEELING | WEST BENGAL | 734001 | L3 | Rejected-Finance Other than lowest bidder | |
| 4 | L4₹50.5 L+₹2.2 L (4.54%)Rejected-Finance SIMULBARI T E PO VILL SIMULBARI PS KURSEONG DIST DARJEELING PIN 734009 WEST BENGAL | SIMULBARI | DARJEELING | WEST BENGAL | 734009 | L4 | Rejected-Finance Other than lowest bidder | |
| 5 | L5₹50.5 L+₹2.2 L (4.65%)Rejected-Finance A 4 VIVEKANANDA SUPER MARKET 2ND FLOOR HILL CART ROAD SILIGURI 734 001 DIST DARJEELING W B | JALPAIGURI | WEST BENGAL | 734001 | L5 | Rejected-Finance Other than lowest bidder |
Tender Value
₹47.4 L
EMD Value
₹94,800
Closing Date
11 Aug 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE Bengdubi
Headquarters Commander Works Engineers Bengdubi, Post - Bengdubi Distt - Darjeeling (WB) PIN- 734424
REPAIR/ MAINTENANCE OF CERTAIN HT INSTALLATIONS AT SUKNA MIL STATION UNDER GE SUKNA
2022_MES_540443_1
8153/S/E8
Open Tender
Electrical and Maintenance Works
Item Rate
360 days
GE Sukna
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE Sukna
₹94,800
7 Oct 2022
23 Jul 2022
17 Aug 2022
23 Jul 2022
11 Aug 2022
5 Aug 2022
Amount
Supply, laying and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, HT electric power cables (heavy duty) with aluminium conductor 11000 volts grade (Earthed) of size 95 sqmm 3 core, including taking down old unsv, complete all as specified and directed. Note For Item No.1 to 5: Excavation and earth work, Boring/ Drilling, sand cushioning, protection covers, protection pipes and jointing kits including jointing materials shall be measured and paid separately under relevant items.
Supply, laying and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, HT electric power cables (heavy duty) with aluminium conductor 11000 volts grade (Earthed) of size 120 sqmm 3 core, including taking down old unsv, complete all as specified and directed.
Supply, laying and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, LT electric power cables (heavy duty) with aluminium conductor 1100 volts grade (Earthed) of size 150 sqmm 3.5 core, including taking down old unsv, complete all as specified and directed.
Supply, laying and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, LT electric power cables (heavy duty) with aluminium conductor 1100 volts grade (Earthed) of size 240 sqmm 3.5 core, including taking down old unsv, complete all as specified and directed.
Supply, laying and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, LT electric power cables (heavy duty) with aluminium conductor 1100 volts grade (Earthed) of size 300 sqmm 3.5 core, including taking down old unsv, complete all as specified and directed.
Excavation in trenches in soft/ loose soil not exceeding 1.5 metre wide and not exceeding 1.5m in depth for laying of HT/LT under ground cables/ pipes and not exceeding 10 Sqm on plan & 1.5 metre in depth for pole etc, complete all as specified and directed.
Returning, filling in, with approved earth (retrieved from excavation after removal of grass, vegetation etc) including spreading, watering and well ramming in layers not exc 25cm thick in layers, complete all as specified and directed.
Removal of surplus spoil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point, complete all as specified and directed.
M& L for Sand cushioning in trenches/ existing cable trenches for cushioning of HT underground cable including spreading, levelling, well ramming in layers not exceeding 25cm in thickness, complete all as specified and directed.
Material and labour for well burnt Sub-class 'B' old size bricks, best quality locally available laid flat, dry in trenches for cable protection, complete all as specified and as directed.
Supply and fixing GI tubing, light grade, 80mm bore for protection of cable, under road crossing, across drain, along electric pole or floor /wall etc, complete including taking out existing pipe, complete all as specified and directed. Note : Excavation & Earth work and/ or Boring/Drilling shall be measured & paid for separately.
Boring/Drilling (horizontally) manually approx. at 2 metre depth in soil below existing road suitable for passing GI tubing of 40 to 80 mm bore, complete all as specified and directed.
Supply, jointing and testing in repairs, cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination, heat shrink type joint, complete with and including jointing materials and accessories suitable for 11KV XLPE insulated armoured aluminium conductor cable of size 95 Sqmm 3 core, complete all as specified and as directed.
Supply, jointing and testing in repairs straight through cable jointing kit (Heat shrink type) for 11 KV (Earthed) grade cable complete with and including jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm and also including provision of aluminium thimbles, complete all as specified and as directed.
Supply, jointing and testing in repairs cable jointing kit for 11 KV (Earthed) grade cable for indoor termination, heat shrink type joint, complete with and including jointing materials and accessories suitable for 11KV XLPE insulated armoured aluminium conductor cable of size 95 Sqmm 3 core, complete all as specified and as directed.
Material and labour for (i) Disconnecting the HT/LT side and earthing connections of the Compact Transformer (ii) Lifting of transformer with the help of crane, loading on suitable vech to transport it to the workshop and Unloading at workshop for servicing (A).Details of the transformer to be repaired: Dry type cast resin distribution transformer. (a) Rated KVA 630 KVA (b) Voltage Ratio 11 KV/.433 KV (c) Phase / Frequency: 3 / 50 Hz. (d) Vector group: Dyn11 (e) Cooling: AN (f) Class: H (iii).Transporting of transformer from workshop to site, unloading and connection of HT anf LT side all as directed by Engineeer in charge.
Dismantle transformer core coil assembly to acquire physical data of all the parameters and dimensional details. To open one of the coils for procuring the electrical data. Cleaning of the existing core and banding it with rayon tapes. Fixing of insulating material, new copper coil/ strip etc. to make new coils and casting of the same. Windings to be done with new copper conductors including all other insulation material for Core and coil assembly LV side of 630 KVA transformer complete all as directed by Engr in charge.
All as per Sl item No. 17 Above but for core and coil assembly complete HV side of 630 KVA transformercomplete all as directed by Engr in charge.
Material and labour for (i) Disconnecting the HT/LT side and earthing connections of the Compact Transformer (ii) Lifting of transformer with the help of crane, loading on suitable vech to transport it to the workshop and Unloading at workshop for servicing (A).Details of the transformer to be repaired: Dry type cast resin distribution transformer. (a) Rated KVA 315 KVA (b) Voltage Ratio 11 KV/.433 KV (c) Phase / Frequency: 3 / 50 Hz. (d) Vector group: Dyn11 (e) Cooling: AN (f) Class: H (iii).Transporting of transformer from workshop to site, unloading and connection of HT anf LT side all as directed by Engineeer in charge.
Dismantle transformer core coil assembly to acquire physical data of all the parameters and dimensional details. To open one of the coils for procuring the electrical data. Cleaning of the existing core and banding it with rayon tapes. Fixing of insulating material, copper coil etc. to make new coils and casting of the same. Windings to be done with new copper conductors including all other insulation material for Core and coil assembly complete LV side of 315 KVA transformer complete all as directed by Engr in charge.
All as per Sl item No. 20 Above but for core and coil assembly complete HV side of 315 KVA transformer complete all as directed by Engr in charge.
Material and labour for (i) Disconnecting the HT/LT side and earthing connections of the Compact Transformer (ii) Lifting of transformer with the help of crane, loading on suitable vech to transport it to the workshop and Unloading at workshop for servicing (A).Details of the transformer to be repaired: Dry type cast resin distribution transformer. (a) Rated KVA 250 KVA (b) Voltage Ratio 11 KV/.433 KV (c) Phase / Frequency: 3 / 50 Hz. (d) Vector group: Dyn11 (e) Cooling: AN (f) Class: H (iii).Transporting of transformer from workshop to site, unloading and connection of HT anf LT side all as directed by Engineeer in charge.
Dismantle transformer core coil assembly to acquire physical data of all the parameters and dimensional details. To open one of the coils for procuring the electrical data. Cleaning of the existing core and banding it with rayon tapes. Fixing of insulating material, copper coil etc. to make new coils and casting of the same. Windings to be done with new copper conductors including all other insulation material for Core and coil assembly LV side of 250 KVA transformer complete all as directed by Engr in charge.
All as per Sl item No. 23 Above but for core and coil assembly HV side.of 250 KVA transformer complete all as directed by Engr in charge. Note For item No. 16 to 24 (a) All insulation used into winding will be new, non-hygroscopic and non-flammable. (b) In all three coils, the primary & secondary windings both will be replaced with new ones. (c) In case of damage during tpt/ loading/unloading at any stage after recipt of transformer from Dept, the contracor shall be repsonsible for damage and it shall be made good by him at his own expense.the decision of Engineer in charge in the regards shall be fixed & biding. (d) Rates are inclusive of testing of earthing before connection of transformer
M&L in replacement Switch Air Break, Gang operated, Triple Pole, Mechanically Operated, mounted on Insulators and Steel Frame Single Break Insulator suitable for Out door Vertical Mounted complete with Manual Operating Mechanism made and operation from GL including 25mm bore GI pipe heavy duty and handle Arching Horns and Terminal Connectors for ACSR Conductors conforming to IS-1818/72 and 9921/85 with 3 Isolator Per Pole of Capacity 200 Amp, 11 KV Operation including necessary Adjustment and making Holes on Mild Steel Angle and Testing complete all as specified and as directed.
S&F in repair Pin type, porcelain, vitreous, white, brown or green insulator including one galvnished mild steel spindle, two galvanised iron washers and one galvanied iron nut, 150 mm height and 150 mm dia, for 11 KV grade, complete all as specified and directed.
S&F in repair DO fuse expusion type single pole for 200Amps grade, suitable for 11 KV, complete all as specified and directed.
S&F in repair, lightening arrester, non-linear metal oxide type, complete with and including all fittings, expulsion type, transmission class, discharge capacity 65 Kilo amps suitable for 11 KV, out door typeand also including necessary connection and fittings all as per IS-3070 Part-III and IEC 1994, complete all as specified and as directed.
Dismantling of defective 33 KV VCB type PCOB-36, 36/ 33 KV/ 1250 Amps, out door and indoor remote control unit of complete VCB panel (Make: Schneider/ Crompton Greaves/ Alstom), servicing, repairing/ replacement (as directed) of the unserviceable items such as closing/ triping coil assembly, spring charging motor and gear assemby, auxilary relays, over current relays, overhauling and including rectification of the electrical & mechanical fault by the Service Engineer/ Authorised Personnel of the Company after necessary cleaning and providing silicon grease to all the moving parts, also including adjustment of all springs/ relays etc, commissioning of 33 KV VCB Panel, CT, PT, Relays, VCB testing including CRM, Timer, IR Testing in VCB and ratio primary, IR, winding resistance, polarity testing in CT and PT and secondary current injection with 03 setting & tripping test with timing in relays and applying control voltage & testing all scheme logic with on/off trip operation, also checking metering and protection and annunciation with indication kit, making the VCB Panel (including VCB, its components, entire system) 100% serviceable, complete in all respects, as specified and directed. Note - Cost of all the materials, labour and other elements to make the entire system servicable shall be deemed to be included in the quoted rates and only payment for supply only of the items listed at ser No 30 to 35 here-in-below shall be measured and paid for separately in case these are ordered and provided as directed. The make of the items /materials shall be as specified in the item(s) and in case not specified, the same shall be of make Schneider/ Crompton Greaves/ Alstom or as per existing suitable to match with the existing VCB system as approved by the GE.
Supply only closing and triping coil assembly of 33 KV VCB's matching with the existing system, complete all as specified and as directed.
Supply only spring charging motor & gear assembly matching with the existing VCB system,complete all as specified and as directed.
Supply only Auxilary Relay Type VAA, Model -VAA32ZG80 13 BCH, 30 Volt DC of ALSTOM or equivalent model of existing make as approved by the GE, complete all as specified and as directed.
Supply only Auxilary Relay Type VAA, Model - VAAII YF8006AH (M) of ALSTOM or equivalent model of existing make as approved by the GE, complete all as specified and as directed.
Supply only Auxilary Relay Type VAA, Model -SPECM2YF251A (VAAII) of ALSTOM or equivalent model of existing make as approved by the GE, complete all as specified and as directed.
Supply only Over Current and Earth Fault Relay (Inverse) Capacity 10 Amps, type CDG, Model CDG 31 EG011SBCH of ALSTOM or equivalent model of existing make as approved by the GE, complete all as specified and as directed.
Dismantling of defective 11 KV VCB ,400/ 630 Amps, Indoor VCB panel (Make: Schneider/ Crompton Greaves), servicing, repairing/ replacement (as directed) of the unserviceable items such as closing/ triping coil assembly, spring charging motor and gear assemby, master trip relays, supervision trip relays, over current relays, overhauling and including rectification of the electrical & mechanical fault by the Service Engineer/ Authorised Personnel of the Company after necessary cleaning and providing silicon grease to all the moving parts, also including adjustment of all springs/ relays etc, commissioning of 11 KV VCB Panel CT, PT, Relays, VCB testing including CRM, Timer, IR Testing in VCB and ratio primary, IR, winding resistance, polarity testing in CT and PT and secondary current injection with 03 setting & tripping test with timing in relays and applying control voltage & testing all scheme logic with on/off trip operation, also checking metering and protection and annunciation with indication kit, testing of CT ratio, polarity test, making connection of CT100-50/5 +5A by primary injection complete, caliberation of IDMT relay over current, earth fault and under voltage 100-50/5 +5A secondary injection complete, preparation of surfaces of VCB panel board cubical in shape & applying one coat of SFRC paint, mking the VCB Panel (including VCB's, its components, entire system) 100% servicable, complete in all respects, as specified and directed. Note: - Cost of all the materials, labour and other elements to make the entire system servicable shall be deemed to be included in the quoted rate and only payment for supply only of the items listed at ser No 37 to 52 here-in-below shall be measured and paid for separately in case these are ordered and provided as directed. The make of the items /materials shall be as specified in the item(s)and in case not specified, the same shall be of make (Make: Schneider/ Crompton Greaves/ Alstom) or as per existing suitable to match with the existing VCB system as approved by the GE.
Supply only digital Ampere Meter suitable for 11KV, 400 amps VCB Panel, complete all as specified and directed.
Supply only digital Volt Meter suitable for 11KV, 400 amps VCB Panel, complete all as specified and directed.
Supply only Over Current Relay and Earth Fault Relay (Make : Schineider, Type Micon P 111) suitable for 11KV, 400 amps VCB Panel, complete all as specified and directed.
Supply only master trip relay (Make : ALSTOM) suitable for 11KV, 400 amps VCB Panel, complete all as specified and directed.
Supply only supervision trip relay (Make : ALSTOM) suitable for 11KV, 400 amps VCB Panel, complete all as specified and directed.
Supply only single phase, PT suitable for 11KV, 630 amps VCB Panel, complete all as specified and directed.
Supply only single phase, PT fuse suitable for 11KV, 630 amps VCB Panel, complete all as specified and directed.
Supply only space heater 230V, AC, 100W suitable for 11KV, 630/400 amps VCB Panel, complete all as specified and directed.
Supply only multi voltage type indicator lamp suitable for 11KV, 630/400 amps VCB Panel, complete all as specified and directed.
Supply only tripping coil, 110V, DC suitable for 11KV, 630/400 amps VCB Panel, complete all as specified and directed.
Supply only closing coil, 110V, DC suitable for 11KV, 630/400 amps VCB Panel, complete all as specified and directed.
Supply only spring charging gear motor, 230V, AC suitable for 11KV, 630/400 amps VCB Panel, complete all as specified and directed.
Supply only buffer suitable for 11KV, 630/400 amps VCB Panel, complete all as specified and directed.
Supply only TNC switch suitable for 11KV, 630/400 amp VCB Panel, complete all as specified and directed.
Supply only digital type, multifunction meter of size 96 x 96mm, (Make : Schineider) suitable for 11KV , 630/400 amps VCB Panel, complete all as specified and directed
Supply only 11 KV CTs having CT ratio 100-50/5 +5A and output & accuracy class Core 1:15 VA/ CL1.0 and Core 2:15 VA/ 5P10, STR: 13.1 KA for 1 sec, BII 28/ 75 KVP Frequency: 50 Hz, conforming to IS: 2705/ 1981, suitable for existing system, complete all as specified and directed.
Supply, installation, testing and commissioning of unarmoured, PVC insulated & sheathed, 1100 Volts grade control cable with FRLS, solid copper conductor, 2.5 sqmm 4 core for VCBs, remote control units including taking down old unsv, complete all as specified and directed.
Disconnection & dismantling of OLTC from 2.0 MVA Power Transformer after disconnection of OTIs & WTIs from Marshalling Box, Repairing & Overhauling of 17 Nos Tap position of OLTC after opening each Tap, refixing of the same after proper cleaning of sludge & other foreign materials and reconnection of OLTC, WTI and OTIs with 3.15 MVA Power Transformer, complete all as specified and directed. Note: Cost for provision of new oil seal shall be deemed to be included in the quoted rate. However the payment for supply only of Transformer oil as required for filling upto required level in Conservation Tank shall be measured & paid for separately.
Dismantling of unserviceable remote tap changer control panel (RTCC) (Make: SCHNEIDER) for 2.0MVA 33/11 KVA Power transformer, servicing and maintenance of the unserviceable items, replacement of remote WTI, TPI, remote OTI including rectification of the electrical & mechanical fault by the Service Engineer/ Authorised Personnel of the Company after necessary cleaning and applying control voltage & testing all scheme logic with tap adjusting operation, also checking metering, protection & annunciation with indication and making the RTCC 100% serviceable, complete in all respects as specified and directed.
Supplying and laying reinforced factory made (Make: As approved by the GE) pre cast reinforced concrete cable cover class EHV, type 1 with peak, size 450x230x50 mm for cable protection in trenches, complete all as specified and directed.
M&L for broken stone or boulders hardcore of gauge n. exc 63 mm, deposited, spread and levelled in layers n.exc 15 cm thick, watered and rammed to a true surface, complete all as specified and directed.
Surface dressing averaging 15 cm deep in soft/ loose soil, including site clearance, cutting of green vegetation, grass, subsequent to above spreading thin layer of anti-vegetation chemical as per the manufacturer instructions (make of chemical shall be as approved by the GE) near the 2/4 pole structures, GODs and various unmanned electric sub stations inside and outside of premises, also including disposal of all spoil, grass, green-vegetation etc outside of the premises, complete all as specified and as directed. Note :- The surface dressing shall normally be done once in three months for the Sub-Stations etc as ordered. Payment for each time shall be made for separately as per the actual work done at site.
Cutting/ trimming of tree branches in close proximity to over head lines to maintain a clearance of 1.5 metre from the over head line to nearby trees, complete all as specified and as directed. Notes:- (i)Tree Branches upto 100 mm girth shall be deemed to be included in the quoted rate of above item. (ii) For payment purposes total length from pole to pole shall be considered as "Each Job for Each Span".
Re-routing and re-laying of HT 11 KV UG cable in trenches with necessary connection and disconnection for re-distribution of load of 33/11KV power transformer including taking out of existing cable, necessary extension of cable (where required & ordered), complete in all respects as specified and directed. Note:- Excavation, returning filling, removing, sand cushioning, protection covers, protection pipe, extra quantity of UG cable, cable jointing kits will be measured and paid separately under relevant items.
Dismantling, collecting and depositing of HT/LT switch gears, transformers, VCBs including transporting from different Sub Station to MES Store Yard as directed with necessary arrangement of heavy load lifting hydra and transportation by vehicle and cleaning of Sub Station, all as directed by Engr-in- charge. Notes:- (a) Dismantling of unserviceable items from foundation etc and carrying all shall also be deemed to be included in the quoted rate. (b) For heavy unserviceable items, dismantling in stages/ parts/ piecemeal and lifting, carrying all shall also be deemed to be included in quoted rate.
M&L for carrying out repair to the 11 KV, 400 Amps, Outdoor type, Gang Operated, Air Break Switch by replacing unserviceable spares like flexible jumper, closing handle, brass connections, clamps, bolt, nuts etc including necessary cleaning, applying grease and all other relevant works to make the Air Break Switch fully functional, complete all as specified and directed.
S &Fin repair post type, polymer insulator including Borron free ECR FRP rod with silicon rubber, two GI washers and one iron nut, 150mm height, 150mm dia for 11000 Volts grade complete all as specified and as directed
Cleaning of insulators any type with necessary cleaning agent, complete all as specified and directed.
M/S DAWN ELECTRICAL INDUSTRIES
MS ORIENT ENGINEERING WORKS
R N SAH N CO
KARMIBRINDA
Damdoo Bhutia
KAMLESH ENTERPRISE
GEETA CONSTRUCTION
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .