Executive Engineer Medical And Health Chittorgarh
Executive Engineer Medical And Health Chittorgarh
3. Fire Fighting work at CHC Dungla, Distt. Chittorgarh
2026_MEDIC_604023_3
NIT No 04/2026-27 EXECUTIVE ENGINEER MEDICAL AND HEALTH CHITTORGARH
Open Tender
Electrical Works
Percentage
120 days
CHITTORGARH
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
RTGS-NEFT TO CANARA BANK AC 3034101004985
₹1.4 L
14 Oct 2026
14 Oct 2026
27 Oct 2026
14 Oct 2026
26 Oct 2026
14 Oct 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Fire Detection System | - | - | - | - |
| - | SITC of UL 10th edition / EN54 / VDS certified Automatic Floating Sensitivity type Analog addressable Multi criteria (two optical/Smoke sensor to reduce false alarm) detector with mounting base & LED etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | 220 | Each | 3,104 | ₹6,82,880 |
| - | SITC of UL 10th edition / EN54 / VDS certified Addessable Manual Call point (MCP) with LED / FIRE Indication Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | 12 | Each | 3,509 | ₹42,108 |
| - | SITC of UL 10th edition / EN54 / VDS certified Addressable sounder with strobe light, Loop Powered / Direct powered from FACP with sound level 90 dB and programmable from the panel etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | 12 | Each | 8,128 | ₹97,536 |
| - | SITC of UL 10th edition / EN54 / VDS certified Microprocessor based inteligent, Analogue addressable,modular, expandable networkable loop Fire Alarm Control Panel with each loop capacity of min 125 detectors per loop with total of 125 detectors & devices with Loop length up to 1 KM as per NFPA 72 approval. The Panel shall be able to give pin point location of addressable units via the address code for each unit. The Panel shall also be able to automatically switch off all control switches when-ever any Alarm is triggered. . The panel shall have 230 + 5 % volts power supply, Automatic battery charger 24V, sealed lead acid maintanence free battries sufficient for 24 hours normal working and then be capable of operating the system for 30 minutes during emergency condtion. Loop interface cards, communication module, LCD/LED unit to indicate Fire / Fault Signal of individual unit, inbuilt networking port(both RS485&Ethernet),Serial port for printer,two supervisory inputs,two position key switch and USB port for programming.including the cost of all accessories Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | - | - | - | - |
| - | 2 - Loop Panel | 1 | Each | 2,96,858 | ₹2,96,858 |
| - | Add Extra for per Loop expansion beyond Two Loop | 2 | per Loop | 67,462 | ₹1,34,924 |
| - | Supplying and drawing Fire Resistant flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | - | - | - | - |
| - | 2 x 1.5 Sq.mm Unarmoured With Outer Sheath in Red Color | 3,500 | Mtr | 94 | ₹3,29,000 |
| - | SITC of PA system Operator Console of following wattage to be installed with Conventional fire alarm system complete with following capacity , channel mixing amplifier , 1 no cardioids goose neck microphone , 1 no professional grade cassette deck/ CD Player , 16 zone floor selector console , equipment rack complete in all respects. PA system shall be coupled to the Fire Alarm System. Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | - | - | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.60 MB
Tendernotice_2.pdf
PDF • 4.19 MB
Tendernotice_3.pdf
PDF • 11.58 MB
Tendernotice_4.pdf
PDF • 0.19 MB
BOQ_1071328.xls
BOQ • 0.49 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .