Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.7 LAccepted-AOC | ₹20.7 L Quoted ₹22.5 L | L1 | Accepted-AOC Being Lowest Bidder. |
| 2 | L2₹25.4 L+₹2.9 L (12.7%)Rejected-Finance | ₹25.4 L+₹2.9 L (12.7%) | L2 | Rejected-Finance Being L2 |
| 3 | L3₹27.9 L+₹5.4 L (24.2%)Rejected-Finance | ₹27.9 L+₹5.4 L (24.2%) | L3 | Rejected-Finance Being L3 |
Tender Value
₹12 L
EMD Value
₹24,000
Closing Date
4 Apr 2020, 6:00 pmClosed
GE (South) Patiala
MILITARY ENGINEER SERVICES GARRISON ENGINEER SOUTH TARAPORE ENCLAVE PATIALA CANTT
As per tender document
2019_MES_307012_3
GE(S)/PAT-38/P/2019-20
Open Tender
Civil Works
Item Rate
150 days
MIL Stn Patiala
Refer tender document
6 documents required · 6 mandatory
₹500
Yes
GE South Patiala
₹24,000
Yes
21 Apr 2020
16 Mar 2020
6 Apr 2020
16 Mar 2020
4 Apr 2020
23 Mar 2020
16 Mar 2020 - 21 Mar 2020
Amount
Disconnecting the electrical connections from LT panel board, taking out from sump well 40 HP electric motor pump set non clogging self priming 100x125 mm size Horizontal/ vertical type disconnecting input and output sewage connections by manual/mech arrangements, dismantling the motor and carrying to workshop for repair and carrying back the after repair, reconnecting with pump set, fixing on foundation in sump well and testing, commissioning to the entire satisfaction of Engineer-in-Charge. (Including taking out pumping set from sump well and lowering the same after repair.)
All as per serial item No 1.00 here-in-before but 20 HP pump set non clogging self priming 100 x 125 mm size.
All as per serial item No 1.00 here-in-before but 12.5 HP pump set non clogging self priming type (Horizontal/Vertical type)
All as per serial item No 1.00 here-in-before but 7.50 HP 415 Volts, 3 phase pump set non clogging self priming tube (Horizontal/Vertical type)
All as per serial item No 1.00 here-in-before but 5.00 HP submersible pump set non clogging 80 mm discharge.
Rewinding the electric induction motor 3 phase 400/415 Volts 40 HP, 50 C/S by opening the same carefully removing all windings and cleaning the slots properly and rewinding the same with copper binding wire of existing gauge including providing paper insulation sheets, bamboo sticks and applying two coats of varnish for proper insulation, reassembling the motor, testing and commissioning of motor on full load to the entire satisfaction of Engr-in-Charge complete. Note: (i) Unit rates also include taking out motor, dismantling and lowering after repair. (ii) Ball bearing, cooling fan if required to be replaced shall be measured & paid separately.
All as per serial item No 6.00 here-in-before but 20 HP motor.
All as per serial item No 6.00 here-in-before but 12.5/10 HP motor.
All as per serial item No 6.00 here-in-before but 07.50 HP motor.
All as per serial item No 6.00 here-in-before but 5.00 HP motor.
Supply only ball bearing of existing size and make in electric induction motor, 40 HP including applying correct grade grease before replacement.
All as per serial item No 11.00 here-in-before but 20 HP
All as per serial item No 11.00 here-in-before but 12.5/10.00 HP
All as per serial item No 11.00 here-in-before but 7.5/5.00 HP
Supply only for replacement cooling fan of electric induction motor 40 HP to suit the existing size of fan in replacement of fan nut bolt, keys etc all as directed by Engineer-in-Charge.
All as per serial item No 15.00 here-in-before but 20 HP
All as per serial item No 15.00 here-in-before but 7.5/5.00 HP
Supply only for replacement tyre coupling between motor and pump 40 HP complete with rubber tyre,CI/MS flanges and rings nuts, bolts, washers including lathe work for cutting holes for both shafts and providing keys and nut, bolts etc all as directed by Engineer-in-Charge.
All as per serial item No 18.00 here-in-before but 20 HP.
All as per serial item No 18.00 here-in-before but 12.5/10 HP.
All as per serial item No 18.00 here-in-before but 7.5/5HP.
Rewinding the submersible electric motor 3 Phase 400/415 Volts 12.5 HP 50 C/S by opening the same carefully, removing all winding and cleaning the slots properly and rewinding the same with PVC insulated copper binding wire of existing gauge including replacement of oil seal, water seal, refilling of oil, lubricants as per existing sizes, reassembling the motor, testing and commission of motor on full load to the entire satisfaction of Engr-in-Charge complete. Note: Unit rates also include taking out motor, dismantling and lowering after repair.
All as per serial item No 22.00.00 here-in-before but 35 HP motor.
Earthing with galvanized steel earth plate electrode 600 mm x 600mm x 6.3mm thick, burried directly in ground (earth pit not less than 4.5 metre deep below normal ground level) with top edge of the plate not less than 3.75 metre below normal ground level connected to galvanized earth lead GI strip 32x6mm thick by means of bolts, nuts check nuts and washers of galvanized iron or steel with protection pipe of GI, medium grade 40mm bore upto adequate length, watering pipe 20mm bore of GI medium grade, earth plate surrounded by picked layer of coal dust and common salt 15 cm thick all as per electrical plate No 5 of SSR of SSR -2009 Part I & including necessary excavation and earth work in any type of soil. The rates also include charcoal and salt in alternate layers, 20mm bore pipe (Light grade) for watering, protection pipe, funnel wire mesh, PCC chamber in cement concrete (1:2:4) type B-1, 40mm thick RCC (1:2:4) type B-1 cover (Reinforced with XPM not less than 3kg/sqm) and CI frame etc. and earth pit of size 30cm x 30cm x 45 cm including dismantling and taking up old unserviceable earthing complete all as directed.
Disconnecting the electric connection from LT Panel board, dismantling pump set non clog self priming 100 x 125 mm size horizontal/vertical type suitable for 40 HP motor complete after disconnecting input and output sewage connections by manual/mechanical arrangements and taking out pump from sump well including dismantling the pump and replacement of unserviceable part ie impellers, Gun metal bushes, stainless steel shaft, nut bolts washer etc, cleaning and reassembling pump including machine work for shaft, reinstalling the motor, as original and testing, commissioning to the entire satisfaction of Engr- in-Charge. Note: Unit rates also include taking out pump, dismantling and fixing after repair.
All as per serial item No 25.00 here-in-before but 20 HP.
All as per serial item No 25.00 here-in-before but 12.5/10 HP.
All as per serial item No 25.00 here-in-before but 7.5/5.00 HP.
Submersible copper cable for sewage pumps 3 core 1100 V grade, with copper conductor, 10 Sqmm including providing cable lugs/bottle lugs on cable end.
All as per serial item No 29 here-in-before but 25 sqmm
Cast iron sluice valve 100 mm dia PN-1 as per IS-780 with brass spindle and iron wheel head including providing new nut, bolt, washers and rubber insertion sheets on both ends and taking down the existing unserviceable valves.
All as per serial item No 31.00 here-in-before but 150 mm dia
All as per serial item No 31.00 here-in-before but 200 mm dia
Demolition of cement concrete un-reinforced in ground floors and pavings any thickness and in any position (above or below ground level) complete all as specified and directed.
Dismantling the base plate of motor and pump set and taking out from sump well.
Cement concrete 1:2:4 type B-2 using 40mm graded crushed stone aggregate as in foundation, mass concrete complete all as specified and as directed.
Material and labour for fabrication of base plate for motor & sump set fabricated from MS steel sections including fixing on foundation with nut,bolts,etc and applying two coats of synthetic enamel paint over a coat of red-oxide primer.
GI tube light grade (ISI marked) 40mm bore laid in trenches across road/nallah or fixed along with wall/pole including two clamp, 2 Nos FI of 40 x 6mm size with nuts, bolts and washers or laid in floors complete fixed as in repair for cable protection complete all as specified and directed.
MCCB TPN, 415 Volts, with suitable sheet metal enclosure, rupturing capacity 16 KA with adjustable thermal range capacity 40 to 63 Amp including making arrangements for fixing the MCCB all as directed by Engineer-in-Charge, fixed in replacement of old unserviceable MCCB.
All as per serial item No 39.00.00 here-in-before but capacity 100 Amp.
All as per serial item No 39.00.00 here-in-before but capacity 200 Amp.
Supply and replacement of copper bus bar fabricated with copper strip 25 x 6mm size and duly fixed on post insulators including taking down existing bus bar complete all as directed.
All as per serial item No 43.00 here-in-before but for 20 HP
All as per serial item No 43.00 here-in-before but for 12.5/10 HP
Supply and replacement of DOL starter 3 phase, 415 volt for centrifugal pump set 7.5 HP/5HP with over load relay, contactor ML 1.5 magnetic coil duly fixed in enclosure having relay setting suitable for 5/7.5 HP pump set including taking down existing unserviceable starter of any make & type.
All as per serial item No 48.00 here-in-before but 0-100 Amp
Supply and replacement of CT coils of ratio 100/5 Amps
Supply and replacement of push button for starter in three colour coding (R,Y,B) suitable for existing panels and connecting up complete.
Supply and replacement of phase indicating lamps in three colour coding (R,Y,B) and connecting up complete.
Supply and replacement of automatic electronic timer suitable for 5 HP to 40 HP star delta starter complete all as specified directed.
Supply and replacement non return valve 100 mm dia having rubber gasket on both sides, including nut bolts washers of required size and taking down existing unserviceable.
All as per serial item No 54.00 here-in-before but 150 mm dia
Material and labour for replacement of Gun Metal/Brass bush for 40 HP capacity pump set to suit the existing size of pump shaft complete all as directed.
All as per serial item No 56.00 hereinbefore but 20 HP
All as per serial item No 56.00 hereinbefore but 12.5/10 HP
All as per serial item No 56.00 hereinbefore but 7.5/5 HP
Dismantling the Monoblock/Tulu pump set 1.00 HP, single phase 230 Volt and carrying the pump to workshop for repair, replacement of required parts such as CI impeller, nut bolts, bushes, packing sheet etc.,servicing to motor, greasing etc including rebinding of the copper winding and making ready for fixing, bringing back the pump set and fixing in foundation and testing to the entire satisfaction of Engr-in-Charge.
Grinding the 40 HP pump set shaft/ sleeve on grinding machine and making it smooth for re-using in pump set complete all as directed.
All as per serial item No 61.00 here-in-before but 20 HP
All as per serial item No 61.00 here-in-before but 12.5/10 HP
All as per serial item No 61.00 here-in-before but 7.5/5 HP
Supply and replacement phase preventor of existing size of motor capacity 5 HP to 40 HP complete
Supplying, laying, jointing, testing and commissioning of XLPE insulated armoured electric power LT cable (heavy duty) with aluminium conductor 1100 Volts grade of cross sectional area 16 Sqmm 4 core complete laid on wall/pole complete all as specified and directed. Note : (i)Cable shall be laid in trenches, under road, across the nallahs, along pole/wall and in ducts. (ii) Excavation & earth work, pipe, clamp, sand cushioning and cable protection shall be measured separately.
All as per serial item No 66.00 here-in-before but cross sectional area 70 Sqmm 3.5 core
Supply and laying jointing copper cable multi stranded whether proof 16 sqmm three run copper conductor cables with & including one run 6 sqmm copper conductor cable as earth wire for connection to motor & starter with proper thimbles in and including with heavy duty PVC conduit 40mm dia or nearest size with proper clamps, screws, joints, bends etc. complete all as specified directed.
Supply and laying jointing copper cable multi stranded whether proof 10 sqmm three run copper conductor cables with & including one run 6 sqmm copper conductor cable as earth wire for connection to motor & starter with proper thimbles in and including with heavy duty PVC conduit 40mm dia or nearest size with proper clamps, screws, joints, bends etc. complete all as specified directed.
Taking down gear of Aerator unit with flaps of plant aeration motors & carrying to workshop for repair, servicing the gear unit and flaps and replacement of any spares as deemed necessary for proper working of gear units in filling gear oil upto marked level refixing the gear unit with motor and testing all as directed by Engineer-in-Charge.
Applying two coats of synthetic enamel paint to suction pipe, discharge line, pump, motor with frame and all type of fixture i.e sluice valve, non return valve etc as installed at sewage installation No. 5, 6, 7,11, 12, 13, 14 & 15 after preparation of surface including marking the direction of flow of Sewage, complete using colour code as directed by Engr-in-Charge.
Painting with two coats of synthetic enamel paint to DG set 160/62.5 KVA complete with spray painting complete all specified & directed.
Applying two coats of synthetic enamel paint to Aerator motor with gear including gear boxes along with connected equipments complete using spray painting system complete all directed.
Writing letters or figures (Block. Roman, Italic or Indian) n exc. 30 cm high with synthetic enamel paint on installation boards, pumps etc fixed at sewage installations according to design, pattern etc as directed by the Engineer-in-charge.
MS Work as in sign boards, valve pit cover, ventilators for sump well etc using PBI sheet, frames of angle iron or other section incl all necessary cutting, welding or drilling holes for fixing sheet complete all as specified and directed.
Preparing new or previously untreated surfaces of steel or iron work of any description and girth over 10cm and applying two coats of synthetic enamel paint complete all as specified and as directed by Engineer incharge.
Material & labour for fixing, jointing and testing Spun cast iron soil, waste and vent pipes 100mm dia, in any length with or without ears, with cement joints fixed to walls as in sump after taking out of old broken CI pipe complete all as specified & directed.
All as item No.77.00 here-in-before but size of pipe 150 mm dia.
All as item No.77.00 here-in-before but size of pipe 200 mm dia.
Cleaning the sewage sump wells, septic tanks of any size, depth and in any location by taking out complete sludge water and solids of any description, mechanically by HCV mounted suction discharge machine having blow back facility with sludge tank of adequate capacity removing & disposing the entire retrieved material to a distance not exceeding 1000 meter outside the periphery of defence land and covering the entire sludge with local earth complete all as directed by the engineer-in-charge. Note: Depth of sludge in the pit shall be measured from bottom of pit to the existing water/affluent level prior to ordering the cleaning in the presence of EIC.
Excavation in trenches not exceeding 1.5 meter wide and not exceeding 1.5 meter in depth for laying of cable in any type of soil complete all as specified and directed.
Return filling in approved soil,, including spreading levelling, watering and well ramming in layers n. exc 25 cm thick each complete all as specified and directed. (Surplus soil if any shall not be removed but left protrude over the trench as directed by Engr-in-Charge)
Sub class ‘B’ old size bricks laid adjacent to each other perpendicular to the direction of cable in trenches for protection of cable all as specified.
Clean dry sand laid in trenches/ducts for bedding and cushioning to cable, including spreading and levelling complete, all as specified and directed. Note:-(i) Consolidated/punned sand shall be considered for the purpose of payment.(ii) Sand shall be same as specified for plastering work.
Shivam Engg and fabricators
AR CONSTRUCTIONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .