Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| 5 | Not Admitted-Fee/PreQual/Technical 19 A DURGA BARI SADAR BAZAR MEERUT MEERUT MEERUT UTTAR PRADESH 250001 | MEERUT | UTTAR PRADESH | 250001 | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹28.8 L
EMD Value
₹30,000
Closing Date
20 May 2023, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE ETC MEERUT
130 D PAARESHAN BHAWAN VICTORIA PARK MEERUT
work of increasing capacity including shifting of 132 KV Transfer Bus Coupler and Strengthening of existing 132 AND 33 KV Main Bus Bar at 132 KV S/S Lohiyanagar under ETD Meerut
2023_UPTCL_799972_1
T-03/23-24/ETC/MT
Open Tender
Electrical Works
Item Rate
60 days
MEERUT
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,770
SE ETC MEERUT
₹30,000
17 Jul 2023
2 May 2023
22 May 2023
2 May 2023
20 May 2023
2 May 2023
Amount
Supply
Bolted type single Tension fitting for Twin Moose Conductor with turn buckle suitable for 1x10 No Disc insulator complete with hardware set as per technical specification.
Bolted type single Tension fitting for Twin Moose Conductor without turn buckle suitable for 1x10 No Disc insulator complete with hardware set as per technical specification.
Bolted type single Tension fitting for Panther Conductor suitable for 1x10 No Disc insulator complete with hardware set as per technical specification.
Bolted type single Suspension fitting for single Moose conductor suitable for 1x10 No Disc insulator with hardware set as per technical specification.
132 KV Tandom Isolator clamp suitable for Twin zebra/ Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
132 KV Bus Isolator clamp made of aluminum alloy LM-6 Alloy suitable for Twin Zebra / Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
132 KV Circuit Breaker clamp made of aluminum alloy LM-6 Alloy suitable for Twin Zebra / Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
132 KV Bimetallic CT clamp made of aluminum alloy LM-6 for Zebra / Moose conductor with HDG nut & bolts and washer as per Technical specification.
132 KV LA clamp made of aluminum alloy LM-6 Alloy suitable for Panther conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
Supply of 36 KV Bus Post Insulators
132 KV Section Isolator clamp twin Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
Bimetallic terminal connector for 40MVA T/F HV side bushing rod 30 mm dia made of aluminum alloy LM-6 suitable for ACSR Zebra /Moose conductor of matching with bushing rod complete with hot dip galvanized nut & bolts as per technical specification.
Bimetallic terminal connector for 40 MVA T/F LV side bushing rod 30 mm dia made of aluminum alloy LM-6 suitable for Twin Zebra /Moose conductor matching with bushing rod complete with hot dip galvanized nut & bolts as per technical specification.
Bolted type double tension fitting for Twin Moose conductor with turn buckle suitable for 1x4 No disc insulator with hardware set as per technical specification.
Bolted type double tension fitting for Twin Moose conductor without turn buckle suitable for 1x4 No disc insulator with hardware set as per technical specification.
3 Bolted Type PG clamp suitable for Panther to Panther conductor Complete with HDG nut bolt & washer as per technical specification.
4 Bolted Type PG clamp suitable for Panther to Moose conductor Complete with HDG nut bolt & washer as per technical specification.
4 Bolted Type PG clamp suitable for Zebra to Moose conductor Complete with HDG nut bolt & washer as per technical specification.
4 Bolted Type PG Clamp suitable for Zebra to Panther conductor complete with HDG nut bolt & washer as per technical specification.
33KV Bus post clamp suitable for Twin Moose conductor complete with hot dip galvanized nut bolts & washer as per technical specification.
Bimetallic 33 KV CT clamp made of aluminum alloy LM-6 for Twin Moose conductor with HDG nut & bolts and washer as per Technical specification.
33 KV Circuit Breaker clamp suitable for Twin Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
33 KV Bus Isolator clamp Twin Panther conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
33 KV P.T clamp suitable for Panther conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
33 KV LA clamp suitable for Panther conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
33 KV Section Isolator clamp twin Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
Spacer for 100 mm spacing for Twin Panther Conductor 02 Bolted completed with hot dip galvanized nut, bolts & washer as per technical specification.
Spacer for 60mm spacing for Twin Panther Conductor Single Bolted completed with hot dip galvanized nut, bolts & washer as per technical specification.
Spacer for 250 mm spacing for Twin Moose Conductor 02 Bolted completed with hot dip galvanized nut, bolts & washer as per technical specification.
Supply of cable gland of different sizes
i. 2C x 2.5 mm (16mm)
ii. 4C x 2.5 mm (19mm)
iii. 6C x 2.5 mm (22mm)
Shifting of 132 KV TBC Bay, Installation of 40 MVA Transformer
Erection of Main & Auxiliary Sub-Station Structure for 40 MVA Transformer Bay and 132 KV TBC Bay
Erection of Main & Auxiliary structure lattice type ATM, ABL, BCT, ALP, BPL etc. consisting of column, beam, peak, mast etc. and auxiliary structure for installation of isolator, CTs, PTs, LA etc. erection of structure as per drawing with the help of GI nuts & Bolts flat spring washer matching the hole, cutting and matching the member if required include cost of all men and T & P excluding GI structure nut and bolts to complete the work erection of main & auxiliary structure lattice type ATM, BTM, AXM, ABL, CCM,CGM, EKR, BBR, BCT, ALP, BPL, BTI etc. upon foundation and its proper tightening.
Erection of following equipment as per instruction manual of various equipment’s and technical specification including shifting of material / equipment from store to erection site including all other associated works to complete the job satisfactorily.
145 KV Circuit Breaker
36 KV Vacuum Circuit Breaker
145 KV Current Transformer
36 KV Current Transformer
145 KV CT junction box.
36 KV CT junction box.
145 KV Bus Isolator
145 KV Tandom Isolator without earth switch (Non-Motorized)
145 KV Bus Post Insulator
36 KV Bus Isolator
120 KV Lighting Arrestors
30 KV Lighting Arrestors
Erection of following control and relay Panels as per instruction manual and technical specification including shifting of panel from store to erection site including all other associated works to complete the job satisfactorily.
132 KV control relay panel for 40 MVA Transformer.
40 MVA RTCC Panel.
Stringing of various main, Transfer bus bar and jack buses of 132/33 KV for all three phases with different type conductor and different length of span as mentioned below .the work includes cutting &bending of conductor fixing of single /double bolted type tension fitting /suspension hoisting of disc Insulator and shifting of material from store .site to erection site and all other associated work to complete work satisfactorily as per drawing and technical specification.
132 KV Jack Bus of panther conductor for 40 MVA Transformer
132 KV Main bus of Twin Moose for Main Bus Extension @ Rs.
132 KV Transfer bus of single Panther of Transfer Bus Extension
Bay wise interconnection of equipment with specified conductor of various 132 KV & 33 KV Equipment with Main /Transfer / jack Bus bar of ACSR Zebra /Panther conductor. The work Includes cutting of conductor. Bending in proper shape .clamping with the help of clamp and all other associated work to complete job.
40 MVA Transformer Bay 132 KV side
33 KV side Transformer bay Twin Moose
132 KV Main/Transfer Bus jumper (3X4) for 132 KV TBC Bay
Laying of following size control cable in trench/cable trays from different control room equipment to 132/33 KV Isolator, circuit breakers CT/PT & their junction boxes. Transformer marshaling box. Isolator box & other outdoor equipment’s installed in 132/33 KV switch yard as per cable schedule. Including carriage of cable drum from store and all other associated work.
Control cable of size 2 core x 2.5 mm2
Control cable of size 4 core x 2.5 mm2
Control cable of size 6 core x 2.5 mm2
Termination of cable laid as as per cable schedule including making necessary hole in laid plates or box wherever required, fixing cable glands of appropriate size and ferruling of each core and other associated work to complete the job satisfactorily. Rates of termination of control cables including the all cores of cable and one end with lugs.
Laying of 40 mm size M S round bar blow 700 mm from ground level including cutting straightening welding painting of joints excavation of trench its back filling and all other associated work to complete the job Note : work required for shifting of 132 KV TBC Bay
Fabrication of 3 Meter long electrodes with following MS Rod having 150 mm long conical shape and then its placing vertically inside the ground with 700mm below ground level including cutting turning and machining of electrode. Note : work required for shifting of 132 KV TBC Bay
Making cross joint of above laid 40mm dia MS Round bar 700mm below the ground level by due welding at all 4 corners including welding of suitable size 2 Nos. MS angle Pieces on opposite corner of the cross joint, Note : work required for shifting of 132 KV TBC Bay
Making of end joint of above laid 40 mm dia MS round bar with top of the already vertically pierced MS electrode 700 mm below the ground level by due welding. Note : work required for shifting of 132 KV TBC Bay
Making of the 300 mm long lap joint of above already laid round bar to connecting existing earth mat of the substation. Note : work required for shifting of 132 KV TBC Bay
Installation work of 40 MVA Transformer.
Shifting of main tank of 40 MVA Transformer from unloading point to the plinth up to 30 Mtr distance including turning of tank if required including all T & P and labour required to complete the job satisfactorily.
Complete erection of 40 MVA 132/33 KV Transformer by erection of radiator, conservator t ank all bushing oil pipe lines, cooling fans etc. to complete the job satisfactorily.
Circulation of complete Transformer oil in Transformer tank through centrifuging machine, centrifuging machine shall be provided by the contractor, oil capacity (Approx 20 KL)
Laying & Termination of following size PVC power cable from ACDB /DCDB installed on control room / 33/.04 KV station Transformer marshaling box etc. in 132/33 KV switchyard in side 500mm below ground level including excavation of trench & laying on its edge along with cable of both side filling the same with Ganga sand and then putting the bricks on 115mm side cover the trench & then filling with earth. Proper termination at both side by providing crimping type aluminum lugs as per requirement including cost of bricks sand cable route marker as per cable schedule including carriage of cable drum from store and all other associated works.
Laying Power cable 31/2 core x 300 mm2 /150 mm2
300 mm2 Power cable termination.
Fabrication of 3 meter long electrode with 40 mm dia M S round bar having 150 mm long conical shape by digging cutting, straightening etc. and then placing it vertical. inside the ground with Top 700mm below the ground level including shifting of MS round bar from storage place at the Sub-Station to switchyard.
Delta earthig of 120/33 KV LA's of 132 KV Lines and 40 MVA Transformers neutral by consisting of 3/6 Nos. 3.0 Mtr long electrode of 40mm dai having 150mm long conical shape, its placing inside the ground in rectangular/triangular shape and connection all 3/6 Nos electrodes with 75x10/50x6mm MS flite laid on its edge and then this rectangle/tringle shape be connected to main earth mat at two place in opposite direction strictly as per drawing.
120 KV Lighting Arrestors (Rectangle shape 6 electrode )
30 KV Lighting Arrestors (Rectangle shape 6 electrode )
132/33 KV 40 MVA Transformer (Triangular shape 3 electrode)
Earthing of equipment’s by cutting straightening, bending, laying 700mm below ground and above ground of following size of MS flat for earthing of main and auxiliary structure, equipment’s structure. Transformer body and its neutral point including welding with main earthmat and with object to be earthed excavation of trenches its back filling including painting of MS flat of different size after cleaning of rusted surface 1st coat of Red Oxide and 2 coat of Bus Green Paint to complete the work All other associated work as required to complete the work.
Laying of MS Flat of size 75x10 mm
Laying of MS Flat of size 50x6 mm
Laying of MS Flat of size 25x6 mm
Periphery and switchyard lighting
Providing and fixing of half round GI pipe OD-50mm for mounting the 120 Watt LED light upon gantry mounting of 2 No GI bracket up on gantry and fixing GI pipe complete with nut bolt and washer as per technical specification.
Providing and fixing of junction box on gantry structure with 1 No MS flat 40x5 mm of size 200x200x150 mm made of MS sheet of 16 gauge dully powder coated inside mounting 1 No 6 Amp MCB 1 No TB of 4 terminal & 1 No Kit Kat 16 Amp fixed upon mica sheet and back side mounting a flat 40x5 mm with 1 No 16mm dia hole and mounting PVC pipe from ground level to box as per technical specification.
Supply & fixing of new generation energy saving and environment friendly long life versatile pressure die cost aluminum outdoor high been flood light 120 Watt LED as light source and exclusively designed polycarbonate cover along with electronic driver complete fitting suitable for 220 V input supply for ISI make CGL/Hevells/ Surya/ Philips/Bajaj of equivalent etc. including electrical connection also to be done by the contractor.
Shifting and Modification of 250 KVA, 33/0.4KV Station Transformer
Dismantling of 250 KVA Station Transformer including dismantling of foundation.
Erection of 132 KV Auxiliary structure lattice type ALP & BBL consisting of PI, Isolator. Erection of structure as per drawing with the help of GI nuts & Bolts flat spring washer matching the hole, cutting and matching the member if required include cost of all men and T & P excluding GI structure nut and bolts to complete the work erection of auxiliary structure lattice type ALP, BBL upon foundation and its proper tightening.
Erection of 250KVA Station Transformer
Erection of 36 KV Bus Isolator i
Erection of fuse set
Jumpering of following equipments from main bus bar by opening of all associated clamp step by step during bus bar ACSR panther conductor
Strengthening of 132 and 33 KV Main Bus Bar
132 KV Main Bus
Dismantling of existing 132 KV Bus bar of ACSR Zebra conductor along with tension fitting and disc insulators including shifting and proper staking of dismantling material in the store.
132 KV Main Bus (3 Nos. section of 03 Phases) @ Rs. 5900 per Phase
Dismantling of jumpers of 132 KV Main Bus bar with various type of equipments including cutting of conductor and shifting & proper staking of dismantled material in the store.
132 KV Jumpers
Stringing of Main Bus of 132 KV with Twin Moose ACSR conductor of different length of span as mentioned below. The work also includes cutting & bending of conductor fixing of single /double bolted type tension fitting /suspension hoisting of disc Insulator and shifting of material from store site to erection site with all other associated work to complete work satisfactorily as per drawing and technical specification.
132 KV Main Bus of Twin Moose of 3 Section of 03 Phases
Bay wise interconnection of equipment with specified conductor of various 132 KV Equipment with Main /Transfer / jack Bus bar of ACSR Zebra or Panther conductor. The work Includes cutting of conductor & bending in proper shape, clamping with the help of clamp and all other associated work to complete job.
132 KV Main Bus of Twin Moose
Dismantling of existing 33 KV Bus bar of ACSR Zebra conductor along with tension fitting and disc insulators including shifting and proper staking of dismantling material in the store.
33 KV Main Bus Bar of 2 section of 3 phase
Dismantling of jumpers of 33 KV Main Bus bar with various type of equipments including cutting of conductor and shifting & proper staking of dismantled material in the store.
33 KV jumpers
Stringing of 33 KV Main Bus Twin Moose conductor of different length of span as mentioned below. The work includes cutting &bending of conductor fixing of single /double bolted type tension fitting /suspension hoisting of disc Insulator and shifting of material from store site to erection site and all other associated work to complete work satisfactorily as per drawing and technical specification.
33 KV Bus Bar Twin Moose of 2 section of 3 phase
Bay wise interconnection of equipment with specified conductor of various 33 KV Equipment with Main /Transfer / jack Bus bar of ACSR Zebra /Panther conductor. The work Includes cutting of conductor. Bending in proper shape .clamping with the help of clamp and all other associated work to complete job.
33 KV Main Bus Jumpers Twin Panther
Perfect Power Transformer Associates
SATKAR TRADERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .