EE(E) HMED(N) PWD,
EE(E) HMED(N) PWD, Dr. BSA Hospital Sec-6 Rohini Delhi-85.
SH Repairing and replacement of cooling tower accessories including cleaning of ducts of HVAC
2026_PWD_286274_1
92/EE(E)HMED(N)/PWD/BSAH/2025 26
Open Tender
Composite Works
30 days
DCB Hospital Kokiwala Bagh Ashok Vihar New Delhi
Please refer the tender Documents as per NIT
10 documents required · 10 mandatory
₹0
₹36,460
23 Feb 2026
5 Feb 2026
13 Feb 2026
5 Feb 2026
13 Feb 2026
5 Feb 2026
Replacement of following accessories of cooling tower i/c dismantling of old wornout & installation of new at its place along with accessories complete etc as required at site.
PVC nozzles
spacer
End cap
Supply & Fixing of new P.V.C. fills of 600x300x150 mm size in induced forced draft FRP cooling tower for proper air flow for suitable capacity including dismantling of old / damaged PVC fills, testing & commissioning etc complete as reqd. Throwing & dumping of old fills. As per environmental norms.
Supply and replacement of totally enclosed fan cooled, squirrel, cage 3 phase induction motor HE-1 E2 (Cast Iron) fan Motor (Long shaft) of 5.5 KW 750 rpm 440 Volts, 50 Hz i/c dismantling of old burnt motor & installation of new at its place along with accessories like nut bolts, angle frame i/c but back of old motor etc complete as required.
Cleaning all Supply Air Ducts internally by NADCA Certified agency only with skilled personnel with specialized latest Robotic Technology equipment and Vacuum machines. A robotic camera to be used for inspection and or cleaning. contractor has to provide access in duct opening for present and future cleaning requirement and sealing the same after cleaning to avoid air leakage. The contractor shall give copy of the video footage in CD before and after cleaning of ducts. Upon completion a cleaning certificate will be issued within 10-15 days, valid for 12 months. Cleaning Certificate will be issue and signed by ASCS (Air System Cleaning Specialist) & OSHA certified Complete work will be supervised & signed the daily report BY NADCA certified ASCS only on DAILY Basis.
Providing access in duct opening for present and future cleaning requirement and sealing the same after cleaning to avoid air leakage as per NADCA standard.
Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original
Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature).
1.5 TR with 5 Star BEE Rating
Dismantling of existing Split AC unit i/c Less credit for old Dismantling Material etc as complete.
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.27 MB
NIT.pdf
Tender Documents • 3.25 MB
BOQ_378936.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid