Tender Value
₹18.2 L
EMD Value
₹36,400
Closing Date
5 Nov 2020, 5:00 pmClosed
Executive Engineer
Electrical Division PWD BnR Rohtak
Pdg. 250 KVA Sub Station in Govt. I.T.I. at Kiloi in District Rohtak.
2020_HRY_148402_1
PWD/Electrical/154460
Open Tender
Electrical Works
Item-rate/Agreement basic
60 days
Rohtak
Please refer to tender documents
3 documents required · 3 mandatory
₹1,000
Executive Engineer, Electrical Division PWD BnR RO
₹36,400
Yes
25 Feb 2021
21 Oct 2020
6 Nov 2020
21 Oct 2020
5 Nov 2020
21 Oct 2020
Amount
6.6 Earth work in excavation in foundations, trenches, etc. in all kinds of soils, not exceeding 2 metres depth including dressing of bottom and sides of trenches stacking the excavated soil, clear from the edge of excavation and subsequent filling around masonary, in 15 cm layers with compaction, including disposal of all surplus soil, as directed within a lead of 30 metres
10.40 Cement concrete 1:3:6 with stone aggregate 20 mm nominal size foundation and plinth
10.26 Cement Concrete Cement concrete 1:8:16 with brick ballast 40 mm nominal size in foundation and plinth
10.41 Cement concrete 1:2:4 with stone aggregate 20 mm nominal size in foundation and plinth.
11.2 First class brick work laid in cement sand mortar 1:6 in foundation and plinth.
15.6 12 mm thick cement plaster 1:5.
31.12© Moulded case Circuit breakers. Supply and erection of moulded case circuit breakers on wall or on existing pedestal including bonding to earth and necessary connections.
31.12 c (i) 15 amp.to 60 amp. 415 V ,10 KA 3-phase
31.12 c (ii) 100 amp.to 220 amp.415 V,10 KA 3-phase.
31.12 c (iii) 250 amp. 415 V , 35 KA 3-phase.
31.12 c (iv) 300 amp. to 400 amp. 415 V , 35 KA 3-phase.
(P) Pipe Laying. 31.21 Supply and erection of pipe for wiring purposes including bends inspection boxes etc. where necessary and painting as required.
31.21 (vii) Galvanised iron pipe 65 mm dia on surface.
31.22 (Q) Earthing
31.22(iii) Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as equired.
31.22(iv) Earthing with tinned copper earth plate 600 mm x 600 mm x 3 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required.
31.22(v) Extra for charcoal or coke and salt for G.I. Plate or copper plate earth electrode
31.22(x) Pdg. and fixing 25 mm x 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required
31.22(xi) Pdg. and fixing 25 mm x 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode as required .
31.22(xiv) Pdg. and fixing 25 mm x 5 mm copper strip on surface or in recess for connections etc. as required with all labour and material
31.22(xv) Pdg. and fixing 25 mm x 5 mm G.I. Strip on surface or in recess for connections etc. as required with all labour and material.
31.26 Supply and erection of under ground cable ,loose in existing pipe or trenches complete with necessary connections
31.26 (xxix) Ard. 95 Sq. mm 3.5 Core Cable
31.26 (xxx) Ard 120 Sq. mm 3.5 Core Cable
31.26 (xxxiii) Ard. 240 Sq. mm 3.5 Core Cable
31.28 Supply and erection of suitable compression type brass cable glands for underground Cable
31.28(iv) 70 Sqmm to 95 Sqmm Cable 3 to 3.5 Core
31.28 (v) 120 Sqmm to 185 Sqmm Cable 3 to 3.5 Core
31.28 (vi) 240 Sqmm Cable 3 to 3.5 Core
( T ) Street Light
31.30 (VI) Supply and erection of prestressed cement concrete pole as per IS : 1678-1960
31.30 (VI) (ii) 9 metres long 105 mm x 115 mm at top and 105 mm x 315 mm at bottom with working load of 200 Kg. burried 1.80 m in ground.
31.63 Supply installation testing and commissioning of wall/free standing floor mounting dust & vermin proof compartmentalized cubical panel made out of 2mm thick CRCA sheet, required hardware 3mm thick bakelite sheet provided all along the bus bar cable alley separating switches compartment and supporting cutable channel duly painted by 2 coat of Zinc/ Red Oxid primer having PU/Neoprene rubber gasket of not less than 3mm thickness separate detachable gland plate MS base channel hinged door with inter locking arrangement for equipment/switch wear.
Transparent acrylic sheet shall be provided in front of bus bar compartment to prevent direct access to bus bar bakelite sheet 3 mm thick for separately cable alley to BBC from switch chamber Extended solid copper bars up to cable alleys shall be provided for outgoing connection which shall be paid as extra items. Side walls and cable alley comartments shall be having bolted type doors with detachable extension type structure. The panel will be complete with control wiring (Copper) and fuse protection.
31.64 Supplying and fixing of copper bus bar duly tinned by means of SMC/DMC type insulator high tensile nuts and boltes spring washers fixing to same in existing panel including bending, cutting in required shape and size and insulation with colour coding heat shrinkable PVC insulation Complete in all respect
31.66 Supply & fixing of rotary handle for on/off operation of existing MCCB in the LT panel including fixing the same in position with all labour and material requied to complete the job in all respect.
(i) Rotary handle upto 125 Amp. MCCB
(ii) Rotary handle above 125 Amp. MCCB
31.67 Supply and erection of mark double walled corrugated (DWC) HDPE pipe laid 1Mtr. Below ground level including diging and refilling of earth including cost of sutiable size socket/cuppler for HDPE pipe including the cost of labour and material required to complete the job in all respect upto the entire satisfaction of Engineer-in-Charge of the work
(ii) HDPE pipe 90/75 mm outer dia/inner dia
(ii) HDPE pipe 145/123 mm outer dia/inner dia.
31.71 S/E of XLPE (E) 11 KV HT aluminum conductor armoured cable ISI marked laid in existing pipe / trenches / surface with all labour and material required to complete the job in all respect upto the entire satisfaction of Engineer-incharge of the work
(iv) 50 Sq. mm 3 Core XLPE Cable
31.72 Supply and erection of heat shrinkage type end termination jointing kit indoor type of suitable to accommodate 3 core 11 KV XLPE aluminum cable/ ABC cable complete with all the kit contents including earth continuing connection along with 3 nos. crimpling type aluminum lugs of suitable capacity including making joining etc complete in all respect.
(i) Suitable for 16 to 50 sqmm 3 core XLPE Cable
31.73 Supply and erection of heat shrinkage type end termination jointing kit outdoor type of suitable to accommodate 3 core 11 KV XLPE aluminum cable/ ABC cable complete with all the kit contents including earth continuing connection along with 3 nos. crimpling type aluminum lugs of suitable capacity including making joining etc complete in all respect.
(i) Suitable for 16 to 50 sqmm 3 core XLPE Cable
M.R. items N.S - 1 Supply, erection, testing and commissioning of outdoor type copper wound, transformer of 250 KVA 11 / 433 KV, 3 Phase, 50 Hz complete in all respect upto the entire satisfaction of Engineer-in-charge of work ( on existing pole / plateform including first filling of oil conforming to IS 1180 level -2- (Only valid approved makes)
No. load voltage ratio 11/ 433 KV
No. of Phase 3
Frequency cycles 50 Hz
Types Double wound core type Copper wound
Cooling ONAN
Duty outdoor
Vector Group ISS-DYN 11 / IS 2026 /77
Tapping on HV compensation +5% to - 5% Insteps of 2.5%
Temperature rise (Oil / res.00) 500 / 550 C
Attitude upto 1000 m above MSL
Off circuit tape changer
Externally hand operated
Oil conservator with filling hole & cap
Plain oil level gauge with minimum level marking
Thermometer pocket
4 Nos. Plain roller undirectional.
1 No. 4" dial type thermometer
Silica Gel breather
Ist filling of oil.
Drain cum filter valve with plug
Rating & diagram plate
Two earthing terminals
Lifting arrangement
Explosion vent
Air release plug
Oil conservator tank
Shunt off valve between buchloz & conservator
TERMINATION
HV-3 Pole single glands cable box suitable for reception of one No. 3 core upto 120 sqmm HT XLPE cable including compound for filling the cable end box with aluminium lugs / thimble
LV- 4 Pole 3 glands cable boxes suitable for 3 Nos. 240 sqmm 3.5 core Polyvinyl chloride cable having extended copper bars of requisite Capacity from LT bushing for making connections with cable including cost of aluminium lugs, thimbles LV : Neutral suitable cable Box for earthing provided.
NS-2 Supply, erection, testing & commissioning of cubical type dust & vermin proof LT automatic power factor control panel 80 KVAR capacity suitable for automatic operation and control power factor within the set limit free standing floor mounting made out of 14 G mild steel sheet with channel iron base frame painted with stoving synthetic light grey enameled paint suitable for operation on 3 phae 4 wire 50 cycles, per second 400 / 440 volts AC supply equipped with the following ( as per diagram attached ) 1 No. automatic power factor control relay of GE / L&T make space for incomer 200 amp tripple pole MCCB.
1 No. power factor relay L&T / Neptune
A set of pilot lamp ( 3 Nos. ) phase indicating lamp of L&T make iron clad bus bar chamber suitable for 200 Amp. 440 V having 3 Nos. phase copper bars of cross-section 25 mm x 05 mm and 1 No. neutral copper bars of cross-section 20 mm x 5 mm duly tinned and insulated with polyvinyl chloride sleeving with requisite clearance as per ISS connection from incomer 250 amp. 4 pole MCCB to bus bar by means of solid copper strips of requisite capacity duly tinned & insulated with PVC sleeving.
2 Nos. 3 Phase 20 KVAR capacitor ( Total 40 KVAR ).
2 Nos. 3 Phase 10 KVAR capacitor ( Total 20 KVAR ).
4 Nos. 3 Phase 5 KVAR capacitor ( Total 20 KVAR ).
Make: Havells, Epcos, Neptune, L&T & Siemens
2 Nos. 3 Phase 63 Amp. contactor for 20 KVAR capacitor
Make: L&T
2 Nos. 3 Phase 45 Amp. Contactors for 10 KVAR capacitor of L.T. make
4 Nos. 3 Phase 16 Amp. Contactors for 05 KVAR capacitor of L.T. make
2 Nos. 40 Amp. MCB for 25 / 20 KVAR capacitor of L.&T / GE make
6 Nos. 20 Amp. MCB for 10 / 05 KVAR capacitor of L.&T / GE make
8 Nos. indicator lamp 220 volts for an indicator of respective capacitor bank of L&T / Siemens make.
8 Nos. MCB for each capacitor of L&T / GE make
CTs of ratio 200 / 5 amp of AE make as per required load of building
16 Nos. push button on / off for manual operating of required of L&T make connection from bus bar to capacitor by means of 16 sqmm PVC copper cable, earthing copper bus bar of cross-section 20 mm x 5 mm duly tinned throughout the length of panel.
NS-3 Supply, erection, testing & commissioning of 11 KV indoor H.T. Metering panel complete with CTs, PTs cubical and electronics meter with accuracy class 0.5 as per requirement / approved by UHBVNL Consisting of the following :
i) Cubical panel free standing floor mounting type made of sheet steel 14-G SWG CRCA sheet with channel iron base frame spray paintd with strong Synthetic grey channel paint as per size & design approved by UHBVNL .
ii) 3 Nos. 11 KV CTs of rating as approved by HVPN for indoor installation of approved make of HVPN
iii) One No. 11 KV PT 11000/110 Volts 10 KA burden 0.5 accuracy oil filled suitable for indoor installation of approved make of HVPN.
iv) Digital electronic meter 3 Phase 4 wires 0.5 accuracy for recording reading operating system for difference kind of readings. The cubical panel will be complete in all respect including interconnection, internal wiring with PVC copper cable its testing and approved of all items by HVPN including cost of all testing/approved charges of all items of HVPN including cost of all labour & material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-Charge ofthe work.
N.S - 4 Supply and erection of Fire extinguisher ISI mark Co2 type of 4.5 Kg. capacity as per IS 7285 duly erected / hung on wall with hooks with all labour & petty material required to complete the job in all respect upto the entire satisfaction of Engineer-in-Charge of the work..
N.S - 5 Supply & Erection of MS Bucket Stand made of 32 x 5 mm angle iron / channel iron suitable for 6 Nos. fire bucket including cost of 6 Nos. bucket, welding & painting of complete stand with one coat of red oxide and two coats of approved paint of red color with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-Charge of the work.
N.S - 6 S/E of 11 KV gang operated switch 'Jayshree make' conforming to IS with latest amendment including suitable size of copper blade erection of same on the existing 'H' pole fixed with angle of size 50x50x6mm, suitable size of MS clamp, nuts & bolts including cost of 6 Nos. 11 KV insulator with GI Pin, RD fuses and painting with 2 coats of approved paint and one coat of red oxide material required to complete the job in all respect utpo the entire satisfaction of Engineer-in-charge of work..
N.S - 7 Supply & erection of lightening Arrestor Model SDU ALPRO make suitable for 11 KV 3 Phase 50 Hz grounded neutral system comprising of Speek gap type ( Quench gap type ) in series with non liner resister element housesed in horizontally Scale porcelain bushing with line and ground terminal along with mounting clamps Conforming to ISS 3070 (Part-1) of 1985 with latest amendment with all labour and material required to complete the job in all respect utpo the entire satisfaction of Engineer-in-charge of work.
N.S - 8 Providing and fixing of stay set complete with stay wire with dis insulator as per specification upto the entire satisfaction of Engineer-in-charge of work..
N.S - 9 Providing and fixing of wire mesh jali around the transformer of size 4'x 8' made out of 75 x 25 x 3.25 mm jali fixed with angle iron frame made out of M.S. angle 50 x 50 x 6 mm support of M.S. flat 50 x 6 mm and fixed in C.C. Block 1:2:4 including cutting, welding etc. as per drawing complete in all respect upto the entire satisfaction of the Engineer-in-Charge.
N.S - 10 Erection of MS Angle 50 x 50 x 6 mm, M.S. flat & nuts & bolts including cutting, bending to the required shape drilling holding carriage, painting loading & unloading complete in all respect
Chopra Electric Company
PS ELECTRIC
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .