GE I R and D Kanchanbagh
GE I R and D Kanchanbagh Kanchanbagh Post Hyderabad 500058
REPAIR/REPLACEMENT OF UNSV CABLES ,HT VCB S/SF6 BREAKERS MAINTENANCE POWER/DISTRIBUTION TRANSFORMER ,LT/HT SWITCH GEAR PANELS AND ITS CONNECTED ACCESSORIES AT DLRL KANCHANBAGH, HYDERABAD
2024_MES_654776_1
8781/E8
Open Tender
Civil Works
Item Rate
270 days
Hyderabad
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE I R and D Kanchanbagh
₹98,000
Yes
19 Jul 2024
18 May 2024
10 Jun 2024
18 May 2024
7 Jun 2024
1 Jun 2024
18 May 2024 - 25 May 2024
Amount
Testing and setting the relays of incoming VCB's/SF6s of 33 KV by primary injection method of any make/model mechanical parts, cleaning inside & outside with CRC-26 spray including replacing the unserviceable minor parts like springs, gear, nuts, bolts and washers, internal wiring if necessary and lubricating all the complete to the entire specification of Engr-in-charge.
Testing and setting the relays of incoming VCB's/SF6s of 11KV by primary injection method of any make/model mechanical parts, cleaning inside & outside with CRC-26 spray including replacing the unserviceable minor parts like springs, gear, nuts, bolts and washers, internal wiring if necessary and lubricating all the complete to the entire specification of Engr-in-charge.
Disconnecting and removing the unserviceable 33 KV burnt out six bolt clamps and supply and fixing new six bolt type Aluminium clamps suitable for panther aluminium jumpers / pipes including nuts, bolts, washers and testing complete all as specified and directed.
Dehydration and filtration of 2.5 MVA transformer oil 33/11 KVA and indoor/outdoor/ isolation type at different location and different size of transformer from 63 KVA to 1000 KVA or any capacity Transoformers at DLRL location with centrifuging machine, manually operated and achieve BDV 60 KV including carrying out oil testing before and after the dehydration process for each transfarmer complete all as directed. Note : Required oil for top up will be measured and paid separately under relevant item of schedule
Supply only topping up of Transformer oil as per IS :335, break down voltage not less than 60 KV all as specified and directed. Make :- Power Oil/Electrol/ Servo
Supplying, installation, commissioning and testing in replacement of 33 KV Current Transformer (CT`s), indoor type, resin cast epoxy type, of 13.1 KA/Sec having ratio 40/5-5 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering including associated wiring complete all as specified and directed.
Testing & setting 11 KV current transformer by primery injuction method complete all as specified and directed.
Supplying, installation, commissioning and testing in replacement of 11 KV Current Transformer (CT`s), indoor type, resin cast epoxy type, of 13.1 KA/Sec having ratio 150-75/5-5-1A Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering including associated wiring complete all as specified and directed
S&F in repairs copper Bus Bar 10 X 70 MM with HT Tape as Per Required Design & Dimensions with NUT BOLTS SET including fixing charges all as directed.
Supply, laying, testing and commissioning in trenches/ ducts, fixed on walls/panels of LTUG cable, 1100 volts grade, PVC insulated, PVC unsheathed armoured with aluminum conductor cable complete including lugs of requied sizes for the following nominal cross sectional areas of cables including taking down old unserviceable cable complete all as directed:- Make: HAVELL'S/UNIVERSAL/CCI/GLOSTER/KEI/ POLYCAB/ KEC INTERNATIONAL (RPG)
3.5 core x 50 Sqmm
3.5 core x 70Sqmm
3.5 core x 95 Sqmm
3.5 core x 120 Sqmm
M&L for Servicing & Repairs to Air-break switch (isolator) off load, rotating type, 33 KV, 800 Amps to 1250 Amps capacity, with proper alignment of isolator rotating blades, with fixed contact jaws, arcing horns, applying petroleum jelly to moving mechanism, cleaning and lubricating to isolator gear box assembly, tightening all nuts, bolts and clamps of jumpers etc, repairing to isolator gear box assembly and making in proper serviceable condition for smooth functioning, testing and commissioning on load complete all as specified and directed.
S&F in replacement of LED indication lamp for breaker ON/OFF/TRIP/Breaker Spring Charged/R-Y-B etc for 11/33 KV (110V/30V DC supply) control panel including associated wiring, complete all as specified and directed.
Supply, Lay cable 1100 volts with PVC insulated and steel armoured with multi stranded copper conductor of the sizes 16 core 2.5 Sq mm.
M & L for cutting and removing grass, vegetation bushes etc from surrounding HT installation as bushes grows during a period of contract and removing all rubbish to a distance not exceeding 50 m as directed.
M&L for Repairs/maintenance of 11KV HT VCB/SF6 breakers Panel including bus coupler of any type, size and capacity complete including the following :- Taking out 11KV HT VCB/SF6 breakers of 400/630/800 Amps rating trolley from HT Panel after switching off electric supply, checking of mechanical/motorised system for proper functioning of upward/downward movement of HT VCB trolley including opening the VCB & checking the quality of insulating. Cleaning & servicing the fixed/moving contact & blowing out dust from bus bar chamber, spout gear mechanism and applying the proper lubrication/greasing and cleaning/servicing the entire motorised mechanism of VCB including all spare parts required at site, reassembling the VCB connection, testing, commissioning and putting on load to the entire satisfaction of Engr-in-charge.
Supply & Fix Gasket in replacement for upto 2.5 MVA transformer (SRC RC 70C Grade) with including all required T&P for drain out and refilling trainsformer oil after proper filteration,comminissioning and testing complete complete all as directed.
All as per item no 16 above Gasket replacement upto 800 KVA transformer (SRC RC 70C Grade)
Supply installing testing and commissioning in replacement the relay module Micom P111 making necessary cutting in the existing panel and necessary control wiring FRLS of size not less than 2.5Sqmm and providing Ferules for identification and necessary spares for fixing complete to the entire satisfaction of the Engr-in-Charge.
Testing and re-setting and calibration of protection relay of 11 KV RMU/VCBs/SF6 breaker (indoor/outdoor) for incoming and out going feeders with control panel and control cable differential relay through authorised service engineer, Checking of instruments function and taking corrective action for improvement if found improper, functioning complete all as specified and directed.
M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm including takin down old joint.
M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm including takin down old joint.
M&L for XLPE cable jointing kit for 11 KV (earthed) for outdoor termination heat shrink type joint complete with jointing material & accessories suitable for 240 to 300 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed.
M&L for XLPE cable jointing kit for 11 KV (earthed) for indoor termination heat shrink type joint complete with jointing material & accessories suitable for 120 to 185 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed.
M&L for XLPE cable jointing kit for 11 KV (earthed) for indoor termination heat shrink type joint complete with jointing material & accessories suitable for 50 to 95 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed.
Supply, fix, testing and commissioning of Air break gang operated switch, triple pole mechanically operated out door type with all fittings/accessories mounted on and including 11 KV HT polymeric insulators and steel channel frame, GI operating rod 25 mm dia of suitable length with operating mechanism worked from ground level vertically operated including locking arrangement for operating handle with and including 7 levers Navtal lock complete suitable for current rating of 400 Amps HT 11 KV working pressure all as specified and directed.
Supply, laying, testing and commissioning in trenches/ ducts of HT UG cables 3 core,size of 95 sq mm, 33000 volts grade, PVC insulated, PVC unsheathed armoured with aluminum conductor cable complete including lugs of requied sizes for the following nominal cross sectional areas of cables including taking down old unserviceable cable complete all as directed:- Make: HAVELL'S/UNIVERSAL/CCI/GLOSTER/KEI/ POLYCAB/ KEC INTERNATIONAL (RPG)
All as per item no.27 but size of 185 sq mm
All as per item no.27 but size of 240 sq mm
Isolate,disconnect,dismantle the burnt out lugs from main switches/MCCB and crimping with new lugs as per existing one including fixing, insulation, termination to main switch/MCCB for the following sizes of cables complete all as directed .
35 sqmm to 50 sqmm
70 sqmm to 95 sqmm
120 sqmm to 240 sqmm
240 sqmm to 300 sqmm
M&L for Preparation of old painted inner/outer surfaces of indoor/out door HT/LT panels, spray painting the same with two coat of synthetic enamel paint(RAC 7032) simens grey to achive smooth finish including writing of SM/MES No complete all as directed.
Supply and fix in repairs of Alarm annucator 12 window of model MBAS-0600 suitable for 33/11KV HT breaker complete all specified and directed.
S&F cable jointing kit for straight through joint (epoxy) for 1.1 KV grade XLPE, PVC insulated and sheathed aluminium conductor under ground cable including thimbles, nuts & bolts, washers etc and testing after jointing complete, all as directed for the following sizes. Make: M-seal/Raychem/Transeal/Denson
upto 16 sqmm 4 core
25 sqmm to 50 sqmm 3.5 core
70 sqmm to 120 sqmm 3.5 core
Material and labour painting of HT two pole structure 11 KV complete by scrapping the existing old paint and making the surfaces smooth including cross arms bracings complete and applying two coats of synthetic aluminium paint complete all as specified and directed.
All as per Item No: 33 above but four/Six pole structure Make of Paint for item No. 33 & 34 : Asian/Nerolac/Berger
All as per item no.33 above but 33/11 KV Incoming breking,incoming structure yard and GOD's operated devices for whole structure.
Labour for cutting the bushes and plants grown near the substation/ structures premises using necessary tools and plants and removing the plants from the root level at any depth and cleaning the premises completely and making good the site suitable for spreading the stone aggregate including disposing all the waste to a distance not exc 50M form the site all as directed by the Engr-in-Charge.
Pin type, porcelain, vitreous, white,brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 50mm height, 65/100mm dia for 550 volts grade complete all as directed.
M&L in replacement of Shackle Type insulator 1100V 100mm hight 115 mm dia same as per existing complete.
Cutting of trees and tree branches of girth up to 20cm and to a radius of 3M all around LT/HT OH line complete all as directed. Note: The distance between two adjacent poles will be considered as one span.
M&L 11KV grade pin type, composite polymeric insulator insulator of clevis/Tounge/socket or ball type spindle including nuts and bolts of size type as specified by the manufacturer conforming IS- 61109 including all galvanised steel disc fittings as required at site and removing of unserviceable insulators complete all as specified and directed. Make :- Jaipuria/Rashtriya Electrical/Denson or make approved in the state Electricity board
M&L 11KV grade suspenction type, composite polymeric insulator insulator of clevis/Tounge/socket or ball type spindle including nuts and bolts of size type as specified by the manufacturer conforming IS- 61109 including all galvanised steel disc fittings as required at site and removing of unserviceable insulators complete all as specified and directed. Make :- Jaipuria/Rashtriya Electrical/Denson or make approved in the state Electricity board
M&L in replacement horn gap fuse assembly mounted on porcelan insulator and steel frame, D or Channel type for HT 11 KV, 400Amps rated current including base frame made with 'C' channel cross arms of suitable size shall be robust enough to sustain the various stresses encountered during all operational conditions of the cutout and necessary reconnecting all the wires/cables etc including removing the unserviceable drop out fuse assembly complete all as specified. Note: Fuse assembly for three phases will be considered as one Set.
M&L in replacement of Lightning arrester expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo Amp connecting to the earth strip including necessary fixing spares as required at site all as specified and directed. Note: A set of three lightening arresters will be considered as one set suitable for 11000 voltas.
Repairs to AB switch (GOD) including replacement of male and female contacts, bolts & nuts and cleaning the carbon/ dust deposited on the switch contact surfaces and applying mineral jelly, oil grease to the moving/rotating parts etc after cleaning, removing carbon deposits including testing and commissioning the same for operation complete all as directed by Engr-in-charge. Note: The repairs to three poles of AB switch will be measured as on job.
Material and labour for locating UG cable fault through high voltage UG cable testing van through TSSPDCL or any authorised service provider in HT cables of any size or distance complete all as specified and directed to the entire satisfaction of Engr-in-Charge.
Material and labour for tracing the cable route using ultra sonic cable route locator of any HT/LT UG cables complete all as specified and directed.
Supply and fix Impluse Emergency First aid kit box with basic medicine like Band Aid strips of min 20 Nos, Anteseptic cream, Cotton, Surgical tape 1 inch, non sterial gauge swabs, Hydrogen peroxide bottle, medical spirit bottle complete all as specified and directed.
Disconnectiong and taking down the unserviceable gang operationed device unit of 33 KV complete from the structure for repairing including replacement Male contacts/movingg contact blads (set of 3) Female contacts/fixed contacts (set of 3) Tinned copper flexible jumpers and applying mineral jelly oil grease after proper removal of carbon deposit and refixing of switch AB gang operated triple pole mechanically operated mounted on isolator and steel frame with operating mechanism worked from ground level from current rating upto 800 A,33 KV grade horizontal/vertical type complete all as directed all as directed by Engineering-in- charge.
Supply and fix pad 4 hole/6 hole clamps,pipe clamps suitable size for 33KV jumper in structure.
Material and Labour for cutting existing BT road/PCC of size 45cm x 60cm for taking out/laying of underground cable and including necessary earth work and refilling the same in layers well ramming including watering as required and matching with the existing surface with 200mm thick PCC 1:2:4 type B1 and curing the same with wet gunny bags and removing debris to a distance not less than 50m complete all as specified and directed.
Supply and lay GI tubing 100mm dia, light grade for cable protection at road crossing/on poles and tubing sealed at both ends after laying the cables including taking out old GI tubing complete all as directed.
All as per iem No 51 here-in-before but 80mm dia Make for item Nos.51 & 52: ZENITH/ TATA/ JINDAL/SWASTIC
S&F in repairs MCCB 200 Amps, 4 pole 50 HZ, complete all as directed.
S&F in repairs MCCB 100 Amps, 4 pole 50 HZ, complete all as directed.
S&F in repairs MCCB 125 Amps, 4 pole 50 HZ, complete all as directed.
Opening of the 11 KV / 0.433 KV transformer 160 KVA to 1000 KVA by removing the inspection cover / top cover, decanning of the transformer oil up to the required level for replacement of leaked cork seal with insulator or LT/HT bush (which is unsv) complete from the shell and making again connections of LT/HT bush to avoid leakage of oil refilling back to existing oil into the transformer testing & commissioning complete all as directed Note : HT/LT bush will measured and paid separately under relevant item and cork seal with insulator is deemed to be included in quoted rate.
M&L for opening the top of Transformer upto 2.5 KVA for renewal of jumpering (with brazing or welding) with new copper wire of existing size after removal of burnt out internal copper links from winding top to studs including decanning of oil upto required level and testing the tranformer complete all as directed.
M&L Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick, buried directly and preferably vertically in ground ( earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanised iron strip of 25x4mm (upto 7.5 M in length from earth plate) by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 5, connected to earthing test point all as specified including earth work and excavation in any type of soil, PCC 1:3:6 type C1 chamber and RCC 1:2:4 type B1 cover 40 mm thick, with 8 mm dia steel deformed (TMT bars) reinforcement at 150mm c/c both ways, 40 mm dia GI light grade pipe for earth lead protection, 20 mm dia GI light grade pipe for watering , water funnel, testing point etc., complete all as specified and testing on completion.
M&L for common salt to fil in existing earthing pit to recharge the pit all as specified and directed.
Supply & lying in repairing for 2 core round flexi copper wire of 1sqmm dia for AC/DC supply connections to VCBs/SF6 with suitable size glandsand insulated lugs of required qty complete all as directed.
Testing protection by secondary injection method and other relays such as IDMT, Over current earth fault relays, auxilary relays, such as VAJ 10C & VATH relays provided on 33 KV Breakers and servicing of relays complete all as directed.
Testing and calibration of protection Over current and Earth Fault relays numerical type P-111/123 complete all as directed.
Testing and calibration conducting stability test of transformer 33/11 Differential relay complete all as directed.
M&L for factory repairing reconditioning of by authorised service workshop 11 KV Sulphur Hexafluoride breaker defective pole assembly of type 63D, KEC make including Gas Charging (SF6) and testing and commissioning complete all as directed. Note:- Quoted rates deemed to including transport material required FRP links Gas Rings,Membrane,Aluminium Silicate,Mesh box,Pressure switch& filling of Gas
Charges for fixing for SF6 pole assembly to the breaker after repair and testing of breaker and charging at site including packing Note :-Nature of work Assembly of poles Assembly replacment of pole AssemblyGas filling and testing.
M & L for Inspection and servicing of OLTC of transformer of capacity 1.5 MVA and checking the electrical/manual operation of tap changer mechanism, check the integrity of the active components /contact surface mating for all tap positions, voltage ratio test for all tap position etc including cleaning of the OLTC complete all as directed. Note : The Contrator shall be responsible for correct servicing of the OLTC and servicing to be done through OEM of OLTC.
Supply and fix in repairs wiring and commissioning including thormostate switch space heater 200w for VCB/SF6 breaker/RMU complete all as directed.
M&L for repairs servicing CT/PT wiring with required material all as directed.
Supply and fix 11 KV voltage transformer (Potional Transformer) Ratio1100/110Volts- V3 complete wiring testing and commissioning complete all as per directed.
S&F Tripping coils for sulphur hexafluoride (SF6) breakers operated on 30/110Volts DC including taking down old unserviceable coil complete all as directed.
Supply and installation of Spring Charging Motor for breaker including taking down of old Unserviceable spring charging motor complete all as directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in soft loose soil for foundation of poles, structures, stay rods, laying of underground cable etc complete all as directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers each not exceeding 25cm thick using soil complete all as directed.
Removing excavated surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as directed.
Supply and spreading of natural, clean, dry, river sand in trenches for cable protection / transformer yard/ two pole structure yard complete all as directed. Note:- Punned thickness only shall be measured for payment purpose.
Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 250mm x 150mm x 40mm lete all as directed.
M&L for opening the top of Transformer upto 1000 KVA for renewal of jumpering (with brazing or welding) with new copper wire of existing size after removal of burnt out jumpering including decanning of oil upto required level and testing the tranformer complete all as directed.
S&F in repairs Silica gel complete all as directed.
Making Primery/Secondary coil with insulating copper wire of required gauge craft paper cotton tape HT/LT insulation as per specification of old transformer including making of coil as required of any capacity of transformer of any voltage and range including transportation and all as specified and directed.
S&F earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 2mm dia galvanised iron or steel wire of 25x4mm galvanised iron strip including taking down old Conductor.
hari enterprises
Maruthi international
vvcenterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .