Civil Works and Installation of Power Backup System at Santhigiri Ayurveda and Siddha Research Centre Skill Development Training Institute, Saket, New Delhi
NBCC/NIT/CGM-RFM/16
NBCC/NIT/CGM-RFM/16
Open Tender-Domestic
Miscellaneous Services
New Delhi, Delhi
₹2,950
₹27,402
15 Jul 2026
16 Jun 2025
27 Jun 2025
27 Jun 2025
1 Jul 2025
S. No. Description Amount (Rs.)
1 Compound Wall & Gate Work 1315418.37
2 Power Backup System 1424850.00
Digitally signed by RAJ PAL
COMPOUND WALL & GATE WORK
S.No. DSR No. Item Description Unit Rate Qty. Amount
Demolishing R.C.C. work manually/ by mechanical
1 15.3 means including stacking of steel bars and disposal
of unserviceable material within 50 metres lead as
per direction of Engineer - in- charge. Cum 3657.79 2.80 10241.81
Demolishing brick work manually/ by mechanical
15.7 means including stacking of serviceable material
and disposal of unserviceable material within 50
metres lead as per direction of Engineer-in-charge.
Earth work in excavation by mechanical means
(Hydraulic excavator)/ manualmeans over areas
2.6 (exceeding 30 cm in depth, 1.5 m in width as well
as 10 sqm on plan) including getting out and
disposal of excavated earth lead upto 50 m and lift
upto 1.5 m, as directed by Engineer-in-charge.
Filling available excavated earth (excluding rock) in
trenches, plinth, sides of foundations etc. in layers
not exceeding 20cm in depth, consolidating each
deposited layer by ramming and watering, lead up
Centering and shuttering including strutting,
propping etc. and removal of form work for :
5 5.9.1 Foundations, footings, bases for columns Sqm 403.91 18.48 7464.33996
Lintels, beams, plinth beams, girders, bressumers
and cantilevers Sqm 758.49 31.00 23513.25
7 5.9.6 Columns, piers, abutments, pillars, posts and struts Sqm 990.14 52.80 52279.3392
Providing and laying in position cement concrete
of specified grade excluding the cost of centering
and shuttering - All work up to plinth level :
1:4:8 (1 Cement : 4 coarse sand (zone-III) derived
from natural sources : 8 graded stone aggregate
40 mm nominal size derived from natural sources) Cum 7016.36 7.44 52201.7184
Digitally signed by RAJ PAL
Providing and laying in position machine batched
and machine mixed design mix M-25 grade cement
concrete for reinforced cement concrete work,
using cement content as per approved design mix,
including pumping of concrete to site of laying but
5.33 excluding the cost of centering, shuttering,
finishing and reinforcement, including admixtures
in recommended proportions as per IS: 9103 to
accelerate, retard setting of concrete, improve
workability without impairing strength and
durability as per direction of Engineer-in-charge.
(Note :- Cement content considered in this item is
@ 330 kg/cum. Excess/ less cement used as per
design mix is payable/recoverable separately).
5.33.1 All works upto plinth level
Concrete of M25 Grade with minimum cement
content of 330 kg/cum Cum 9789.89 8.04 78740.11
All works above plinth level upto floor V level
Concrete of M25 Grade with minimum cement
content of 330 kg/cum Cum 10156.21 2.97 30163.94964
Steel reinforcement for R.C.C. work including
straightening, cutting, bending, placing in position
and binding all complete upto plinth level
Thermo-Mechanically Treated bars of grade Fe-
Steel reinforcement for R.C.C. work including
straightening, cutting, bending, placing in position
and binding all complete above plinth level
Thermo-Mechanically Treated bars of grade Fe-
Brick work with common burnt clay machine
moulded modular bricks of class designation 12.5
6.28 in exposed brick work including making horizontal
and vertical grooves 10 mm wide 12 mm deep
complete in cement mortar 1:6 (1 cement : 6
13 6.28.1 From ground level upto plinth level Cum 7207.32 12.12 87359.95
14 6.28.2 Above plinth level upto floor V level Cum 9240.23 21.39 197648.58
15 mm cement plaster on the rough side of single
or half brick wall of mix :
Finishing walls with Acrylic Smooth exterior paint
of required shade :
New work (Two or more coat applied @ 1.67 ltr/10
16 13.46.1 sqm over and including priming coat of exterior
primer applied @ 0.90 litre/10 sqm) Sqm 165.42 291.40 48202.81
GRC Jali work on inner side of boundary wall Sqm 2400.00 45.00 108000.00
18 NS Electric Work & Light Fittings Nos 1120.00 28.00 31360.00
Steel work welded in built up sections/ framed
10.25 work, including cutting, hoisting, fixing in position
and applying a priming coat of approved steel
primer using structural steel etc. as required.
In gratings, frames, guard bar, ladder, railings,
brackets, gates and similar works Kg 177.78 1500.00 266667.00
Digitally signed by RAJ PAL
POWER BACKUP SYSTEM
S. No. Description Unit Qty Rate Amount
Supply, installation, Testing & Commissioning of
'Silent Type Diesel Generating set as per CPCB IV +
or better norms along with having Prime Power
Rating of KVA as below, 415 volts at 1500 RPM, 0.8
lagging power factor at 415 V suitable for 50 Hz, 3
1 phase system & for 0.85 Load Factor, including
testing at factory and site with fuel, load for test
and other necessary arrangements Complete as
per CPWD specifications, should
have QR code which should contain drawing, test
report OEM manual,GeoTag of manufacturing
location, rating plate as per relevant IS Code etc.
and consisting of the followings:
(A) Diesel Engine:
Turbocharged Diesel engine 4 stroke water cooled,
multi cylinder, dynamically balanced fly wheel,
electric start of suitable BHP at 1500 RPM suitable
for above output of alternator at 40 Degree C, 50%
RH & at 1000 Meter MSL, capable of taking 10%
over loading for one hour after 12 hours of
continuous operation. The engine will be with
Electronic governor, Dry typeAir filter with service
indicator, first filling of engine fuel (after
commissioning) lubricating Oil, Coolant and other
consumables complete with all the required
accessories, the Electronic governor shall be as per
ISO 8528.The engine shall comply to the latest
CPCB norms (CPCB IV + or better) and
Conforming to BS 5514, BS 649, IS 10000, IS
10002, IS 13018 and as per CPWD specifications.
(B) Engine mounted Instrument Panel fitted with
and having digital display for following:
(i) Start-stop switch with key
(ii) Water temperature indication
(iii) Lubrication oil pressure indication
(iv) Lubrication oil temperature indication
(v) Battery charging indication and Voltage
(vi) RPM indication
(vii) Over speed indication
(viii) Low lubricantion Oil trip indication
(ix) Engine Running Hours indication
(C) Alternator:
Synchronous alternator rated of appropriate KVA,
415 volts at 1500 RPM, 3 phase 50 Hz, AC supply
with 0.8 lagging power factor at 40 Degree C, 50%
RH & at 1000 Meter MSL. The alternator shall be
having Screen ProtectedDrip Proof (SPDP)
enclosure IP23, brushless, continuous duty,
balanced rotor, capable of taking 10% over loading
for one hour after 12 hours of continuous
operation, self cooled,self-excited and self-
regulated through AVR conforming to
IS13364(Part 2)/IS: 4722/BS 2613 suitable for
tropical conditions and with class- H insulation.
Digitally signed by RAJ PAL
(D) Base Frame & Foundation:
Both the engine and alternator shall be mounted
on suitable base frame made of MS channel with
necessary reinforcement which shall be installed
on suitable cement concrete foundation and
vibration isolation arrangement as per
recommendations of manufacturer.
Daily service fuel tank of suitable liters capacity as
per CPWD Specifications, fabricated out of 3 mm
thick M.S. sheet complete with all standard
accessories and fuel piping between fuel tank and
diesel engine with MS class 'C' pipes of suitable
dia. Complete with valves, level indications &
accessories as required as per specifications.
(F) Exhaust System:
Dry exhaust manifold with hospital type exhaust
silencer and catalytic convertor.
(G) Starting System:
12V/24V DC starting system comprising of starter
motors: voltage regulator and arrangement for
initial excitation complete with suitable numbers
of batteries (180 AH capacity lead acid SMF type)
as required as per specifications. The battery shall
be housed inside the acoustic enclosure
(H) Acoustic and weather proof enclosure with
arrangement for fresh air intake for cooling of the
engine & alternator, extraction, discharging hot air
in to the atmosphere and the temperature rise
inside the enclosure, noise level
outside enclosure. The acoustic enclosure should
be suitable for cable connection/connection
through bus-trunking. Such arrangements on
acoustic enclosure should be water proof & dust-
proof conforming to IP-65 protection. The
enclosure shall be as per CPCB IV + or better
norms etc. and as per CPWD specifications.
Free standing floor mounted IP 42 automatic
mains failure control panel including auto by-pass,
suitable for KVA as below for silent type DG set
complete with relays, timers, set of CTs for
metering & protection and energy analyser to
indicate currents, phase and line voltages,
frequency, power factor, KWH, Kilo Volt Ampere
Reative Hour (KVARH), KVA (Phase & Total), KW &
provision for overload, short circuit, restricted
earth fault, under frequency, power (aluminum)
and control (copper ) cabling of suitable size upto
15 meter between AMF panel, LT Panel and DG Set
including connection interconnection etc. as
required, all complete and inter locking
and communication/ Ethernet /RS485/SNMP port
open protocol for BMS integration including
suitable software, the panel shall be of DG Set
OEM make etc. as per approved by Engineering in
charge and including the following:
1. Suitable numbers and appropriate capacity 4
electrically operated draw out with cradle type 3
position ACB/ MCCB with electronic release for
O/C & E/F and shunt trip.
2. Auto/Manual/Test/Off selector switch
Digitally signed by RAJ PAL
3. Protection for under and over voltage phase
reversal (2 nos Over voltage relay, 2 Nos. reverse
power relay and 2 Nos. under voltage relay).
4. 3 Sets of current transformers 15 P10 accuracy
for protection and 15 VAclass-I for metering
5. Energy analyser unit to indicate current,
Voltage( L-N & L-L), kW, kVA (Phase & Total),
Frequency, KWH, PF.
6. LED Indicating lamps for load on mains and load
7. Fuse/ MCB for instruments.
8. Battery charger, complete with transformer/
rectifier, D.C. voltmeter and ammeter, selector
switch for trickle, off and boost and current
9. Main supply failure monitor
10. Supply failure timer.
11. Restoration timer
12. Control unit with three impulse automatic
engine start/stop and failure to start lockout.
13. Impulse counter with locking and reset facility.
14. ON/OFF/Control circuit switch with indicator
15. Audio/Video annunciation for
(i) High water temperature
(ii) Low lubricating oil pressure
(iii) Engine over speed
(iv) Engine fails to start
(v) Full load/maximum load warning
16. Protection for over/under Frequency, Loss of
AC sensing, Over Current, Unbalancing load with
suitable number of relays and accessories
17. Maintenance notification based on Engine Run
Hour & due date.
18. Load Management through PLC to achieve
auto opening and closing of incomer breakers, bus
coupler switching of essential panel , interlocking
providing signal to AMF Panel for load status and
AMF shall give command to DG Set to auto start /
auto stop depending upon load status and
requirement etc. and necessary hardware and
software required to perform the operation shall
be provided by the contractor including all control
Digitally signed by RAJ PAL
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT santhgiri.pdf
Tender Document
BOQ Santhigiri.pdf
Tender Document
Scope of Work.pdf
Tender Document
APPROVE MAKE.pdf
Tender Document
GCC PMC 2022 with 12 amnd.pdf
Tender Document
corrigendum-3901-corrigendum01.pdf
pdf • 0.17 MB
corrigendum-3900-corrigendum01.pdf
pdf • 0.17 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .