| 1 | L1₹8.0 LAccepted-AOC WARD NO 40 REGRON KA MOHALLA NEAR RAVI DASS JI MANDIR SHIV BARI BIKANER RAJSTHAN 334001 | BIKANER | RAJASTHAN | 334001 | L1 | Accepted-AOC Lowest Bid L1 rank is competitive and reasonable during Scrutiny amongst bidders | |
| 2 | L2₹10.2 L+₹1.9 L (23.2%)Rejected-AOC | L2 | Rejected-AOC Being not lowest |
Tender Value
₹9.6 L
EMD Value
₹19,100
Closing Date
18 Sept 2023, 6:00 pmClosed
CWE
CWE AF BAMRAULI
REPAIR MAINT OF VCB, TRANSFORMERS, HT UG CABLE, OH ACSR CONDUCTOR ALLIED WORK AT AF STATION DARBHANGA UNDER GE AF BIHTA
2023_MES_612931_1
87253/E8
Open Tender
Electrical and Maintenance Works
Item Rate
182 days
DARBHANGA
Class E Category b ii and other criteria as per NIT and Tender Doc
7 documents required · 7 mandatory
₹500
GE AF BIHTA
₹19,100
Yes
5 Dec 2023
12 Aug 2023
21 Sept 2023
12 Aug 2023
18 Sept 2023
30 Aug 2023
12 Aug 2023 - 19 Aug 2023
Amount
Supply and laying synthetic Rubber insulating mat of size 2m X 1m X 2.5mm for voltage upto 11 KV complete all as specified and directed
S&F in replacement of Pin type,porcelain ,vitreous,white , brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height and 150 mm dia for 11000 volt grade complete all as specified and directed .
S&F in replacement of Disc type insulator, porcelain, vitreous, 145 mm height and 255 mm dia , ball and socket type, white, brown or green single disc assembly complete all as specified and directed. .
Dismantling cross arms of mild steel channel or angle section from the pole and setting out complete all as specified and as directed.
S&F cross arms, bracings, suports, clamps, back plates etc., fabricted with strututral steel sections including bolts, nuts, washers etc., welding , bending cold or hot,drilling holes for bolts,in any shape or size,as indicated or as directedincluding applying two coats of synthetic enamel paint over one coat of red oxide primer including preperation of steel surfaces complete all as specified and as directed.
S&F Danger Notice board made out of 1.6 mm thick mild steel sheet of size 25 cm X 20 cm , vitreous, enamelled white with letters , figures and conventional skull and bones in signal red colour and fixed with mild steel clamps, bolts, nuts for HT 11000 Volts complete all as specified and as directed.
S&F Lightning Arrestor, expulsion type complete with all fittings, transmission class, discahrge capacity 65 Kilo amps suitable for 11000 Volts complete all as specified and as directed.
M&L for painting of transformer 100 to 315 KVA by scrubbing out dust, dirt and oil from all places and applying two coats of grey synthetic enamel paint by spray machine, writing MES/SM No as per existing pattern inluding disconnecting and taking down including reconnecting and refixing the same in its position complete all as specified and as directed.
Taking down/refixing defective transformer upto 315 KVA capacity and VCB from poles/structures after disconnecting all electrical connections removing to sub station or workshop as directed, placing the repaired transformer in place of taken down defective transformer including transportation, loading, unloading of transformer from sub station to work site or work shop and connecting HV and LV side including all connecting and jointing materials such as suitable size of lugs, bolts, nuts etc complete all as specified and as directed.
Opening/striping off transformer 11 KV/0.433 KV step down capacity upto 315 KVA including draining off oil, lifting the core and coil assembly washing and cleaning dust, dirt and sludge deposit etc from all parts, removing damaged or defective parts requires replacement, making internal connection, servicing of tap changer and re assembling the transformer after repair and replacement work including new cork sheet gasket, packing, nuts, bolts, washer etc as required filling fresh transformer oil and testing complete including replacement of the following items:- (a) High voltage/low voltage coil including double paper insulated conductor of same gauge as per existing and all insulating material varnishing with vaccum impregnation and baking of coil suitable for upto 315 KVA capacities of step down transformers of aluminium/copper wound. (b) HV bushing of 12 KV grade with gasket complete. (c ) LV bushing of 1100 volts grade with gasket suitable for transformer upto 315 KVA capacity (d) LV brass studs with brass nuts, check nuts, washers etc complete for transformers upto 315 KVA complete. (e) HV brass studs with brass nuts, check nuts, washers etc complete for transformers upto 315 KVA complete. (f) Replacement of breather with fresh filling of silica gel 0.5 Kg capacity in non metallic transparent enclosure for transformer up to 500 KVA capacity complete. (g) Insulating transformer oil conforming to IS-335 for filling/toping up of transformers not less then 100 litre quantity duly filtered having dielectric breaking strength not less than 40 KV at the gap of 4mm complete.
Maintenance and complete overhauling and calibration of 11 KV VCB including dismantling of Vaccum intrrrupter bottel, trip coil,closing coil, Auxilary switch, spring limet switch,braker limet switch mechanical parts, well cleaning with petrol and CRC-226, replacing of moving parts, reassembly, fine setting of mechanism, replacement of unserviceable parts and reassembly of parts including well cleaning the complete panel board decarburization of all joints, metal parts and making VCB perfect operating condition including all routine and preventive maintenance complete and Servicing of HT,11 KV,VCB, 50 Hz,breaking capacity 630Amp , 20 KA trolly by drawing out from panel chamber including removing carbon deposits from moving/fixed contact points,greasing and tightening all fixed and moving contacts for smooth functioning including replacement of tripping and closing coils as per existing and servicing of solenoid switch all as specified and as directed including supply and fixing the following accessories :- (a) Voltage meter HT - 1No (b) Amp meter -3 Nos (c ) LED Indicating lamp RYB - 3 Set (d) 3 PH Overcurrent & earth fault relay Art no 1MYN742838 Make ABB - 02 Nos (e) Vaccum intrrrupter bottel (f)Trip coil (g) Closing coil (h) Auxilary switch (i) Spring limet switch (j)Braker limet switch (k) Relay
Supply and filling insulating transformer oil conforming to IS-335 for filling or toping up of transformers as required at site duly filtered having dielectric strength not less than 50 KV at 4 mm gap complete all as specified and as directed. Note :- Transformer oil shall be brought at site in sealed drum.
Dehydration of transformer oil both factory and site of work including heating, filtration, cleaning and testing required upto dielectric strength 50 KV in 4mm gap and testing to the satisfaction and after dehydration complete all as specified and as directed.
Cutting / trimming and removing tree branches close to the or touching the electric overhead lines HT / LT or at sub stations etc by climbing on the tree with necessary safety precautions, tools ,removing , transporting the cut branches from site and depositing where directed at a distence not exceeding 300 m complete all as specified and as directed. Note :- Shut down of electric supply shall be taken before commencement of work. Any damage to existing OH lines / services etc shall be made good without any extra cost.
M&L cleaning and preperation of surfaces by scrubbing with wire brushes, emery papers etc from all metalic surfaces of mild steel tubular HT electric poles , any type , any model not more than 11 m long including cross arms, clamps etc any size on the same pole and applying one coat of aluminium paint on pole,cross arms, clamps, GI pipes brackets etc including writting of pole number as per existing size and pattern complete all as specified and as directed.
S&F in replacement of Air break gang operated switch , HT, 11000 volts,Triple pole mechanically operated, vertical/horizontal ,mounted on insulators and steel frames with operating mechanism worked from ground level with operating rod, handle etc for current rating up to 400 Amps fixed on pole or stuctures complete all as specified and directed .
Supply and laying cable 95 Sqmm 3 core , XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 11000(E) Volts grade with stranded aluminium conductor including taking out old unserviceable cable from trenches or duct or pole,complete all as specified and directed .
S&F Cable joining kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm complete all as specified and directed.
S& F Cable joining kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm complete all as specified and directed.
Excavation In trenches not exceeding 1.5 m In depth and not exceeding 1.5 m width and getting out in soft/loose soil for laying of cables or pipes, erection of poles, stays, cable fault detection etc complete all as specified and as directed.
Returning, filling in, including spreading leveling watering with ramming in layers not exceeding 25cm thick in soft/loose soil complete all as specified and as directed.
Removing excavated soil not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and as directed.
Supply & laying sand cushioning for cable protection in trenches 8 cm thick before laying cable and 15 cm thick over the cable and punning down to 18 cm complete all as specified and ditected. Note:- Punned thickness shall be measured and paid.
Supply & laying brick sub class 'B for protection of cable laid dry flat across the cable with width equal to the length of whole bricks complete all as specified and ditected.
Dismantling of existing unserviceable stay assembly complete all as specified and as directed
M&L for stay assembly having diameter of stay rod 20 mm complete with accessories as shown in electrical plate No. 1 of SSR Part-I 2009 complete all as specified and directed. Note :- Loop type insulator, stay clamps, excavation and earth work including concrete shall be measured separately under respective item as considered therein.
M&L Cement concrete 1:3:6 type C-2 using 40 mm graded stone aggregate as foundation and mass concrete including necessary use and waste of form work as required complete all as specifed and as directed.
M&L Cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregate in foundation and mass concrete complete all as specified and directed.
M&L for earthing complete with copper plate 60cm×60cm ×3 mm thick electrode and buried directly in ground vertically to a depth not less than 2.25 m below normal ground level (with top edge of earth plate not less than 1.5 m below ground level) connected to copper strip 25mmx3mm main earthing lead by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I 2009 with connected to earth test point and to main switch board including adequate quantity of charcoal dust and common salt alround earth plate and 40 mm dia GI pipe light grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia light grade for watering pipe with funnel and wire mesh including necessary excavation and earth work, PCC 1: 3 : 6 type C-1 using 20 mm graded stone aggregate as in earth pit and 40 mm thick precast RCC cover in 1 : 2 : 4 type B-1 using 20 mm graded stone aggregate reinforced with 8 mm dia TMT bars @ 75 mm c/c both ways with 12mm dia mild steel round bar handle complete all as specified and directed including testing on completion. NOTE:- Earth lead wire and its protection pipe upto and including 7.5 m only from the top of earth electrode are included under this item and additional earth strip/protection pipe if any required at site shall be measured and paid for separately under respective item.
S&F Earth continuity conductor or main earthing lead 25mm X 3mm, aluminum strip fixed in any position including jointing by existing tinned copper/brass nuts, bolts and washers and brazing with gas welding using brass electroded complete all as specified and directed.
S&F Earth continuity conductor or main earthing lead 20mm X 3mm, copper strip fixed in any position including jointing by existing tinned copper/brass nuts, bolts and washers and brazing with gas welding using brass electroded complete all as specified and directed.
S&F HT cable joining kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with joining material and accessories suitable for 35 Sqmm , 3 core XLPE armored aluminum cable complete all as specifed and as directed.
S&F HT cable joining kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with joining material and accessories suitable for 95 Sqmm , 3 core XLPE armored aluminum cable complete all as specifed and as directed.
S&F HT cable joining kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with joining material and accessories suitable for 185 Sqmm , 3 core XLPE armored aluminum cable complete all as specifed and as directed.
Dismantling of old unserviceable Steel tubular pole 11.00 m long and removing from site complete all as specified and directed.
Supply and erection of steel tubular swaged pole , type 410-SP 55 (LT 11.00 mtr long pole) complete conforming to IS: 2713 complete with CI base plate, pole cap, bolts, nuts and screw complete all as specified and including of following works:- (a) Excavation in trenches as required , returning filling and disposal of surplus soil to a distance not exceeding 50 m (b) PCC 1:4:8, type D-2 using 40mm graded stone aggregate in foundation 900mmx600mm cross section and planting depth 1.5 m for concrete encasing the pole upto GL (c) PCC 1:3:6, type C-1 using 20mm graded stone aggregate for plinth block/collar above GL 500mm high and 450mm dia (d) Painting of pole externally with one coat of black bituminous paint (upto planting depth) and above plinth block concrete collar with two coat of aluminum paint over a coat of red oxide primer including preparation of surface andpainting of 30 cm wide bands 3 Nos with synthetic enamel paint of appropriate colour in alternate layer upto the height of 1.5mm above plinth block (e) Writing letter or figures (Block Roman, Italic as Indian) with thick synthetic enamel paint of apprised shade not exceeding 5 cm height including numbering of pole (f) Painting of coping with two coats of cement based paint . Note : Manufacture's test certificate shall be produced alongwith purchase vouchers .
M/S Akash Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .