Loading…
Loading…
Tender Value
₹23.1 L
EMD Value
₹46,100
Closing Date
1 Sept 2026, 5:00 pm
NITIN MODI
Gurgaon PHED
Replacing and Repair of guide pipe, dual screen D.O meter sensor , air blower, detritus unit , existing actuators and centrifuge unit and V.F.D. etc.
2026_HRY_542866_1
20268F5F7B9F 2E2E 41AC 8C09 CFA08B85F3B9557PUH
Open Tender
Civil Works
Works
90 days
Farukh Nagar
2 documents required · 2 mandatory
₹2,500
₹46,100
Yes
22 Aug 2026
22 Aug 2026
2 Sept 2026
22 Aug 2026
1 Sept 2026
22 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Provision for replacing of guide pipe and chain for MPS
Motors. | - | Nos. | 100 | - |
| 2 | Provision for providing and fixing open channel digital
flow meter for outlet and inlet including sensor and all
accessories including integration in PLC and link with
website of HSPCB and CPCB. | - | Nos. | 100 | - |
| 3 | Provision for Repair of detritus unit including civil and
mechanical work | - | Nos. | 100 | - |
| 4 | Provision for repair of 5 nos. existing actuators and
replacing of 1 no. actuators | - | Job | 100 | - |
| 5 | Providing, Installation, Testing and Commissioning of
Dissolved Oxygen Meter with 2 Probes , each in SBR
Aeration Tanks with LED Display , Electrical Panels,
Mounting and all related works | - | No. | 100 | - |
| 6 | Supplying, erection, testing and commissioning
Variable frequency drive for 15 HP motor of centrifudge
of stp and to ensure that there is no voltage drop ,
Variable frequency drive IP66 with mains Disconnect
having Modbus Communication and designed at 50
Degree Celsius without any deration with inbuilt real
time clock for time assistance. Variable frequency drive
All Electronic cards should be 3C3 Coated. Variable
frequency drive with Dual DC choke at both the Limbs
with 5 % Impedance. Variable frequency should be
having all protection features like Dry Run detection,
Deragging, Automatic energy optimization, Low flow
detection, sleep mode, complete in all respect including
earthing and its connection, erection and commissioning
complete in all respect to the entire satisfaction of
engineer in charge. | - | Nos. | 100 | - |
| 7 | Providing and fixing IOT device (RTRU 301 CEMS,
Spare, RTRU 301 Varient 2 with In built RS 485
Splitter, Sim slot, 2x RS 485, 2xD , ETH, 4G, AI ,
HART, 24 VDC with panel inclulding one year Data
transmission at CPCB / HSPCB and Remote AMC | - | Job | 100 | - |
| 8 | Repairing of electrical panels and replacement of
damaged/burnt panel accessories i.e. contactor 50 Amp.
= 4 Nos., Overload relay= 4 Nos., MCCB= 8 Nos. for
MPS and blower motor | - | Job | 100 | - |
| 9 | Providing and fixing, testing and commissioning of
Stainless Steel Progressive Cavity (Single Screw) Pump
having capacity 5.0 m³/hr at 10 bar pressure with 11 kW
motor, complete with stator, rotor, coupling, base frame
and all allied accessories complete in all respects. | - | Job | 100 | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.78 MB
BOQ_622361.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].