| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.6 LAccepted-AOC | L1 | Accepted-AOC Accepting being lowest | |
| 2 | L2₹34.5 L+₹6.8 L (24.6%)Rejected-Finance | L2 | Rejected-Finance Rejected being other than lowest | |
| 3 | L3₹41.7 L+₹14.0 L (50.4%)Rejected-Finance PLOT NO 1134 1196 MORIVALI VILLAGE TAL AMBARNATH DIST THANE AMBERNATH 421505 | AMBERNATH | THANE | MAHARASHTRA | 421505 | L3 | Rejected-Finance Rejected being other than lowest |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
7 Feb 2023, 6:00 pmClosed
Maj Pramod Kumar Tripathi
Military Engineer Services, Garrison Engineer (South) Ahmednagar - 414002
Repair/Maint of DG Sets, EOT Crane, Repair/Maint and Cleaning of Swimming Pool, Filtration Plant, UG Sumps and OH Tanks, Servicing of Chloronome Plants and Allied E/M works at MIRC under GE (S) Ahmednagar
2022_MES_561239_2
8921/E8
Open Tender
Miscellaneous Works
Item Rate
270 days
Ahmednagar
Class D Cat a (ii)
8 documents required · 8 mandatory
₹500
Garrison Engineer (South) Ahmednagar
₹80,000
Yes
28 Feb 2023
10 Jan 2023
9 Feb 2023
10 Jan 2023
7 Feb 2023
24 Jan 2023
10 Jan 2023 - 17 Jan 2023
Amount
Inspection, maintenance and servicing of DG set, 320 KVA, Make : GREAVES POWER, Model no. GPWII-320E including alternator, electric panel board connection to DG Set for routine check ('A' check) of DG set for smooth functioning and carriying out maintenance as under :- Monthly Service (a) Checking engine oil level and topping up as and when required. NOTE : Oil shall be measured and paid separately (b) Checking and adjusting the belt for tension and replacemnt of belt. NOTE: Belt shall be measured and paid separately (c) Checking of oil bath air cleaner level (d) Checking of exhaust system for leakage (e) Draining of sediment from fuel filter and fuel tank (f) Cleaning of air cleaner element. Note : Replacement of Air Cleaner shall be measured and paid separately. (g) Checking engine alternator coupling, mounting bolts and alignment. (h) Tighting all nut, bolts, in alternator terminal block. (j) Checking of alternator carbon brush and connections in alternator (k) Checking and tighting of all connection in DC control wiring. (l) Checking of all radiator rubber hose and replacement if required. NOTE : Hose pipes shall be measured and paid separately (m) Checking and recording oil pressure, water and oil temperature (n) Checking anti vibration mounting and replacement if required. NOTE: Antivibration pad shall be measured and paid separately (o) Checking throttle linkage (p) Checking battery for cell test, electrolyte level, gravity and topping up to required level(q) Routine check / repair work of panel, switch, MCCB, main switch, all contactor, engine control unit.
All as per serial item No. 01 but for 125 KVA DG set, Make ; KIRLOSKAR, Model KG 125 WS
All as per serial item No. 01 but for 100 KVA DG set, Make ; KIRLOSKAR Model KG 125 WS/Model no. KG100W52
All as per serial item No. 01 but for 82.5 KVA DG set, Make ; CUMMINS M/C no 9920805-001
All as per serial item No. 01 but for 62.5 KVA DG set, Make ; CUMMINS, MODEL NO. 4BTAA3.3G11
All as per serial item No. 01 but for 50 KVA DG set, Make ; GREAVES COTTON, MODEL NO. 3G11TAG25
All as per serial item no. 01 but for 40 KVA DG set, Make ; KIRLOSKAR
All as per serial item no. 01 but for 40 KVA DG set, Make ; ASHOK LEYLAND MODEL NO. ALGPW04DMK1.E4
Material and labour required for `B' CHECK inspection, maintenance, servicing of DG set 320 KVA Make GREAVES POWER, Model no. GPWII-320E including items covered in `B' check of DG set for smooth functioning and carriying out maintenance complete all as per OEM instructions and as directed under :- (a) Repeat the activities of 'A' check (b) Replacing lubricant oil Note:- Lub Oil are Paid separately. (c) Replacing lubricant oil filter element with `O' ring (d) Replacing fuel filter element (e) Replacing Bypass Filter (f) Replacing Air Filter (g) Replacing Governer oil (h) Replacing coolant NOTES : i) `B' CHECK ONCE IN SIX MONTH OR 300-350 HRS RUNNING OF DG SET WHICHEVER IS EARLIER ii) `B' check kit, coolant, Lubricant Oil shall be measured and paid seperately under relevant item.
All as per serial item No. 09 but for 125 KVA DG set, Make ; KIRLOSKAR, Model KG 125 WS
All as per serial item No. 09 but for 100 KVA DG set, Make ; KIRLOSKAR Model KG 125 WS/Model no. KG100W52
All as per serial item No. 09 but for 82.5 KVA DG set, Make ; CUMMINS M/C no 9920805-001
All as per serial item No. 09 but for 62.5 KVA DG set, Make ; CUMMINS, MODEL NO. 4BTAA3.3G11
All as per serial item No. 09 but for 50 KVA DG set, Make ; GREAVES COTTON, MODEL NO. GPWII-PII-50
All as per serial item No. 09 but for 40 KVA DG set, Make ; KIRLOSKAR
All as per serial item No. 09 but for 40 KVA DG set, Make ; ASHOK LEYLAND MODEL NO. ALGPW04DMK1.E4
Supply only B' Check Kit for DG set 320 KVA, Make ; GREAVES POWER, Model no. GPWII-320E complete all as per OEM instructions and all as specified and as directed. Note : Quoted rate shall be included for oil filter (1.00 Ltr/0.5 ltr), Air Filter, Fuel/Diesel filter, by pass filter with element etc.
All as per serial item No. 17 but for 125 KVA DG set, Make ; KIRLOSKAR, Model KG 125 WS
All as per serial item No. 17 but for 100 KVA DG set, Make ; KIRLOSKAR Model KG 125 WS/Model no. KG100W52
All as per serial item No. 17 but for 82.5 KVA DG set, Make ; CUMMINS M/C no 9920805-001
All as per serial item No. 17 but for 62.5 KVA DG set, Make ; CUMMINS, MODEL NO. 4BTAA3.3G11
All as per serial item No. 17 but for 50 KVA DG set, Make ; GREAVES COTTON, MODEL NO. GPWII-PII-50
All as per serial item No. 17 but for 40 KVA DG set, Make ; KIRLOSKAR
All as per serial item No. 17 but for 40 KVA DG set, Make ; KIRLOSKAR, ASHOK LEYLAND MODEL NO. ALGPW04DMK1.E4
Disconnecting all the connections from alternator of 320/125/100 KVA DG set, removing the alternator from foundations , transporting to workshop, dismaintling completely including stator, roter, removing rotor and bearing, cleaning all the parts with thinner and varnishing completely with F class varnishing, applying expoxy coating, rewinding & reassembling, dynamically balancing the alternator transporting and fixing on frame and reallignment within tolerance limit , connecting the alternator with all connections and testing on load completely all as specified and as directed.
All as per serial item No. 25 but alternator of 82.5/62.5/50/40 KVA DG set.
M&L in repair/replacement, anti vibration mounting of DG Sets of capacity 40/62.5/100 KVA including connecting and testing all as specified and as directed.
M&L in repair/replacement, battery Lead with Brass Terminals of DG Sets of capacity 40/82.5/125 KVA all as specified and as directed.
M&L in repair/replacement, emergency shutdown switch with wiring of DG Set 40 KVA to 320 KVA all as specified and as directed.
M&L in repair/replacement, fan belt of DG set 320/125/100 KVA all as specified and as directed.
M&L in repair/replacement, fan belt of DG Set 82.5/62.5/50/40 KVA all as specified and as directed.
M&L in repair/replacement, oil seal of DG Set 40 KVA to 320 KVA all as specified and as directed.
M&L in repair/replacement, banjo bolt for pipe of DG Set 82.5/62.5/40 KVA all as specified and as directed.
M&L in repair/replacement, fuel level float ball of DG Set 320/125 KVA all as specified and as directed.
M&L in repair/replacement, radiator hose pipe set with clamps of DG Set 125/82.5/40 KVA all as specified and as directed.
M&L in repair/replacement, air filter hose pipe set with clamps of DG Set 320/100/62.5/50 KVA all as specified and as directed.
M&L in repair/replacement, dial type mechanical fuel level gauge meter of DG Set 125/82.5/40 KVA all as specified and as directed.
M&L in repair/replacement, dial type mechanical water Temp gauge meter of DG Set 125/100/62.5/40 KVA all as specified and as directed.
M&L in repair/replacement, dial type mechanical Volts gauge meter of DG Set 100/50/40 KVA all as specified and as directed.
M&L in repair/replacement, coolant drum assembly of DG Set 320/125/100/40 KVA all as specified and as directed.
M&L in repair/replacement, radiator fan metalic of DG Set 125/82.5/40 KVA all as specified and as directed.
M&L in repair/replacement, radiator fan drive pulley of DG Set 125/82.5/40 KVA all as specified and as directed.
M&L in repairs/replacement, hydraulic aluminium pipe for engine of DG Set 125/100/62.5/40 KVA all as specified and as directed.
M&L in repair/replacement engine generator controller Model no GCU DSE 6120 suitable for DG set 320 KVA AMF panel all as specified and as directed.
M&L in repair/replacement DIN Type Fuse Links Type HN Size 3, 500Amp, 415 V ~ 36.1 W all as specified and as directed. Make: L&T
M&L in repair/replacement starter solenoid valve of DG Set 100/62.5/50//40 KVA all as specified and as directed.
M&L in repair/replacement, starter / solenoid complete Assembly of DG Set 125/82.5/40 KVA all as specified and as directed.
M&L in repair/replacement, Left/Right hand door locks with catcher.of DG Set 40KVA to 320 KVA all as specified and as directed.
M&L in repair/replacement, engine generator controller Model no GCU 101 suitable for DG set 100 KVA AMF panel all as specified and as directed.
M&L in repair/replacement complete silencer Assembly with wrapping of rope of DG Set 82.5 KVA complete all as specified and directed
M&L in repair/replacement, wrapping of rope on exhaust silencer completely DG Set 125/100/50/40 KVA all as specified and as directed.
M&L for leakage rectification of radiator, cleaning, pressure testing etc for any make and capacity DG Set complete all as required and directed.
M&L in repair/replacement, battery charger 12 V DC SMPS 10 Amp for AMF panel all as specified and as directed.
M&L in repair/replacement, battery charger 24 V DC SMPS 20 Amp for AMF panel all as specified and as directed.
M&L in repair/replacement, engine generator controller as per existing model for AMF panel of DG Set 125/100/62.5/50/40 KVA all as specified and as directed.
S&F in repair/replacement, 3 phase, 12-24V DC, charging alternator as per existing capacity suitable for DG Set 100/125/320 KVA all as specified and as directed.
M&L for scraping, cleaning of old steel surface and painting with two coats of synthetic enamel paint over a coat of red oxide primer on DG set/EOT Crane of any Make & Capacity all as specified and as directed.
M&L for bearing grease HP/BP type servo Gem Natra-3/Lithon-3 all as specified and as directed.
Supply only high pressure grease gun complete with handle, high pressure hose 2.2 mtr and 4 Jaw coupler capacity 6 Kg all as specified and as directed.. Make: DURELO GBP-6
Supply only 11/32 mm high pressure grease gun Type GCL 45C complete all as specified and as directed. Make : TAPARIA
Supply only rotary barrel machine with dual direction operated ideal for lubrication or injected fuel in DG sets with suitable pipe 3 mtr fixed with clamp all as specified and as directed
S&F in repairs/replacement, car washing pump hose pipe as per standard shape and size 8.5 mm all as specified and as directed
Comprehensive repair and maintenance of class II indoor duty double girder EOT cranes each of capacity of 5 Ton,13 mtr Length installed in buildings located within in area of approx 10 Sq Km (MIC&S AREA) all as specified and as directed Note : Maintenance cost of each crane comprises of the following:- (i) Cost of tradesman and helper. (ii) Cost of Petty repairs and consumables such as cotton waste, 'K' Oil, Grease, Nuts, Bolts washer etc. (iii) Cost of labour for fixing all the components, which needs replacement. (iv) Cost of labour for weekly, monthly, quarterly and annual maintenance in addition to other instructions given in Maintenance and operational manual of the manufacturer.
All as per serial item No. 63 but capacity 5 Ton, 4 mtr Length
Taking LT shutdown, dismantle and remove the EOT crane set, 5 Ton capacity, from existing foundation / position, shifting to authorized workshop for the repair work, removing the burnt winding, cleaning rotor / stator slots, re-winding the motor with super enameled copper wire of the size equivalent to the original winding including insulated packing materials, varnishing, heating, drying, gear oil,power contactors,breaks,steel ropes and spare kits and the cost of motor parts/ equpments etc etc, replacing star bush coupling,replacing the bearings, reassembling and installing back at it's original position, aligning, testing and commissioning on full load for 8 hrs continuous running all as specified and as directed.
S&F in repair/replacement, power contactor, 30 Amp, 440 Volts with 110 volt coil for 5 Ton capacity EOT crane all as specified and as directed. Make: BCH/L&T/ Siemens/ Telemech/CG.
S&F in repair/replacement, spare kit unit suitable for power contactor, 30 Amp, 440 Volts with 110 volt coil for 5 Ton capacity EOT crane all as specified and as directed. Make: BCH/L&T/ Siemens/ Telemech/CG.
S&F in repair/replacement, hooter/siren suitable for EOT crane, 5 Ton capacity, flame proof of same size as exisiting with the crane all as specified and as directed.
S&F in repair/replacement, push button switches ON and Off inside the pendant/ panel board of 5 Ton EOT crane all as specified and as directed. Make:- L&T/Standard/Siemens / Legrand.
S&F in repair/replacement, bimetallic overload relays, suitable for power contactor, 30 Amp, 440 Volts with 110/230/440 volt coil all as specified and as directed.
S&F in repair/replacement, flexible copper cable PVC insulated multi stranded of size 4 core 6 sqmm 1100 Volts grade ,ISI Marked complete all as specified and as directed.
S&F in repair/replacement, flexible copper cable PVC insulated multi stranded of size 4 core 4 sqmm 1100 Volts grade, ISI Marked complete all as specified and as directed.
S&F in repair/replacement, wheel with pin shaft all as specified and as directed.
S&F in repair/replacement, ball bearing (Bearing No-6207) all as specified and as directed.
S&F in repair/replacement, MS gear for wheel all as specified and as directed.
S&F in repair/replacement, steel wire rope multi stranded 10mm dia all as specified and as directed. Make: Usha Martin
S&F in repair/replacement, PVC coated & PVC Insulated copper conductor multistranded of size 10 sqmm 4 core all as specified and as directed.
S&F in repair/replacement, HRC fuse link 32 amps as per site requirement all as specified and as directed.
S&F in repair/replacement gear box oil EP-230 suitable for EOT cranes all as specified and as directed.
M&L for brake oil all as specified and as directed.
S&F in repair/replacement, brake shoe of 150mm dia all as specified and as directed.
S&F in repair/replacement, magnetic coil all as specified and as directed.
S&F in repair/replacement, limit switch, 3 phase, 415 volt, 50 Hz as per site requirement all as specified and as directed.
S&F in repair/replacement, four pole contactor, AC three phase, 415volt Amps as per Site requirement all as specified and as directed.
S&F in repair/replacement, carbon brushes for clutch for micro movement of EOT Crane all as specified and as directed.
S&F in repair/replacement, current collector complete as per existing for EOT Crane of different capacity of EOT Crane all as specified and as directed.
Taking LT shutdown, remove YASKAWA V1000 Inverter Drive (VFD), 3 phase In 400 volt AC complete and repair same and refix as per existing for EOT Crane all as specified and directed. Note: Replaced parts cost will be measured in this job.
Supply only engine oil 15W40 of approved and standard in seal packed containers all as specified and as directed. Make : Servo/ BPL/IOC/ Castrol
Supply only Greaves Lub Oil CI4 approved and standard in seal packed containers all as specified and as directed. Make : Greaves
Topping up / replacement of Gear oil of Blower upto the required level in any type. complete all as specified and as directed. Note : Gear oil brought by the contractor at site must be in seal packed in drum having ISI mark as per IS-335 / 1983. Make : HP GEAR OIL EP90/ SHELL SPIRAX S2 G90/ CASTROL HYPOY 90EP
Supply only coolant of approved and standard in seal packed containers all as specified and as directed. Make:K cool Super plus 50-50 Premix, Castrol Radicool Premix, Greaves kool
Supply only battery water with electrolyte mix all as specified and as directed.
Taking LT Shutdown, remove LT Panel wiring and pull of DG set and locate upto 100 mtr distance and M&L cement concerete in foundation filling and mass, Type B2 1:2:4 (40 mm graded aggregate) and fixing of 100 KVA DG set after curing of foundation and connect all cable, Panel board etc as per existing all as per specified and directed by Engineer in charge
S&F in repair/replacement, of battery 12 V, Capacity XP1800 or180 AH, maintenance free battery, 12 Volt initially charged with suitable size of copper leads and brass terminals with 36 month warranty complete as directed by Engr-in-Charge. Make: Exide/ Amaron/ Luminous
All as per serial item No 94 but capacity XP800 or 80 Ah
Taking LT shutdown, complete checking of AMF panel, finding the fault, servicing complete including fixing in repair/replacement of unserviceable spares with necessary wiring and testing complete for manual & Auto operations all as directed. Note:- Items required for replacement will be measured & paid seperately as "Supply only" under respective item of BOQ
Supply only AMF panel timer and over voltage timing relay as per existing type, make and capacity all as specified and as directed.
Supply only AMF panel timer relay for circuit 230 V AC supply as per existing type, make and capacity all as specified and as directed.
Supply only AMF panel relay card 12 V DC supply for change over as per existing type, make and capacity all as specified and as directed.
Supply only AMF panel relay single with batch 8 pin 230 V AC supply as per existing type, make and capacity all as specified and as directed.
Supply only Start/ Stop switch with elements of AMF panel of any make and capacity all as specified and as directed.
Supply only solenoid switch for use of engine stop of AMF panel of any make and capacity all as specified and as directed.
Supply only Volt meter digital type of range 0-500 volts of panel all as specified and as directed.
Supply only Amp meter digital type of existing make,model and capacity of panel all as specified and as directed.
Supply only Indicator lamp 230 V AC Supply of panel all as specified and as directed.
Supply only AMF panel MCCB, 3 pole, 160 Amp, 16 KA all as specified and as directed.
Supply only MCCB, 3 pole,125 Amp,16 KA all as specified and as directed.
M&L in repairs/replacement, broken canopy door hinges and Glasses of any capacity DG set of any capacity and make. Setting of conopy door, properly locking arrengement, welding Brazing of broken parts/body etc complete all as directed by Engr-in Charge
M&L in repairs/replacement, for earthing complete with GI earth plate electrode of size 60cm x 60cm x 6.0m m buried directly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level sorrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt filling in alternate layers etc and connected to and including galvanized earth strip 25mmx4mm upto 7.5 m by means of bolts, nuts, check nuts and washers made of galvanised iron and protected by light grade 32mm dia GI pipe connected to main control board and GI pipe medium grade 20mm bore for watering and including funnel, wire mesh, charcoal,salt etc RCC pit cover flush to earth pit 50mm thick reinforced with 8mm TMT bar 100mmC/C and PCC chamber pit with PCC (1:3:6) type C1 (using 20mm graded aggregate) including excavation and earthwork disposal of surplus soil to distance not exceeding 50 metre) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 complete all as specified and as directed.
M&L in repair/replacement, battery stand frame of existing size with height of 1 feet made of 50mm x 50mm x 6mm mild steel angle iron and support with flat iron of size 40mm x 6mm, duly painted with two coats of synthetic enamel paint over one coat of red oxide primer, 20 mm wooden plank on top to place 01 Nos battery complete all as specified and as directed.
S&F in repair/replacement Power Contactors 500 Amp, Type MCX 44, 4 Pole all as specified and directed . Make : L&T
S&F in repair/replacement, power contactors 160 Amp, Type MCX 32, 4 Pole all as specified and directed . Make : L&T
S&F in repair/replacement, front mounting contactors 10 Amp, Type MNX-A1, 4 Pole all as specified and directed . Make : L&T
S&F in repair/replacement, side mounting contactors MNX-A6 or as per existing Left/right side suitable capcacity single Pole all as specified and directed . Make : L&T
S&F in repair/replacement contactors MNX-A1,10 A or as per existing suitable capcacity four Pole all as specified and directed . Make : L&T
S&F in repair/replacement, contactors MNX-A2,10 A or as per existing suitable capcacity two Pole all as specified and directed . Make : L&T
S&F in repair/replacement, thermal overload relay 4P Model LRE 07 or as per existing suitable capcacity four Pole all as specified and directed . Make : L&T, Scnieder
S&F in repair/replacement, air termination, single pointed aluminium rod 12mm dia and 300mm long all as specified and directed.
S&F in repair/replacement, test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw all as specified and directed.
S&F in repair/replacement, aluminium strip 25 mm x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground all as specified and directed.
S&F in repairs/replacement, 415 volt, 4P, 400 Amp, Change Over in sheet steel enclosur all as specified and as directed. Make. HPL/ L&T/ Havells
S&F in repairs/replacement, 415 volt, 4P, 200 Amp, Change Over in sheet steel enclosur all as specified and as directed. Make. HPL/ L&T/ Havells
S&F in repairs/replacement, 415 volt, 4P, 100 Amp, Change Over in sheet steel enclosur all as specified and as directed. Make. HPL/ L&T/ Havells
Dismantling old LT feeder piller on existing foundation and supply installing commissioning & testing in replacement LT feeder piller panel board factory made, out door, cubical type, vermin proof, dust proof, water proof made out of 3.15 mm thick CRCA sheetand angle iron frame of size 50x50x6 mm inside depth not less than 50 cm and size suitable to accomodate the following accessories with insulated TPN Copper busbar of rating not less than 1.5 times the rated capacity of the incomer MCCB. both side openable (front & back) with locking arrangement duly painted with coat of synthetic enamel paint over a coat of red oxide primer both internally and externally and connecting with cable with lugs including internal wiring with copper cable of suitable size using lugs compressing the following accessories all as directed. (Notes : The rate quoted shall include for earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board ) and Copper bus bar 300 Amps duly colour sleeved mounted on epoxy insulators-01 set.Note:(i)Panel board shall be approved by CPRI and certificate to be produced and to be submitted in the office.(ii) Panel Board should be located at Shrinagar Pump House. Incoming :- (a) MCCB 200 amps, 4 pole, 36 KA with thermal magnetic release - 01 No (b) Manual Change over Switch 200 Amps 4 pole extended type - 01 No (c) Multifunction Digital square type intelligent panel meter to measure voltage, current, frequency & Power factor - 01 No Outgoing :- (a) MCCB TPN 4 pole C-63 amps, 10 KA - 02 Nos (b) Fully automatic Star Delta Starter suitable starter for 25/30 HP pump set (MN 25 FASD) - 02 Nos
Dewatering, cleaning of OH reservoirs' 200000 Gallons (RCC), 60' staging, inside MIC&S complex near Gate No.3 with high pressure jet to remove all mosses, algae, dirt, deposits and other sediments, scrubbing of internal surface with steel wire brush and removal of dirty water with sludge machines / industrial vacuum cleaners and disposal of the same to a safe distance including , Sterilizing the complete internal surface of the tank by using ISI mark Gd I bleaching powder / Liquid Chlorine, wash with fresh water, drying up, applying one coat of anti-fungal Cement Paint on internal surface incl marking / writing the words on external wall at visible place ''Military Engineer Services, Tank Capacity & Date of Cleaning'' using synthetic enamel paint in white colour over black background and letters of height 50 mm height and 40 mm width complete all as specified & directed.
All as per serial item No 126 but for 100000 Gallons (RCC), 60' staging, inside MIC&S at Golf Ground near JCO's MD Accns
All as per serial item No 126 but for 27500 Gallons (RCC), 60' staging, inside MIC&S at MAP near OR's MD Accns
All as per serial item No 126 but for 50000 Gallons (RCC), 60' staging, inside PH complex near Gate No. 3 at MIC&S
All as per serial item No 126 but for 22000 Gallons (RCC), 60' staging, inside MAP PH II complex at MIC&S
All as per serial item No 126 but for 20000 Gallons (RCC), 45' staging, near Harpal Stadium at MIC&S
All as per serial item No 126 but for semi underground sump 300000 gallons (RCC), Cylindrical Curved Roof, inside PH complex near Gate No. 3 at MIC&S
All as per serial item No 126 but for semi underground sump 100000 gallons (RCC), Cuboids, inside PH complex near Gate No. 3 at MIC&S
All as per serial item No 126 but for semi underground sump 20000 Gallons (RCC), Cuboids, inside PH complex near Gate No. 3 at MIC&S
All as per serial item No 126 but for semi underground sump 27500 Gallons (RCC), Cuboids, inside PH complex near Gate No. 3 at MIC&S
Taking LT shutdown, dismantle and remove the submersible suction sweeper 2HP, 415 V, 2750RPM, Make Modi, Model B-200 Pump set from existing position, Shifting to authorized workshop for the repair work, removing the burnt winding, cleaning rotor / stator slots, re-winding the motor with super enameled copper wire of the size equivalent to the original winding including insulated packing materials, Varnishing, Heating, Drying etc, replacing coupling,replacing the bearings, reassembling and installing back at it's original position. Testing and commissioning on full load for 8 hrs continuous running all as specified & as directed.
S&F in repair/replacement, flexible wire with multistranded copper conductor FRLS, PVC insulated and overall PVC sheathed,single core, 1100 Volts grade, 6.0 Sqmm all as specified & as directed.
S&F in repair/replacement, copper ring lugs, 6.0 Sqmm all as specified & as directed.
S&F in repair/replacement, copper pin lugs, 6.0 Sqmm all as specified & as directed.
Supply only submersible flexible cable with multistranded copper conductor, PVC insulated and overall PVC sheathed, 3 core, 1100 Volts grade, 6.0 Sqmm all as specified & as directed.
Supply only nylon braided UPVC flexible hose pipe, heavy grade, 50mm OD with two nose clips all as specified & as directed.
Supply only nylon braided UPVC flexible hose pipe, heavy grade, 40mm OD with two nose clips all as specified & as directed.
Supply only PVC cylindrical pool float ball, high density, double hook, suitable for sustaining hose & cable above water during suction sweeping all as specified & as directed.
Supply only nylon rope 12 mm dia, best quality for operation of suction sweeper all as specified & as directed.
Supply only nylon brushes (700 x 100mm) as per and suitable for submersible suction sweeper , 2HP all as specified & as directed. Make Modi, Model B-200, best quality.
Supply only rubber matting conforming to IS, 1100 Volts grade of size 2.0m x 1.0m and 6 mm thick , ISI marked all as specified & as directed.
S&F in repair/replacement, star coupling, heavy duty, Styrene Butadiene Rubber suitable for 30 HP pump or motor all as specified & as directed.
Taking LT shutdown, dismantle and remove the 30 HP electric motor of the mono block / coupled / Mud pump set from existing foundation / position, shifting to authorized workshop for the repair work, removing the burnt winding, cleaning rotor / stator slots, re-winding the motor with super enameled copper wire of the size equivalent to the original winding including insulated packing materials, varnishing, heating, drying etc, replacing star bush coupling,replacing the bearings, reassembling and installing back at it's original position, aligning, testing and commissioning on full load for 8 hrs continuous running all as specified and as directed. Note :- This job Include drain out sewage water from sump through honey sucking machine for Mud Pump only
All as per serial item No.148 but 10 HP
All as per serial item No.148 but 05 HP
All as per serial item No.148 but 03 HP
All as per serial item No.148 but 1 HP Car Washing pump
S&F in repair/replacement, CI impeller for 30 HP pump all as specified and as directed
S&F in repair/replacement, bearing 6309 for 30 HP pump all as specified and as directed
S&F in repair/replacement, bearing end plate for 30 HP pump all as specified and as directed
S&F in repair/replacement, MS shaft for 30 HP pump all as specified and as directed
S&F in repair/replacement, MS coupling for 30 HP pump all as specified and as directed
S&F in repair/replacement, seal for 30 HP pump all as specified and as directed
S&F in repair/replacement, motor fan for 30 HP pump all as specified and as directed
S&F in repair/replacement, bush for 30 HP pump all as specified and as directed
S&F in repair/replacement, rotor for 10 HP pump all as specified and as directed
S&F in repair/replacement, bearing for 10 HP pump all as specified and as directed
S&F in repair/replacement, bearing end plate for 10 HP pump all as specified and as directed
S&F in repair/replacement, MS shaft for 10 HP pump all as specified and as directed
S&F in repair/replacement, stator for 10 HP pump all as specified and as directed
S&F in repair/replacement, seal for 10 HP pump all as specified and as directed
S&F in repair/replacement, motor fan for 10 HP pump all as specified and as directed
S&F in repair/replacement, bush for 10 HP pump all as specified and as directed
S&F in repair/replacement, rotor for 05 HP pump all as specified and as directed
S&F in repair/replacement, bearing for 05 HP pump all as specified and as directed
S&F in repair/replacement, bearing end plate for 05 HP pump all as specified and as directed
S&F in repair/replacement, MS shaft for 05 HP pump all as specified and as directed
S&F in repair/replacement, stator for 05 HP pump all as specified and as directed
S&F in repair/replacement, seal for 05 HP pump all as specified and as directed
S&F in repair/replacement, motor fan for 05 HP pump all as specified and as directed
S&F in repair/replacement, bush for 05 HP pump all as specified and as directed
S&F in repair/replacement, rotor for 03 HP pump all as specified and as directed
S&F in repair/replacement, bearing for 03 HP pump all as specified and as directed
S&F in repair/replacement, bearing end plate for 03 HP pump all as specified and as directed
S&F in repair/replacement, MS shaft for 03 HP pump all as specified and as directed
S&F in repair/replacement, stator for 03 HP pump all as specified and as directed
S&F in repair/replacement, seal for 03 HP pump all as specified and as directed
S&F in repair/replacement, motor fan for 03 HP pump all as specified and as directed
S&F in repair/replacement, bush for 03 HP pump all as specified and as directed
S&F in repair/replacement, CI impeller for 01 HP Car Washing pump all as specified and as directed
S&F in repair/replacement, bearing for 01 HP Car Washing pump all as specified and as directed
S&F in repair/replacement, bearing end plate for 01 HP Car Washing pump all as specified and as directed
S&F in repair/replacement, MS shaft for 01 HP Car Washing pump all as specified and as directed
S&F in repair/replacement, V belt for 01 HP Car Washing pump all as specified and as directed
S&F in repair/replacement, seal for 01 HP Car Washing pump all as specified and as directed
S&F in repair/replacement, motor fan for 01 HP Car Washing pump all as specified and as directed
S&F in repair/replacement, bush for 01 HP Car Washing pump all as specified and as directed
Taking LT shutdown, dismantle and remove the 5.5 kW/7.5 HP motor blower set Max flow capacity 210 m³/hr, from existing foundation / position, shifting to authorized workshop for the repair work, removing the burnt winding, cleaning rotor / stator slots, re-winding the motor/blower with super enameled copper wire of the size equivalent to the original winding including insulated packing materials, varnishing, heating, drying etc, replacing old gear oil, replacing the bearings, Air filters etc. reassembling and installing back at it's original position, aligning, testing and commissioning on full load for 8 hrs continuous running all as specified and as directed.
All as per serial item No 193 but for 5 HP Blower Set, Max flow capacity 185 m³/hr
All as per serial item No 193 but for 3 HP Blower Set, Max flow capacity 150 m³/hr
Taking LT shutdown, dismantle and remove the 5 HP Submersible Pump set, from existing foundation / position, shifting to authorized workshop for the repair work, removing the burnt winding, cleaning rotor / stator slots, re-winding the motor/blower with super enameled copper wire of the size equivalent to the original winding including insulated packing materials, varnishing, heating, drying etc, replacing old gear oil, replacing the bearings etc. reassembling and installing back at it's original position, aligning, testing and commissioning on full load for 8 hrs continuous running all as specified and as directed.
All as per serial item No 196 but for Sludge pump set 1 HP capacity.
All as per serial item No 196 but for feed pump set 1 HP capacity.
M&L for greasing and Oiling for any type and Capacity Pump/Motor/Blower and Machine etc for smooth running and functioning.all as specified and directed
S&F in repair/replacement, V Belt for blower set 7.5/5/3 HP pump or motor, all as specified & as directed.
Taking LT shutdown, dismantle and remove the screw press sludge machine set from existing foundation / position, shifting to authorized workshop for the repair work, removing the plates, clean and fix with new if any plate and accessories break or burnt, complete greasing, oiling for smooth functioning. After complete the repair work, refix and re-position the machine with all connection of pipes and accessories complete all as specified and as directed.
Cleaning of Areation Tank, Tube Settling tank, Chlorination tank and Cleaning of lamina box plates . Remove of all sludges and mud completely from given tanks using honey sucking machine for 165 KLD STP all as specified and as directed.
All as per serial item No 202 but for 15 KLD STP
Supply only bio-culture suitable for sewage treatment plant and develop bio-culture till making of sludge in sludge bag feed pump all as specified and as directed.
Take Water Sample (Raw Water And Treated Water) form existing STP 160 KLD, sample will be submit in govt lab " Maharashtra State Public Health Services. State Public Health Laboratory, Pune " & Produce test report every month as per given below parameter. INLET PARAMETER (a) pH : 7.5 (b) BOD : 250 mg/l (c) COD : 450 mg/l (d) Suspended Solids : 200 mg/l (e) Oil & Grease : 20 mg/l OUTLET PARAMETER (a) pH : 6.0-9.0 (b) 3 days BOD @ 27deg C : <100 mg/l (c) COD : <250 mg/l (d) Suspended Solids : <50 mg/l (e) Oil & Grease : <10 mg/l (f) Res Chlorine : > 1.0 mg/l (g) E-Coli : <1000 counts/100 ml
All as per serial item No 205 for 15 KLD STP
Supply only Moving Bed Biofilm Reactor (MBBR) to cover the higher surface area size 22 mm X 13 mm thickness 1.5mm, ranging from 200-500 m2/m3 all as specified and as directed.
Supply only sludge bags, capacity 12.5 kg/batch X 2 batches per day for collect sludge/cakes from /screw press sludge machine all as specified and as directed. Make: Auric/Sabari/Serve India
S&F in repair/replacement, 3 phase DOL starter and all components suitable for 5 HP submersible pump set all as specified and as directed. Make Havells, CG, L&T.
S&F in repair/replacement, 3 phase DOL starter and all components suitable for 1.5/3 HP submersible pump set all as specified and as directed. Make Havells, CG, L&T.
S&F in repair/replacement, Single phase/Three phase preventer suitable for Fully automatic Star / Delta starter or Direct - on - Line starter all as specified and as directed. Make : Schneider / Minilec / L&T
S&F in repair/replacement, over load relay for 3/5/10/25/30 HP motor as per existing capacity all as per specified and as directed.
S&F in repair/replacement, fully automatic Star / Delta starter in sheet metal enclosure with Single Phase/Three phase Protection feature (Motor Rating AC - 3 Duty, 415V, 50Hz, 3Ph) suitable for 30 HP pumpset having relay range 20 - 33 Amps all as specified and as directed.. Make: Schneider / L&T
All as per serial Item No 213 but Direct - on - Line starter suitable for 10HP motor, having relay range 9 - 15 Amps.
Drying up the Internal/External surface of the filter tank, preparing surface using suitable sand paper, remove the corrosion completely, filling the cavities or holes by welding /soldering including all extra material/mild steel plate used for welding purpose, smoothening the surface, applying two coats of finishing black bituminous paint over a coat of anti-corrosive metal primer and pressure testing after all welding/soldering process check completely after full on load and filling completely with water and material complete all as specified and as directed.
Labour only for Emptying the swimming pool (L - 50M, W - 21M, Shallow end D - 1M and Deep end D - 1.8m), Diving pool (L - 50M, W - 21M, D - 4.8M), including Scum channel, Connecting channel, Supply duct etc. Take out the grills of man holes, Remove all mosses, algae, dirt, deposits, sediments and sludge. Scrub and clean wall / floor / scum channel tiles with nylon wire brush, remove dirty water with sludge machines / industrial vacuum cleaners and disposal of the same to a safe distance. Wash entire swimming / Diving pool, including Scum channel, Connecting channel, Supply duct etc with lime soda ash solution / hydrochloride acid. Sterilize the complete internal surface using Liquid Chlorine. Wash with fresh water, drying up, complete all as specified and as directed.
Labour only for Emptying the balancing tank and Water Cascade, Removing all mosses, algae, dirt, deposits, sediments and sludge, scrubbing of internal surface with steel wire brush and removal of dirty water with sludge machines / industrial vacuum cleaners and disposal of the same to a safe distance including Sterilizing the complete internal surface of the tank / cascade by using ISI mark Gd I bleaching powder / Liquid Chlorine, wash with fresh water, drying up, applying one coat of anti-fungal paint on internal surface and applying one coat of exterior weather coat cement paint on external surface complete all as specified and as directed.
Labour only for filling the swimming pool / Diving pool / balancing tank with fresh water, operating the filter media pump set, carrying out back washing of filter media, aerating by operating air blower, Suction sweeping of swimming pool at various stages of filling with water after adding chemicals, carryout the filtration of pool water for 8Hrs continuously, carryout PH test and ppm test of pool water complete all as specified and as directed.
Supply only chlorine gas in 100/50 kg cylinder including disconnection and reconnection at site as directed by Engineer-in-charge. Note:- (i) All safety precations to be taken to avoid gass leakage (ii) Rate quoted deemed to include rent for cylinder
Supply only Soda Ash all as specified and directed.
Supply only Non Ferric Alum all as specified and directed.
Supply only Copper Sulphate all as specified and directed.
Supply only Cationic polyelectrolyte liquid 12% chlorine all as specified and directed. Make : OCEAN CHEMICALS pune
Supply only Sodium hypochloride liquid 12% chlorine all as specified and directed. Make : OCEAN CHEMICALS pune
Supply only Roundup Chemical for in Liquid form for cleaning purpose installations all as specified and directed.
Repairs and servicing of chloronome plant at gaseas type 200gms/hour capacity located at Swimming Pool at MIC&S. all as Specified & directed by the Engineer-in-Charge. Note : (i) The servicing is to be carried out monthly. (ii) The rates for the following items is inclusive of attending immidiately the chloronome plants as & when required at site to stop leakages and to be repaired immediately Note : Servicing to be carried out through authorised agency/representative.
S&F Moisture trap/ Glass NRV as per Part No SSAPS-1004 all as specified and directed.
S&F Cylinder Key Part No SPAS 1025 all as specified and directed.
S&F Chlorine flow meter up to 1 Kg / hr SSAPS-1033 all as specified and directed.
S&F Chlorine Mixing chamber Part No SSPAS 1010 all as specified and directed.
S&F Safety Gauge as per existing size and all as specified and as directed.
S&F Primary filter as existing at site and all as specified and as directed.
S&F Secondary filter as existing at site and all as specified and as directed.
S&F Safety loop 'U' bend as existing at site and all as specified and as directed.
S&F PP diaphragm valve for water inlet and outlet of dia 15mm all as specified and as directed.
S&F Heavy duty UPVC pipe for chlorine solution outlet of dia 20mm all as specified and directed.
S&F Teflon pipe for chlorine solution as per existing size all as specified and directed.
S&F Solutionizer as per existing size all as specified and directed. all as specified and directed.
S&F Water bend as per existing size all as specified and directed. all as specified and directed.
S&F Gas Bend as per existing size all as specified and directed. all as specified and directed.
Supply only ammonia solution for checking of chlorine gas leakages and plants in 500ml bottle. all as specified and directed. Make : NICE/Glaxo.
Supply only water testing kit including litmas papers and chemical. all as specified and directed.
Dismantled old LT feeder piller on existing foundation and Supply installing commissioning & testing in replacement LT feeder piller panel board factory made, out door, cubical type, vermin proof, dust proof, water proof made out of 3.15 mm thick CRCA sheetand angle iron frame of size 50x50x6 mm inside depth not less than 50 cm and size suitable to accomodate the following accessories with insulated TPN Copper busbar of rating not less than 1.5 times the rated capacity of the incomer MCCB. both side openable (front & back) with locking arrangement duly painted with coat of synthetic enamel paint over a coat of red oxide primer both internally and externally and connecting with cable with lugs including internal wiring with copper cable of suitable size using lugs compressing the following accessories all as directed. (Notes : The rate quoted shall include for earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board ) and Copper bus bar 300 Amps duly colour sleeved mounted on epoxy insulators-01 set. Note:(i)Panel board shall be approved by CPRI and certificate to be produced and to be submitted in the office.(ii) Panel Board should be fixed at MAGAZINE Plant. incoming :- (a) MCCB 3 P, 415 Volt 160 Amps, 36 KA, 50 Hz with fixed thermal and magnetic setting -01 No Outgoing :- (a) MCCB 3 P, 415 Volt 100 Amps, 16 KA, 50 Hz with fixed thermal and magnetic setting -03 Nos (b) TPN 4P, 415 Volt C-16 Amp, 10 KA, 50 Hz for Blower -01 No (c) TPN 4P, 415 Volt B-63 Amp, 10 KA, 50 Hz for Heater -01 No (d) Direct Online DOL Starter for 1-1.5 Hp Three Phase Motor -01 No (e) Multifunction Digital square type intelligent panel meter to measure voltage, current, frequency & Power factor - 01 No
S&F in repair/replacement, doser capacity 0 to 25 LPH, 0.5 HP Diaphragm/Metering type Suitable for 160 KLD Sewage Treatment Plant all as specified and directed. Make : Ion Exchange
M&L for GI tubing medium grade 15 mm bore laid in trenches / floors or fixed to wall in any length with screwed and socket joints together with all galvanised GI fitting such as sockets, bends, elbows, tees, reducers, unions, jointing materials etc and pressure testing, Washing out complete including dismantling, taking out old corroded pipe complete all as specified and directed.
All as per serial item No. 245 but 20 mm bore pipe.
All as per serial item No. 245 but 25 mm bore pipe.
All as per serial item No. 245 but 40 mm bore pipe.
All as per serial item No. 245 but 50 mm bore pipe.
All as per serial item No. 245 but 80 mm bore pipe.
All as per serial item No. 245 but 100 mm bore pipe.
M&L for UPVC PIPES 100 mm bore (Pressure rating 10 kgf/cm²) laid in trenches / floors or fixed to wall in any length with screwed and socket joints together with all UPVC fitting such as sockets, bends, elbows, tees, reducers, unions, jointing materials etc and pressure testing, Washing out complete including dismantling, taking out old pipe complete all as specified and directed.
M&L for Gun metal or Bronze globe / ball valve 15 mm bore, ISI Marked, screwed both ends suitable for GI tubing with side way operating GI lever handle including taking down old unserviceable valve of any type / make complete all as specified and as directed.
All as per serial item No. 253 but 20 mm bore
All as per serial item No. 253 but 25 mm bore
All as per serial item No. 253 but 40 mm bore
All as per serial item No. 253 but 50 mm bore
Supply, laying and testing cable XLPE of size 2 core 6 Sqmm, insulated screened pvc bedded, galvanised steel strip or wire armored, electric power cables (heavy duty) with stranded aluminium conductor 1100 volts grade all as specified and as directed.
Excavation in trenches not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr in depth for laying pipe line, cables or for shafts, sluice valve, cesspits etc not exc 10 Sqm on plan and n exc 1.5m in depth, and getting out in soft & loose soil complete all as specified and as directed.
Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft / loose soil including making good of disturbed surfaces complete all as specified and as directed.
Removing excavated soil to distance not exceeding 50 Mtrs and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and as directed.
M&L for cutting the existing bituminous road / PCC Hard Standing upto 75cm in depth, 60cm in width and getting out excavated materials making good the damaged portion after laying of pipes by returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick and PCC 1:2:4 type B1 using 20mm graded stone aggregate upto 30cm depth from top of the road all as specified and as directed.
M&L for construction of valve pit/chamber of Internal dimensions 900 mm x 900 mm x 900 mm, using PCC 1:4:8, type D-2, using 40mm graded stone aggregates for foundation, 23 cm thick, brick wall built in cement mortar (1:4) ,15 mm thick rendering all around the brick work in cement mortar (1:6), 75 mm thick PCC (1:2:4) type B-1 using 20mm graded stone aggregates in coping including necessary form work, 3coats of white wash on rendered surfaces and on coping, 2 mm thick mild steel top sheet cover with frame made out of 40x40x6 mm angle iron, locking arrangement, including painting of steel surface with two coats of synthetic enamel paint over a coat of red oxide primer including demolition of existing valve chamber and clearing the debris complete all as specified and as directed.
Cleaning of area around installations including cutting and dressing of the existing vegitation (trees/bushes/plants/grass,etc) of all type and all sizes wherever required for the clear approch to the installation and the work alignment of area completeall as specified and as directed.
S&F in repair/replacement, Aviation obstruction LED light luminarie, 30 Watt , Double Dome, weather proof, IP 65, die-cast aluminium toughened clear, transparent, borosilicate hard glass endless neoprent gasket incuding cable enty ET 19 mm at base including all fittings, 6x2 sqmm XLPE cable, MCB box with 10 Amp MCB and accessories as required complete all as specified and as directed. Make : Bajaj/Havells/Philips/Crompton. Note: 6x2 sqmm XLPE cable will be measured and paid saperately.
Taking out old unserviceable MCCB TP/TPN/ four pole from existing LT panel board and S&F in repair/replacement Same of 63 amps with breaking capacity 16 KA at 415 volt 50 Hz AC supply, ( Ics = 100% Icu), including necessary modification in panel board if required to fix the MCCB complete with replacement of incoming and out going cable connection with lugs, aluminium conductor cable of proper size, nuts bolts all as directed.replacement of burnt lugs and wire/cable pieces etc as required at site all as specified and as directed.
All as per serial item No. 266 but 4 pole, 100 amps capacity, 25 KA.
All as per serial item No. 266 but 3 pole, 125 amps capacity, 36 KA.
All as per serial item No. 266 but 4 pole, 160 amps capacity, 36 KA.
All as per serial item No. 266 but 4 pole, 200 amps capacity, 36 KA.
All as per serial item No. 266 but 4 pole, 250 amps capacity, 36 KA.
S&F in repair/replacement, Illuminated Push Button assembly with Wire harness (Red Green colour) of existing size and shape complete all as specified and as directed. Make : L&T/ Havells/AE
Repair / Servicing to voltage stabilizers 3 phase 4 wire system, 150 KVA at site by opening carefully from top, taking out coils / connections, cleanig coils, checking defective joints / soldering / jointing and Repalce all defective parts as per existing, Copper rewinding as per existing, re-assembling, testing on full load and making fully servicable including spray painting with super enamelled paint of approved colour all as specified and as directed.
All as per serial item No. 275 but 30 KVA.
Topping up / replacement of insulating oil of stabilizer chamber with new insulating / transformer oil upto the required level in any type and capacity of the voltage stabilizer complete all as specified and as directed. Note : Insulating / transforemer oil brought by the contractor at site must be in seal packed in drum having ISI mark as per IS-335 / 1983. Make : Power Oil/ Castrol
S&F in repair/replacement, pressure gauge, stem with dual dial type, 0 - 7Kg / Cm² and 0 - 100 Lb / Sq inch all as specified and as directed.
Preparation of old steel surfaces of Installations sign board at MIC&S pump house, removing the corosion and old paint completely using suitable sand paper, filling the cavities or holes by welding / soldering as required, smoothening the surface and applying two coats of Blue synthetic enamel paint over a coat of anti-corrosive metal primer and write down all details/nomenclature as per existing shape and size with white radium complete all as specified and as directed.
Dismantling and taking down old sign board from existing pillars at 15 feet (Approx) height and M&L in repair/replacement new Electric Sign board of Mild Steel Sheet, Fabric material as per existing shape , size 23 feet x 3 feet, with and including letters " MILITRY ENGINEER SERVICES, GARRISON ENGINEER (SOUTH) AHMEDNAGAR GATE NO. 03 PUMP HOUSE AT MIC&S'' and MES Logo, fixed on existing pillars and connect with electric supply, suitable panel wiring complete all as specified and as directed.
Dismantling existing MS sign board (Approx size 5 feet x 4 feet) alongwith mild steel sections framework and demolition of foundation concrete complete all as specified and directed
Excavating in post holes in soft/loose soil (or similar holes) each n exc 0.5 cum, getting out, returning,filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm complete all as specified and directed.
M&L for PCC 1:2:4 type B-2 (using 40 mm graded stone aggregates) as in foundations,filling and mass concrete etc including necessary form work and finishing exposed surface of concrete even and smooth without using extra cement etc complete all as specified & directed.
M&L for mild steel framed work of channels, angles, flats, square/round bars etc as in sign boards, hordings, and similar work including cutting, bending, welding as necessary, gusset plates, etc conforming to Fe.290.Gde-E-165 complete all as specified & directed.
M&L for mild steel, plain, black sheet 1.60 mm thick, in covering to mild steel framework of sign board, hordings etc cut to size edges beaded if directed, holes punched if required; including round headed screws, clout nails or welded to frame complete all as specified & directed.
M&L for preparation of new surfaces of mild steel sign board and applying two coats of blue colour synthetic enamel paint over a coat of anti-corrosive metal primer/red oxide complete all as specified and as directed.
M&L for writing letters or figures (Block Roman, Italic or Indian) n exc. 30 cm high using synthetic enamel paint of approved colour and shade complete all as specified and as directed.
M&L for writing Stops, Commas, short lines, dashes, hyphens, brackets, etc.using synthetic enamel paint of approved colour and shade complete all as specified and as directed.
M&L for "MES Logo" of maximum area 625 cm² using radium sticker of approved colour and shade complete all as specified and as directed.
M&L in repair/replacement for earthing complete with galvanized steel earth plate electrode 60 cm X 60 cm X 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level connecting to the GI strip 32 x 6mm, by means nut bolt, nuts, check nuts and washer of the GI Earth wire protected by provision of GI light grade pipe 15 mm, GI light grade 20 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, taste point made out of phosphorus bronze with fixing arrangement, funnel, wire mesh and RCC pit cover flush to earth pit 50mm thick reinforced with 8mm TMT bar 100mmC/C and PCC chamber pit with PCC (1:3:6) type C1 (using 20mm graded aggregate) including excavation and earthwork in hard soil, disposal of surplus soil to distance not exceeding 50 metre) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 complete all as specified and as directed.
BHAVIN INFRA
shakti engineering and electrical works
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .