| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.4 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹21.4 L+₹26,405 (1.25%)Rejected-AOC 217 ARHAT BAZAR KASAULI DISTT SOLAN HP 173204 | SOLAN | HIMACHAL PRADESH | 173204 | L2 | Rejected-AOC Other than lowest Bidder |
Tender Value
₹21.5 L
EMD Value
₹43,000
Closing Date
3 Mar 2020, 6:00 pmClosed
CWE(AF) CHANDIGARH
HQ CWE(AF) CHANDIGARH 160 003
REPAIR TO WATER SUPPLY INSTALLATION, PUMPING SET, DG SET, EXTERNAL ELECTRIFICATION AND COOLING/HEATING APPLIANCES AT AIR FORCE STATION KASAULI UNDER GE (AF) CHANDIGARH
2020_MES_320823_1
CWE/AF CHD/CHD/T-43/2019-2020
Open Tender
Civil Works
Item Rate
275 days
KASAULI
As per NIT
8 documents required · 8 mandatory
₹500
GE(AF) CHANDIGARH
₹43,000
Yes
19 Mar 2020
1 Feb 2020
9 Mar 2020
1 Feb 2020
3 Mar 2020
19 Feb 2020
Amount
SECURITY LIGHTS
Disconnecting and taking down of any type of street light fitting from pole for checking and repairing, and replacement of unserviceable wiring, holders , ballasts and lamps etc., re-assembling and refixing on the same location, complete all as specified and directed. Note :- Supply only of spare parts like ballast , holder and lamps, cables etc. shall be measured and paid separately.
Supply and fix in repair LED driver complete suitable for 60 watt LED street light all as specified and directed.
Supply and fix in repair LED driver complete suitable for 120 watt LED street light all as specified and directed.
Supply and fix in repair, Air termination, single pointed aluminium rod 12mm dia and 300mm long fixed with GI pipe bracket, complete all as specified and directed.
Supply & fix, in replacement, bracket 1.20m long, bent to shape at 120 degree out of GI pipe light grade 32mm dia bore, fixing on top of pole with appropriate size bolts, nuts, washers and MS clamp made out of FI 50x6mm, complete all as specified and directed.
Supply and fix in repair, FRP junction box, of suitable size, comprising of 01 No. MCB, SP, 10 Amps, 240volts, 10KA, 'C' Series for each street light with 02 Nos. bus bar of aluminium strips not less than 25mmx3mm duly shrouded/insulated including necessary MS clamps, nuts and bolts, washers etc for fixing, complete all as specified and directed.
Excavation in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth as in hard/dense soil for foundation of poles, stay assembly or laying of cables, water supply pipes etc and getting out, complete all as specified and directed.
Excavation in trenches, not exceeding 1.5m wide and exceeding 1.5m but n.exc 3.0m in depth as in soft/disintegrated rock soil for foundation and getting out, complete all as specified and directed.
Returning, filling in excavated approved soil, including spreading, leveling, and well ramming in layers not exceeding 25cm each, complete all as specified and directed.
Removal of excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point, complete all as specified and directed.
Material and labour, sand cushioning with a layer of dry river sand 80mm thick before laying of cable and 150mm thick (punned down to 100mm) after laying of cables, in trenches/ducts, complete all as specified and directed. Note : Punned down thickness (overall 18cm) shall be measured and paid.
Material and labour, locally available, sub class `B’ bricks (old size), laid flat and dry adjacent to each other, length perpendicular to the direction of cable run, in trenches over the cable for protection, complete all as specified and directed.
Supply and fixing in position, galvanised iron tubes 50mm dia bore, light grade, for protection of cable under floor or road and on wall/pole fixed in replacement, complete all as specified and directed.
Supply, laying, jointing, testing and commissioining of XLPE insulated, armoured, heavy duty electric power under ground LT cable with stranded aluminium conductor, 1100 volts grade, of size 10Sqmm nominal cross section x 2 core, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs, complete all as specified and directed. Note : Excavation and earth work, sand cushioning and protection covers shall be measured and paid separately.
All as per item No. 1.14 but size 16 Sqmm x 2 core
All as per item No. 1.14 but size 16 Sqmm x 4 core
All as per item No. 1.14 but size 25 Sqmm x 3.5 core
All as per item No. 1.14 but size 35 Sqmm x 3.5 core
All as per item No. 1.14 but size 50 Sqmm x 3.5 core
All as per item No. 1.14 but size 120 Sqmm x 3.5 core
Taking out old unserviceable ground cable of any size from trenches, pipes, on pole etc., complete all as specified and directed.
Cutting bituminous road/path (maximum width 45 cm) for passing of GI pipes and making good to the cut surfaces and material and labour concreting with PCC 1:3:6 type C-2 (using 20mm graded crushed stone aggregate) to match with adjoining surfaces including well campaction manually with durmat and watering of the backfill complete all as specified and directed. Note : Only layers of Road (Carpet, WBM & sub-base) shall be measured under this item and earthing beneath shall be measured and paid separately).
Material and labour, earth continuity conductor or main earthing lead or lightning conductor, 25x3.15mm Aluminium strip, fixed to wall/roof on batten with saddles and fixing screws, PVC/ Porcelain/epoxy insulators etc. or recessed or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required, fixed in repair complete all as specified and directed.
Material and labour, test point terminal block made of gun metal or phosphorus bronze or copper, size 75mmx75mmx25mm, drilled and screwed including 3 nos. 8mm dia 25mm long hexagonal head screws, complete all as specified and directed.
Material and labour, earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick burried directly in ground vertically at a depth not less than 2.25m below normal ground level with top edge of earth plate not less than 1.5m below normal ground level, earth plate surrounded from all sides by 15cm thick packed alternate layers of charcoal dust and common salt, electrode connections using galvanized iron strip of size 32mm x 6 mm thick (upto body of equipment) by means of nuts, bolts, check nuts & GI washers connected to main switch board or main control board or test point, protected by galvanized iron pipe light grade 40mm dia bore, and watering pipe 20mm dia bore GI light grade with funnel & wire mesh including all necessary excavation & earth work, PCC chamber in PCC (1:2:4) type B-1, RCC cover, all as shown in electrical plate No 3 of MES Schedule Part-I (2009), testing on completion, including taking out old u/s earthing materials complete all as specified and directed. Note(s) :- (i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with XPM not less than 4Kg/Sqm. (ii) PCC chamber shall be constructed 500 mm away from the edge of earth pit. (iii) Rate shall include GI strip and protection pipe of length 7.5m, excess beyond 7.5m length required at site shall be measured and paid separately. (iv) Earth resistance shall be less than 3Ohm. In case test results are not found below 3Ohm, complete earthing will be re-done without any extra cost to Govt.
Supply and fixing in replacement, Solar street light panel assembly complete with flat plate, collector box, absorber, etc suitable for 30 watt LED street light, complete all as specified and directed.
Supply and fixing in replacement Solar street light Automatic dusk to dawn controller (DTDC) assembly suitable for 30 watt LED street light
Supply and fixing in replacement Solar flat plate collector made of toughened glass 4 mm thick and suitable for collector box Solar water heating system of 1.2mx1.0m size as per IS: 12933/2003 with specified solar transmittance minimum 82 percent at near normal incidence complete all as specified and directed.
Supply and fixing in replacement Aluminium Solar collector box made of aluminium sheet 1.6mm thick for sides of the box, bottom sheet of 0.7 mm thick, support 1.2mm thick for retaining of glass and body sheet 1 mm thick all as per sec-2 of IS:12933, Pt-2/2003, complete all as specified and directed.
Supply and fixing in replacement Solar absorber assembly made of copper tube 0.71mm thick and 25mm diameter for header and copper tube 0.56 mm thick and 13mm diameter for riser all as per sec-3 of IS:12933, Pt-2/2003 and suitable for working pressure upto 24.5 Kpa complete all as specified and directed.
Servicing of solar water heating system of 100 LPD capacity by cleaning of solar plate collector, copper brazing to arrest leakages of header and riser assemblies, brazing/riveting to collector box disturbed parts to make it in original position, descaling of tubes and tanks complete all as specified and directed by Engr-in-Charge.
All as per Srl item No. 1.31 here-in-before but, Solar water heating system of 200 LPD capacity
All as per Srl item No. 1.31 here-in-before but, Solar water heating system of 300 LPD capacity
Supply and fix in replacement ammeter panel mounted type 0-200 Amps range suitable for 415 volts, 3 phase, 50 Hz electric supply alongwith CTs, complete all as specified and directed.
Supply and fix in replacement voltmeter panel mounted type 0-500 volts range suitable for 415 volts, 3 phase, 50 Hz electirc supply, complete all as specified and directed.
Supply and fix in replacemnt indication lamp LED with colour glowing red, yellow and blue for panel mounting complete all as specified and directed.
Supply and fix, Tap changer assy of 11/0.433 KV transformer upto 250KVA including connection sleeves, insulated plates, nut, bolts & washers and testing including taking out old and removal, complete all as specified and directed.
Supply and fix in repairs HV insulator with studs nut & washers suitable for 11 KV/433V HV side of transformer 100 KVA to 150 KVA, complete all as specified and directed..
All as per item No. 1.39 here-in-before above but 200 KVA to 250 KVA Transformer
Supply and fix in repairs LV insulator with studs nut & washers suitable for 11 KV/433 V LV side of transformer of capacity 100 KVA to 150 KVA, complete all as specified and directed.
All per item No. 1.41 here-in-before but 250 KVA to 400 KVA transformer
Supply and fix, heavy duty breather assembly of capacity 0.5kg with silica gel cristal, including taking out old and removal, complete all as specified and directed.
Balancing of load on three phases and neutral of transformer by applying necessary engineering efforts like interchaging of jumpers, interchanging of service connections on over head conductors, in LT feeder pillar boxes or any other such efforts to make a balanced distributions of electrical load on transformer all as directed and required as per site conditions including submission of corrected readings of meters, complete all as specified and directed. Note : The unit rate quoted will include the cost of labour and necessary tools, safety devices and plants etc as required for the purpose.
Material and labour for construction of PCC earth chamber with cement concrete (1:3:6) type C-1 using 20mm graded crushed stone aggregate including necessary form work, demolition of old unserviceable earthing chambers and dispossing off debris outside MoD land, complete all as specified and directed.
Material and labour, RCC (1:2:4) type B-1 using 20mm graded crushed stone aggregate as in covers for earthing chamber reinforced with 8mm dia mild steel TMT bars both ways @ 100mm c/c, provided with lifting hook made out of 8mm dia bar including necessary form work, demolition of old RCC earth pit cover and dispossing off debris outside MoD land, complete all as specified and directed.
Supply, laying, jointing, testing and commissioning, HT cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminum conductor, of size 3 core 70Sqmm, 11000volts grade, laid in trenches/through pipes under road, floor/on wall/on pole or any other indicated place, including taking out old and removal, complete all as specified and directed. Note : Excavation and earth work, sand cushioning and protection covers shall be measured and paid separately.
Material and labour, cable jointing kit, outdoor end termination, heat shrink type, complete with jointing material and accessories, suitable for 11KV (earthed) grade 3 core XLPE aromoured aluminium conductor cable of size 50Sqmm to 95Sqmm, complete all as specified and directed.
Material and labour, cable jointing kit, indoor end termination, heat shrink type, complete with jointing material and accessories, suitable for 11KV (earthed) grade 3 core XLPE aromoured aluminium conductor cable of size 50Sqmm to 95Sqmm, complete all as specified and directed.
Supply and fixing in repair LED 25 to 40W post top lantern with aluminium die cast housing cum heat sinnk in IP 65 protection including all fixing arrangements, complete all as specified and directed.
Material and labour, pin type insulator porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, of 150mm height and 150mm dia, for working pressure 11000volts grade, fixed in position, including taking out old and removal, complete all as specified and directed.
Material and labour, disc type insulator, porcelain, vitreous, 145mm high and 255mm dia, ball and socket type, white, brown or green, single disc assembly for tension with tension clamps for conductors, working pressure 11000volts, fixed in position, including taking out old and removal, complete all as specified and directed.
Materia and labour, switch air break, triple pole, gang operated, mechanically operated, mounted on insulators and steel frame, with operating mechanism worked from ground level, for current rating upto 400Amps suitable for 11000 volts grade, AC supply including taking down old unserviceable & removal, complete all as specified and directed.
Material and labour, drop out expulsion fuse, single pole, suitable for 11000 volts grade, AC supply, upto 50Amps including taking down old unserviceable & removal, complete all as specified and directed.
Material and labour, repairing/overhauling of air break switch triple pole, and DO fuse unit upto 400 Amps capacity, 11KV, mechanically operated, mounted on insulators and steel frame, installed vertically/horizontally, including replacement of broken/worn-out components, oiling and greasing of mechanical moving parts, smoothening and polishing of electric contacts and applying conducting jelly to contacts and testing after repair, complete all as specified and directed. Note: New components to replace worn out components/ insulators will be measured and paid separately under respective items as supply only.
Cutting & trimming tree branches along HT/LT over head lines after arranging shut down and by taking all precautions while working on lines, clearing of area, etc by employing sufficient labourers, T&P and safety measures required for the purpose, complete all as specified and directed. Notes : (i) The unit rate will include disposing off rubbish to nearest waste disposing point of concerned area.
Taking down over head conductor/GI earth wire, of any size and type, after untying binding wire from insulators/cross arms and restringing to achieve permissible sag limit of over head line including supplying new binding wire of proper size, complete all as specified and directed.
Dehydration of HV/EHV grade transformer oil (On line/off line), minimum three cycles to achieve dielectric strength upto 60KV for EHV grade and upto 40 KV for HV grade, complete all as specified and directed. Note - Centrifuging Machine with all T&P & testing eqpt required for dehydration to be arranged by contractor at actual installation of the transformer.
Supply and filling, transformer oil EHV grade as per IS-335 of 1993 Part-II, in sealed drum of 200litre, complete in replacement all as specified and directed.
Material and labour, painting of steel pole upto 9m length including cross arms, clamps of any length and shape, for HT over head line, with two coats of aluminium paint including preparation of the existing surface including marking pole numbers in a 20cm dia yellow circle and marking three black & two yellow bands each of width 30cm by fluorescent paint, from bottom of pole to 1.5m height, complete all as specified and directed.
Material and labour, painting of two pole structure consisting of 11m long steel poles including cross arms, clamps of any length and shape, for HT over head line, with two coats of aluminium paint including preparation of the existing surface including marking pole numbers in a 20cm dia yellow circle and marking three black & two yellow bands of width 30cm by fluorescent paint, from bottom of pole to 1.5m height, complete all as specified and directed.
Material and labour, Pin type, porcelain, vitreous, white, brown or green insulator, 50mm height, 65mm dia for 550 volts grade, AC supply, alongwith one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut, including taking down old and removal, complete all as specified and directed.
Material and Labour for PCC 1:4:8 type D-2 using 40mm graded stone aggregate for foundation filling, complete all as specified and directed.
Material and Labour for PCC 1:3:6 type C-2 using 40mm graded stone aggregate for foundation filling, complete all as specified and directed.
Material and Labour for PCC 1:2:4 type B-1 using 20mm graded stone aggregate for coping incuding necessary form work, complete all as specified and directed.
Supply and fixing/erecting in repair true vertical position, steel tubular pole, swaged, type 410-SP-22 (8.5m long), LT, complete with cast iron base plate of size 300mmx300mm, finial taper plug, bolts, nuts, washer and screws including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to portion embedded in PCC including numbering of poles with two coats of synthetic enamel paints, complete all as specified and directed. Note : Earth work and PCC shall be measured and paid separately.
Taking out, existing transformer from the site to workshop (approved by GE) and from workshop to the site, cutting the old existing winding, Taking out, core from transformer and rewinding the transformer by using super enamelled copper wire of appropriate size (copper wire shall be measured and paid for separately as supply only) including packing material such as latherised paper, cotton tape, varnishing and ovening the core for transformer and refixing the same in position after repair including all connections and testing for transformer of capacity 250 KVA, complete all as specified and directed. Notes:- (i) Any damage if occurred during the process of handling the transformer will be made good by contractor at no extra cost. (ii) Any defective part required to be replaced shall be measured & paid as 'Supply and fix' separately. (iii) Transformer should be repaired within 05 days after receiving message from Engr-in-charge, if the transformer is not repaired within time, the penalty of Rs. 2500.00 per hour shall be recovered from the contractor.
Demolition of PCC in foundation, dismantling and taking out old LT feeder pillar box/panle including accessories and removing the same, complete all as specified and directed.
Supply and fixing in replacement, puff insulated stainless steel hot water storage tank of material 316 grade stainless powder coated GI sheet with inlet and outlet water connection for capacity 100LPD, complete all as specified and directed.
Supply and fixing automatic street light switch using NATURE SWITCH for automatic switching of street lights based on LUX level of natural light. The sensor (Nature switch) alongwith suitable power contactor, MCB and support terminals should be enclosed in pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR grade special moulding compound confirming to IP 54. Contactor, MCB and circuit wiring should be suitable enough to take load of 12KW equally distributed over 3 Phase (4KW/phase). Contactor rating 40Amps, 4pole, MCB rating 40Amps sinngle pole-03 nos and wirinng for main load with 6Sqmm copper connductor FR grade cable, complete all as specified and directed. Make:- Swadeep02EC12kW3P of Kakatiya Energy systems Pvt Ltd/L&T/Schneider
Supply and fixing in repair garden light fittinngs 9 to 12W LED bollard with soft 360 degree light IP-65 protection, resistant to corrosion better optics for uniform distribution includinh all fixinng arrangements, complete all as specified and directed.
Supply and fixing PVC spacer bar for four overhead conductor with locking arrangements with each conductor, complete all as specified and directed.
Supply and fixing PVC spacer bar for five overhead conductor with locking arrangements with each conductor, complete all as specified and directed.
EXTERNAL WATER SUPPLY WORKS
Supply and fix, fire hydrants 65mm dia with single flanged end, inlet flanges as per IS : 5290 and instantaneous female outlet with blank cap, screwed in bonnet inside screw, rising stem, with gland packing, including taking out old and removal, complete all as specified and directed.
Supply and fix, steel water tubing of 25mm dia bore, medium grade, galvanised, with all standard fittings, laid in trenches, complete all as specified and directed. Note : Excavation & earth work as required will be measured and paid separately
All as per Srl item No. 2.02 here-in-before but 40mm bore
All as per Srl item No. 2.02 here-in-before but 50mm bore
All as per Srl item No. 2.02 here-in-before but 80mm bore
All as per Srl item No. 2.02 here-in-before but 100mm bore
Supply and fix, steel water tubing of 15mm dia bore, medium grade, galvanised, with all standard fittings, fixed to walls and ceilings, complete all as specified and directed.
All as per Srl item No. 2.07 here-in-before but 20mm dia bore
All as per Srl item No. 2.07 here-in-before but 25mm dia bore
All as per Srl item No. 2.07 here-in-before but 40mm dia bore
Taking up or down steel tubing 15mm dia bore and connections, including cleaning for re-fixing or removal to store or for credit, complete all as specified and directed. Note : Excavation & earth work as required will be measured and paid separately.
All as per Srl item No. 2.11 here-in-before but 20mm dia bore
All as per Srl item No. 2.11 here-in-before but 25mm dia bore
All as per Srl item No. 2.11 here-in-before but 40 to 50mm dia bore.
All as per Srl item No. 2.11 here-in-before but 80 to 100mm dia bore.
Cleaning and removing all scale and dirt, etc from water tanks of capacity 5000ltrs, from mouths of circulating pipes and cleaning surrounding area of tanks upto 3.0m width all around, complete all as specified and directed.
Cleaning and removing all scale/sludge and dirt from RCC semi under ground sump of capacity 25000gallon and lime washing with two coats after necessary preparatory works and petty cement patch works including removing of debris and vegetations from the surroundings of sump location upto 3.0m width all around and recording of cleaning date and due date on wall with synthetic enamelled paint, material and labour complete, all as specified and directed.
All as per item 2.17 here-in-before but capacity 15000 gallon
All as per item 2.17 here-in-before but capacity 10000 gallon
All as per item 2.17 here-in-before but capacity 4000 gallon
Supply and fixing, gun metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed, for 20mm dia bore pipe, including taking out old and removal, complete all as specified and directed.
All as per item 2.21 here-in-before but for 25mm bore pipe
All as per item 2.21 here-in-before but for 40mm bore pipe
All as per item 2.21 here-in-before but for 50mm bore pipe
Supply and fix, sluice valve with cast iron body and gun metal/steel spindle and hand operated iron wheel, both ends flanged and drilled including nuts, bolts, washers and gaskets, class PN 1.6, for 80mm dia bore pipe, including disconnecting, taking out old and removal, complete all as specified and directed.
All as per item 2.25 here-in-before but for 100mm bore
Material and labour, disconnecting all pipe and electric connections from pumping set centrifugal monoblock 0.5/1.0 HP, dismantling and taking out the defective motor to suitable workshop and taking out the complete copper windings and rewinding with super enamelled copper winding wire, varnishing, heating, replacement of ball bearings, re-assembling and fixing at site, reconnection of all pipe and electrical connections and testing, complete all as specified and directed.
All as per item 2.27 here-in-before but 20 HP, three phase.
Supply and fix, non return valve gun metal (ISI marked), for 50mm dia bore pipe, including taking out old and removal, complete all as specified and directed.
Taking out sluice valve 80mm dia bore size, refacing, regrinding, repacking stuffing box of sluice valve spindle including taking apart, re-assembling and re-fixing in position, complete all as specified and directed.
All as per item 2.30 here-in-before but for 100mm bore
Taking down old unserviceable GI water mains (including all fittings) from trenches and burning out old lead for repair/rectification of leakage of GI water line of size 15 to 25mm dia including draining out water, mud etc and relaying the same after repair in position and testing leakage, complete all as specified and directed. Note for item No. 2.50 and 2.52 : (i) Excavation, earth work and GI fitting and jointing material shall included in the quoted rate.
All as per item 2.32 here-in-before but 40 to 50mm dia
All as per item 2.32 here-in-before but 80 to 100mm dia
Material and labour construction of brick masonry valve pit of size 60cmx60cmx60cm (internal dimension) in cement mortar (1:4), with frame of angle iron of size 40 x 40 x 6mm and MS sheet cover 3mm thick and locking arrangements and handle duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, 15mm thick plaster in cement mortar (1:4) internally and external surfaces flush pointed in the same cement mortar as work proceeds, PCC (1:2:4) in coping, including dismantling of old valve pit and removal of retrieved material outside MoD land, complete all as specified and directed.
All as per item 2.35 here-in-before but pit size 90cm x 90cm x 105cm (internal dimension)
Material and labour, repair to damaged brick masonary valve pit of any size by taking out cement plaster and raking out joints and rendering 10mm thick plaster in CM (1:4) as on fair faces of brick work not exceeding 3.6Sqm area, welding the broken hinges, locking arrangement, hold fast, removing denting of MS sheet pit cover, including removing sludge/soil and cleaning the valve pit, removal of rubbish outside MoD land, complete all as specified and directed.
Supply and fix, rotational moulded polyethylene water storage tank triple layer, white colour, screwable lid, 5000litres capacity (cylindrical vertical with closed top), hoisted and fixed in position and making connection with existing GI pipe line including all fittings such as inlet, outlet, waste pipe and plug, ball valve with float, dismantling old unserviceable PVC water tank, taking out and removal, complete all as specified and directed.
Material and labour, painting of valve pit MS cover both side inner and outer with one coat of synthetic enamel paint including cleaning and preperation of old painted surfaces, complete all as specified and directed.
Supply and fixing in replacement motor starter 240 volts suitable for 1HP capacity motor, complete all as specified and directed.
Dismantling and taking out the old worn out reversible synchronus motor (servo motor) from the voltage stablizer LT 3 Phase 415V, 250 KVA and supply and fix reversible servo motor single phase 230 Volts capacity 10 Kg-cm and testing, complete all as specified and directed by Engineer-in-Charge.
Dismantling and taking out the old worn out PCB from the voltage stablizer LT 3 Phase 415 V, 250 KVA and supply and fix PCB of similar specifications as that of taken out and testing, complete all as specified and directed by Engineer-in-Charge. Make : AE/PREMIER
Dismantling and taking out defected PCB from the voltage stablizer LT 3 Phase 415 V, 250 KVA and reinstalling the PCB after repair complete and testing, complete all as specified and directed by Engineer-in-Charge. Make : AE/PREMIER
Servicing & maintenance of DG sets of capacity 62.5 KVA, from authorised representative of company (approved by GE) installed at different locations to the entire satisfaction of Engineer-in-Charge, complete as per following:- (i) Draining out engine/lubrication oil, flushing and pouring new engine oil after repair of DG set including supply and replacement of oil pan/chamber gasket. (ii) Supply and fix, lubricant oil filter element as in replacement (iii) Supply and fix, fuel filter element, as in replacement (iv) Topping up /filling up of radiator with K cool 10Litres (v) General servicing of DG set by opening of tappet cover/top cover, tappet clearance setting with injector timing adjustment, re-fixing of tappet/top cover including supply and replacement of tappet cover packing set, shellac/bostic tube. (vi) Supply and fix, element air cleaner, as in replacement. (vii) Tightening of all electrical connection, AVR connections, alternator connection and Panel connections (viii) Tightening of all the hoses, Fuel connections & `V' Belts. (ix) Cleaning of silencer mufler, radiators. (x) Checking & adjustment of battery terminals and taking out defective and supply and fix new battery terminal in replacement. (xi) Testing of Engine on load for 30 Minutes. (xii) Supply and fix fuel water separator in replacement. (xiii) Checking of auto programming & manual processing. Note: spare parts required to be replaced shall be measured and paid seperately
Supply only, fuel filter, in replacement for DG set capacity 62.5 KVA, complete all as specified and directed.
Supply only, lubricant oil filter, in replacement for DG set capacity 62.5 KVA, complete all as specified and directed.
Supply only, fan belt set, in replacement for DG set capacity 62.5 KVA, complete all as specified and directed.
Supply only, hose pipe set in replacement for DG set capacity 62.5 KVA, complete all as specified and directed.
Supply and fix in replacement carbon bush and commutator of complete set of DG of capacity 62.5 KVA including necessary lath works to rotor to match with original alignment and position, complete all as specified and directed.
Supply and fix in replacement change over switch 100Amps, 4pole, 415V, 50HZ , complete all as specified and directed.
Servicing & maintenance of DG sets of capacity 12.5 KVA, from authorised representative of company (approved by GE) installed at different locations to the entire satisfaction of Engineer-in-Charge, complete as per following:- (i) Draining out engine/lubrication oil, flushing and pouring new engine oil after repair of DG set including supply and replacement of oil pan/chamber gasket. (ii) Supply and fix, lubricant oil filter element as in replacement (iii) Supply and fix, fuel filter element, as in replacement (iv) Topping up /filling up of radiator with K cool 10Litres (v) General servicing of DG set by opening of tappet cover/top cover, tappet clearance setting with injector timing adjustment, re-fixing of tappet/top cover including supply and replacement of tappet cover packing set, shellac/bostic tube. (vi) Supply and fix, element air cleaner, as in replacement. (vii) Tightening of all electrical connection, AVR connections, alternator connection and Panel connections (viii) Tightening of all the hoses, Fuel connections & `V' Belts. (ix) Cleaning of silencer mufler, radiators. (x) Checking & adjustment of battery terminals and taking out defective and supply and fix new battery terminal in replacement. (xi) Testing of Engine on load for 30 Minutes. (xii) Supply and fix fuel water separator in replacement. (xiii) Checking of auto programming & manual processing. Note: spare parts required to be replaced shall be measured and paid seperately
Supply only, fuel filter, in replacement for DG set capacity 12.5 KVA, complete all as specified and directed.
Supply only, lubricant oil filter, in replacement for DG set capacity 22.5 KVA, complete all as specified and directed.
Supply only, fan belt set, in replacement for DG set capacity 12.5 KVA, complete all as specified and directed.
Supply only, hose pipe set in replacement for DG set capacity 12.5 KVA, complete all as specified and directed.
Repair to AMF panel for DG set 62.5KVA, checking for locating the fault and identifying and replacing the defective spare/accessories and testing, complete all as specified and directed. Note:- The spares/accessories replaced will be measured and paid seperately.
Supply only Air break contactor for main supply AC 415 Volts, complete all as specified and directed. Make: L&T, BCH,Siemens
Supply only Air break contactor for DC supply, complete all as specified and directed. Make: L&T, BCH,Siemens
Supply only over load relay, complete all as specified and directed. Make: L&T, BCH,Siemens
Supply only under voltage relay, complete all as specified and directed. Make: L&T, BCH,Siemens
Supply only time delay relay, complete all as specified and directed. Make: L&T, BCH,Siemens
Supply only Engine cranking relay, complete all as specified and directed. Make: L&T, BCH,Siemens
Supply only digital volt meter AC 415 volts, complete all as specified and directed. Make: AE or equivalent
Supply and fix, in replacement maintenance free battery, factory charged, ready to use with extended cycle life, Instant state of charge indication, clean top with no surface leakage and fumes, of 180AH, 12 Volts for solar street light system, complete all as specified and directed.
Supply and fix, in replacement maintenance free battery, factory charged, ready to use with extended cycle life, Instant state of charge indication, clean top with no surface leakage and fumes, of 100AH, 12 Volts for solar street light system, complete all as specified and directed.
All as per Srl item No. 2.66 here in before but 50 KVAR APFC panel
Supply and fix, in repair, power factor improvement static condenser (capacitors) of required capacity, complete all as specified and directed.
Supply & fix, contactor MNX type, AC 3 phase, 240Volts, 50Hz capacity ML-2, 25Amps with standard coil including taking out old and removal, complete all as specified and directed. Make:L&T (MNX-9) or equivalent in makes specified in Appx 'B'.
Supply & fix, contactor MNX type, AC 3 phase, 240Volts, 50Hz capacity ML-2, 32Amps with standard coil including taking out old and removal, complete all as specified and directed. Make:L&T (MNX-32) or equivalent in makes specified in Appx 'B'.
Supply and fix, MCCB, 160Amps, 4pole, 415Volts, 50Hz, 36KA, with adjustable thermal and magnetic release, including extension links, making connection in panel board taking down old and removal, complete all as specified and directed.
Supply and fix, MCCB, 200Amps, 4pole, 415Volts, 50Hz, 36KA, with adjustable thermal and magnetic release, including extension links, making connection in panel board taking down old and removal, complete all as specified and directed.
Supply and fix, MCCB, 250Amps, 4pole, 415Volts, 50Hz, 36KA, with adjustable thermal and magnetic release, including extension links, making connection in panel board taking down old and removal, complete all as specified and directed.
Supply and fix, MCCB, 400Amps, 4pole, 415Volts, 50Hz, 36KA, with adjustable thermal and magnetic release, including extension links, making connection in panel board taking down old and removal, complete all as specified and directed.
Supply and fix, in repairs APFC relays with auto set function having 7 + 1 steps 8 stage suitable for 415 volts including necessary connections all as specified and directed. Make: L&T Cat part No. ERPML08D500 or equivalent in Siemens/EPCOS.
Supply and fix, in repairs MCB TPN 63 Amps, 415V, complete all as specified and directed.
Supply and fix, in repairs MCB TPN 32 Amps, 415V, 'B' series, complete all as specified and directed.
Supply and fix, in repairs MCB DP 32 Amps, 240V, 'B' series, complete all as specified and directed.
Supply and fix, in repairs MCB SP 6 to 40 Amps, 240V, 'B' series, complete all as specified and directed.
Taking down old unserviceable panel wiring (of any type) and material & labour for internal wiring of capacitor bank with PVC insulated sheathed stranded single core copper conductor cable of cross-sectional area 1.5 Sqmm with ring button belt and feral etc, complete all as specified and directed.
Material and labour for scrapping out of existing painted surface of capacitor bank panel and applying two coats of synthetic enamel paint over a coat of red oxide primer after preparation of surface, complete all as specified and directed.
Supply and fix, in repairs, front mounted add on aux conact block 1 NO + 1 NC suitable for power contactor MNX 45 all as specified and directed. Make: L&T Cat Part No. CS94118 or equivalent in ABB/Siemens
Supply and fix, in repairs side mounted add on aux conact block 1 NO + 1 NC suitable for power contactor MNX 45 all as specified and directed. Make: L&T Cat Part No. CS94221 or equivalent in ABB/Siemens
Supply and fix, in repairs modular contact NO block suitable for capacitor bank, complete all as specified and directed. Make: L&T Cat Part No. HC61A2 or equivalent in ABB/Siemens
Supply and fix, in repairs modular contact NC block suitable for capacitor bank, complete all as specified and directed. Make: L&T Cat Part No. HC61B2 or equivalent in ABB/Siemens
Supply and fix, in replacement DOL motor starter MN 32, 415 Volts, over load relay range 23-32 Amps, suitable for 20 HP capacity motor, complete all as specified and directed.
Supply only sodium Hypo chlorite( NaOCL) chemical solution conforming to IS-1673/86 having chloride content 10 % by weight (bleach liquid solution) complete all as specified and directed by Engineer-in Charge. Note : Chemical solution shall be supplied by the contractor as on requirement basis through out the currency of the contract .Therefore the contractor shall procure the chemical solution in piecemeal as per requirement .The material shall be deposited with AGE B/R Kasauli and RV shall be prepared accordingly. Contractor shall also arrange independent testing of chemical from Govt authorized laboratory at his own expence. The cost of testing shall be deemed to be included in the quotated rate. Payment of supply of Sodium chlorite solution shall only be made on production of test report.
Supply and fixing in repair branch pipe gun metal 63mm instantaneous inlet of length upto 7.5m, made threaded outlet, 15mm bore nozzle short, complete all as specified and directed by Engineer-in Charge.
Supply and fixing, brass ball valves, suitable for 20mm bore dia pipes etc, high pressure, with polylethene float and fiynut, fixed as in repairs, complete all as specified and directed.
Supply and fixing in repair 5mm thick mild steel plates plain or corrugated for valve pit cover, complete all as specified and directed.
Note: The Total amount shall subject to adjustment of credit of Rs. 70523.50 for old Materials as per Schedule of Credit
Vinod Kumar Aggarwal
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .