| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.1 LAccepted-AOC 10 2 NARAYAN BAG INDORE M P | L1 | Accepted-AOC Lowest and reasonable | |
| 2 | L2₹16.9 L+₹1.3 L (8.25%)Rejected-Finance | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹16.9 L+₹1.4 L (8.71%)Rejected-Finance | L3 | Rejected-Finance Being L3 | |
| 4 | L4₹18.5 L+₹2.9 L (18.5%)Rejected-Finance | L4 | Rejected-Finance Being L4 |
Tender Value
₹19.4 L
EMD Value
₹38,880
Closing Date
17 Dec 2020, 6:00 pmClosed
CWE Mhow
HQ CWE Mhow Cantt Mhow 453441
SPECIAL REPAIRS TO E M INSTALLATIONS AND ALLIED WORK AT AWC UNDER GE AWC MHOW
2020_MES_394947_1
CA No CWE/Mhow/27(T) OF 2020-21
Open Tender
Civil Works
Item Rate
180 days
HQ CWE Mhow
Please refer tender documents
7 documents required · 7 mandatory
₹500
GE AWC Mhow
₹38,880
Yes
11 Jan 2021
19 Nov 2020
19 Dec 2020
19 Nov 2020
17 Dec 2020
4 Dec 2020
Amount
Taking down old unserviceable old vintage LT Panel , disconnecting all cable connections , earthing complete all as specified and as directed.
Excavation in trenches in any type of soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of cable and fixing pole,stays etc and getting out complete all as specified and directed
Returning , filling in includiing spreading levelling, watering and well ramming in layers not exceeding 25 cm thick with excavated soil comlete all as specified and directed
Removing excavated material (surplus soil ) to a distance not exc 50 mtr and depositing where directed at level not exc 1.5mtr above the starting point complete allas specified and directed.
Material and labour for approved river sand cushioning for under ground cable in trenches 8 cm before laying and 15 cm after laying of cable and punned thickness of sand shall be measured and paid for 18 cm only after punned/consolidated thickness complete all as specified and directed.
Supply & laying of unreinforced PCC Cable protection cover , Class LV ,Type1 flat ,size 250mm X150mm x 40mm as cable protection laid flat width wise complete all as specified and directed. Make: Mahtab tiles / Alankar Tiles/Pearlers Industries/SIND Mozaic Gujrat/JJ Concrete Lucknow.
Supply and laying galvanised iron pipe 'light Grade' 50 mm in trenches , under floors, roads, along poles for protection of cables with all necessary fittings, including sealing ends complete all as specified and directed .
Supply and laying galvanised iron pipe 'light Grade' 80 mm in trenches , under floors, roads, along poles for protection of cables with all necessary fittings, including sealing ends complete all as specified and directed .
Drilling (Horizontally) existing road (Maximum 10 mtr wide ) suitable for passing GI tubing 80 mm complete all as specified and directed.( GI tubing light grade measured and paid under respected item)
Supply, laying or fixing, jointing and testing LT under ground electric power cable. Crossed linked polyethylene (XLPE Cable ) insulated, galvanised steel strip or wire armoured, ISI -7098 Marked. With aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 120Sqmm 3.5core complete all as specified laid in tenches / laid under floor or fixed naked with walls/ on poles/ in ducts/ in GI pipes etc:-
Ditto all as per item No 10 above but size 95 sq mm 4core
Ditto all as per item No 10 above but size 50 sq mm 4core
Ditto all as per item No 10 above but size 35 sq mm 3.5 core
Ditto all as per item No 10 above but size 25 sq mm 4 core
Ditto all as per item No 10 above but size 16 sq mm 4.0 core
Ditto all as per item No 10 above but size 10 sq mm 4.0 core
Supply,installation, commissioning and testing, LT out door type LT panel board of suitable size factory assembled fabricated (CPRI APPROVED) and of suitable size and angle iron, channel and MS sheet 3mm to 3.15 mm thick (Inner compartment is 2.0 mm thick), double door type, front and rear openable with locking arrangement, duly powder coated painted with locking arrangement and independently housing for each control switch gear duly prewired with colour coading for three phasres and neutral Alunimum busbar 1200Amp , for 415 volts, 50 Hz electric supply with and including suitable sizes of cable glands for incoming and outgoing cables, grouting the panel board on and including suitable size foundation structure made out if equale angle iron as mentioned mentioned below installation, comissioning and testing complete with the following switch gears/ accessories :- (B Mess)
Supply,installation, commissioning and testing, LT out door type LT panel board of suitable size factory assembled fabricated (CPRI APPROVED) and of suitable size and angle iron, channel and MS sheet 3mm to 3.15 mm thick (Inner compartment is 2.0 mm thick), double door type, front and rear openable with locking arrangement, duly powder coated painted with locking arrangement and independently housing for each control switch gear duly prewired with colour coading for three phasres and neutral Alunimum busbar 600 Amp , for 415 volts, 50 Hz electric supply with and including suitable sizes of cable glands for incoming and outgoing cables, grouting the panel board on and including suitable size foundation structure made out if equale angle iron as mentioned mentioned below installation, comissioning and testing complete with the following switch gears/ accessories :- (B Mess ,)
Supply,installation, commissioning and testing, LT out door type LT panel board of suitable size factory assembled fabricated (CPRI APPROVED) and of suitable size and angle iron, channel and MS sheet 3mm to 3.15 mm thick (Inner compartment is 2.0 mm thick), double door type, front and rear openable with locking arrangement, duly powder coated painted with locking arrangement and independently housing for each control switch gear duly prewired with colour coading for three phasres and neutral Alunimum busbar 600 Amp , for 415 volts, 50 Hz electric supply with and including suitable sizes of cable glands for incoming and outgoing cables, grouting the panel board on and including suitable size foundation structure made out if equale angle iron as mentioned mentioned below installation, comissioning and testing complete with the following switch gears/ accessories :- (A Mess)
Supply,installation, commissioning and testing, LT out door type LT panel board of suitable size factory assembled fabricated (CPRI APPROVED) and of suitable size and angle iron, channel and MS sheet 3mm to 3.15 mm thick (Inner compartment is 2.0 mm thick), double door type, front and rear openable with locking arrangement, duly powder coated painted with locking arrangement and independently housing for each control switch gear duly prewired with colour coading for three phasres and neutral Alunimum busbar 600 Amp , for 415 volts, 50 Hz electric supply with and including suitable sizes of cable glands for incoming and outgoing cables, grouting the panel board on and including suitable size foundation structure made out if equale angle iron as mentioned mentioned below installation, comissioning and testing complete with the following switch gears/ accessories :- ( Annexy )
Supply and erection of HOT DIPP Galvanized galvanisig coating thickness & with internal dimension. cable, the tray of sizes 300x100mm of 18 guage including Coupler 100 mm and nut bolt etc of the trey and dia of the wire should be equal or more than the specified.
Supply and erection of HOT DIPP Galvanized galvanisig coating thickness & with internal dimension. cable, the tray of sizes 150mm x 100mm of 18guage including Coupler 100 mm and nut bolt etc of the trey and dia of the wire should be equal or more than the specified.
Material and labour for earthing in repair complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to GI strip 25mm X 4mm main earthing lead by means of galvanized bolts, nuts and washers all as shown in electrical plate no 3 SSR Part-I with connected to earth test point & to main switch board etc with & including adequate quantity of charcoal dust and common salt alround earth plate, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40mm x 40mm x 6mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover reinforced with 6mm dia bars 3 Nos both way with 12mm dia round bar handle, GI light grade watering pipe 20 mm dia with funnel and wire mesh, and 40 mm dia GI light grade earth lead protection pipe complete all as specified and directed.
MODI CORPORATION
AGARWAL BUILDERS
Ms Kailash Chandra Babulal
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .