Loading…
New: tenders and results on WhatsApp
New: Find tenders, results and companies on WhatsApp, by text or voice note
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹1.2 LAccepted-Finance 19 A DURGA BARI SADAR BAZAR MEERUT MEERUT MEERUT UTTAR PRADESH 250001 | MEERUT | UTTAR PRADESH | 250001 | 1 | Accepted-Finance Accepted | |
| 2 | 2₹1.5 L+₹30,150 (24.5%)Accepted-Finance | 2 | Accepted-Finance Accepted | |
| 3 | 3₹1.9 L+₹69,530 (56.5%)Accepted-Finance | 3 | Accepted-Finance Accepted |
Tender Value
₹1.2 L
EMD Value
₹2,000
Closing Date
28 Feb 2025, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EE ETD-I, NOIDA
EE ETD-I, NOIDA
ATTENDING POOR DGA VALUES AND OIL LEAKAGE FROM LV BUSHINGS OF 220/33KV, 100 MVA T/F-I (Make-TAL, Year-2018) AT 400 KV SUB-STATION SEC-148 NOIDA UNDER ELECTIRICTY TRANSIMSSION DIVISION-I NOIDA
2025_UPTCL_1006854_1
ST.ET-04/02/W/2024-25
Open Tender
Electrical Works
Item Rate
10 days
EE ETD-I, NOIDA
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
EE ETD
₹2,000
28 Mar 2025
15 Feb 2025
1 Mar 2025
15 Feb 2025
28 Feb 2025
15 Feb 2025
Amount
FOLLOWING WORK ARE REQUIRED FOR ATTENDING POOR DGA VALUES AND OIL LEAKAGE FROM LV BUSHINGS OF 220/33KV, 100 MVA T/F-I (Make-TAL, Year-2018) AT 400 KV SUB-STATION SEC-148 NOIDA UNDER ELECTIRICTY TRANSIMSSION DIVISION-I NOIDA-
Drain out of the T/F oil from 100 MVA T/F-I tank into empty oil drums/Oil tanker upto LV Bushing Level (around 2 KL).
Opening of jumpers of 100 MVA T/F-I LV SIDE ONLY and other associated works
Dismantling of of LV SIDE bushing, etc. before replacement of Gaskets
Providing and making of LV bushing Gasket of good quality rubberized cork sheet Kotika/Telbroze/NE Cork make including replacement of LV Bushings Gasket as per the instruction of site-incharge.
Erection of of LV SIDE bushing after gasket replacement work.
Centrifuging of T/F oil after topping up drained oil back into transformer; taking the IR/BDV value oil T/F oil at an interval of 6 hrs. as per norms of T/F manufacturer. The contractor shall arrange BDV and ppm machine for testing of TF oil during centrifuging work.
Jumpering of 100 MVA T/F-I LV SIDE bushings and ready for energize of Transformer.
Sampling and testing of transformer, if required, oil at CPRI or any other NABL accredited testing lab including cost of transportation of each sample in standard sampling bottles (adequate number of bottles to be arranged by contractor). Samples to be taken at required intervals (as per actual requirement)- Following tests are to be conducted for eaeh sample- 1.Breakdown voltage 2. Moisture Content, 3. Dissolved Gas Analysis.
M/s S.S. Refregeration (BID ID -5008315)
SATKAR TRADERS (BID ID -5000073)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .