| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹40.4 CrAdmitted-Finance | ₹40.4 Cr | L1 | Admitted-Finance |
| Sl No | Description | Qty | Unit | KANOHAR ELECTRICALS LIMITED L1 |
|---|---|---|---|---|
| 1.00 | Erection of structures including tightening and punching of nuts, bolts. | 9.04 | MT | 5,000 ₹45,200 |
| 2.00Stringing of overhead gantries, vertical droppers with ACSR conductor including fixing of insulator string, spacers, clamps etc. | ||||
| 2.01 | Single Zebra | 1,000 | metre | 125 ₹1.3 L |
| 2.02 | Stringing of overhead shield wire with 7/3.66 mm standard galvanized steel complete with fixing of strain clamps at the structures. | 200 | metre | 50 ₹10,000 |
| 3.00 | Suspension/T Clamps & Power/Terminal Connectors [not covered in respective equipments/ switchgear] etc. suitable for Single ASCR Panther [ for incterconnection from Line gantry, CVT, LA, Line Trap up to isolator incoming end] [Specify the Break Up with Quantity and Unit Prices for various items considered for this component of Price Scehdule] | 1 | Lot | 1,00,000 ₹1 L |
| 4.00 | Add: Any other item bidder may require to complete the Switchyard Erection & Support Installations as per specification requirements | 1 | Lot | - |
| 5.00Installation of transformers | ||||
| 5.01 | 50MVA 132/33KV Transformer (with Oil and associated equipments) Complete assembly and erection of power transformer with connections etc including installation of marshalling boxes, control cabinets, air sealing radiators, cooling fans, all accessories etc for transformer including their preliminary checks. Unloading /handling of transformer accessories, handling and filling of transformer oil along with associated equipments. | 2 | Nos | 6,10,000 ₹12.2 L |
| 5.02 | STATION TRANSFORMERShifting of 33/0.4 KV Station transformer up to Xmer Foundation and placing on it & connection to bushing & earth connection along-with installation of associated Isolator, DO set, LA & LTDB and associated work etc. | 1 | Nos | 61,000 ₹61,000 |
| 6.00132 kV Indoor GIS Switchgear Equipments | ||||
Tender Value
₹34.1 Cr
Closing Date
7 Mar 2022, 4:00 pmClosed
CE (Procurement)
Block No.3, Shakti Bhawan, Rampur, Jabalpur-482008
Design, Supply of all materials and complete construction of one Nos. 132/33 KV Indoor GIS Substations at Phool Bag, Gwalior on total turn-key basis against TR-35/2021
2022_MPPTC_186828_1
TR-35/2021 (Snap )
Limited
Electrical Works
730 days
MPPTCL Gwalior Site
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
Exempted
8 Mar 2022
24 Feb 2022
8 Mar 2022
24 Feb 2022
7 Mar 2022
25 Feb 2022
Amount
Erection of structures including tightening and punching of nuts, bolts.
Stringing of overhead gantries, vertical droppers with ACSR conductor including fixing of insulator string, spacers, clamps etc.
Single Zebra
Stringing of overhead shield wire with 7/3.66 mm standard galvanized steel complete with fixing of strain clamps at the structures.
Suspension/T Clamps & Power/Terminal Connectors [not covered in respective equipments/ switchgear] etc. suitable for Single ASCR Panther [ for incterconnection from Line gantry, CVT, LA, Line Trap up to isolator incoming end] [Specify the Break Up with Quantity and Unit Prices for various items considered for this component of Price Scehdule]
Add: Any other item bidder may require to complete the Switchyard Erection & Support Installations as per specification requirements
Installation of transformers
50MVA 132/33KV Transformer (with Oil and associated equipments) Complete assembly and erection of power transformer with connections etc including installation of marshalling boxes, control cabinets, air sealing radiators, cooling fans, all accessories etc for transformer including their preliminary checks. Unloading /handling of transformer accessories, handling and filling of transformer oil along with associated equipments.
STATION TRANSFORMERShifting of 33/0.4 KV Station transformer up to Xmer Foundation and placing on it & connection to bushing & earth connection along-with installation of associated Isolator, DO set, LA & LTDB and associated work etc.
132 kV Indoor GIS Switchgear Equipments
145kV, 1250A, SF6 gas insulated Transformer bay module each comprising of SF6 gas insulated circuit breaker, current transformer , bus-bar disconnectors with common earthing switch, line disconnector with safety earthing switch, Lightening arrestor, SF6 gas monitoring system for complete bay, local control cubicle, Other accessories/items if any to complete transformer bay module alongwith XLPE Cable and terminations as indicated in the SLD/ Layout of substation and as per technical specifications.
145kV, 1250A, SF6 gas insulated Feeder bay module each comprising of SF6 gas insulated circuit breaker, current transformer , bus-bar disconnectors with common earthing switch, line disconnector with saftey grounding switch, high speed fault making grounding switch, Lightening arrestor, SF6 gas monitoring system for complete bay, local control cubicle, Other accessories/items if any to complete feeder bay module alongwith XLPE Cable and terminations as indicated in the SLD/ Layout of substation and as per technical specifications.
145kV, 1250A, SF6 gas insulated As a Spare module used as Transformer / Feeder Bay module each comprising of SF6 gas insulated circuit breaker, current transformer , bus-bar disconnectors with common earthing switch, line disconnector with safety earthing switch, Lightening arrestor,SF6 gas monitoring system for complete bay, local control cubicle,
145kV, 2500A, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated circuit breaker, current transformer, disconnectors with safety earthing switches, Local control cubicle, SF6 gas monitoring system for complete bay etc. as indicated in the SLD/ Layout of substation and as per technical specifications.
Double Bus Arrangement, 145kV, 3 Phase, SF6 gas insulated metal enclosed 2500A bus bars running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer complete disconnector with safety earthing switch, local control cubicle (if required), SF6 gas monitoring system etc. for the complete bus as indicated in the SLD/ Layout of substation and as per technical specifications.
Suitable Capcity EOT Crane for GIS Hall/ Building
Ventilation system for GIS Hall/ Building (as per technical specification)
Add: Any other item bidder may require to complete the 132 kV Indoor GIS Switchgear Equipments as per specification requirements
36 kV Metal Clad GIS Indoor Switchboard(For indoor installation of modular design alongwith BCU based Control & Protection system.)
Metal clad Double Bus Indoor GIS Switchboard Including Incomer Transformer Feeder Bays alongwith all associated accessories CTs,LAs. Control Cubicle and Complete with the Control & Protection schemes [ 36 kV, 2500A, 31.5 kA Class]
Metal clad Double Bus Indoor GIS Switchboard Including 8 Nos. Outgoing Feeder bays alongwith all associated accessories CTs,LAs,Control Cubicle and Complete with the Control & Protection schemes [ 36 kV,1250A, 31.5 kA Class]
Metal clad Double Bus Indoor GIS Switchboard Including 1 Nos. 1x12MVAR Capacitor bank bayalongwith all associated accessories CTs LAs.Control Cubicle and Complete with the Control & Protection schemes [ 36 kV, 2000A, 31.5 kA Class]
Metal clad Double Bus Indoor GIS Switchboard Including 1 No. bus-Coupler bay CTs. Control Cubicle and Complete with the Control & Protection schemes [ 36 kV, 2500A, 31.5 kA Class]
Metal clad Double Bus Indoor GIS Switchboard Including 1 No. Station Transformer bayalongwith all associated accessories CTs. Control Cubicle and Complete with the Control & Protection schemes [ 36 kV, 1250A, 31.5 kA Class]
Metal clad Double Bus Indoor GIS Switchboard Including 2 Nos. PTs (one for each Bus) associated accessories Control Cubicle and Complete with the Control
Installation of self supporting Composite type Polymeric Premolded Type End Termination for power cable of feeder bay complete in all respect with required fabrication on lattice support structure which also includes required lattice galvanized cable support structure, civil work, suitable clamp and connectors etc. complete in all respect with providing maintenance free earthing pit and GI earthing strip of each phase and required earthing
Installation of self supporting Composite type Polymeric Premolded Type End Termination for power cable of transformer bay complete in all respect with required fabrication on lattice support structure which also includes required lattice galvanized cable support structure, civil work, suitable clamp and connectors etc. complete in all respect with providing maintenance free earthing pit and GI earthing strip of each phase and required earthing
Installation of Three phase earth Link Box with SVL for each circuit with providing maintainance free earthing pit and GI earthing strip including required fabrication of structure, civil work if any
Installation of Three phase earth Link Box without SVL for each circuit with providing maintainance free earthing pit and GI earthing strip including required fabrication of structure, civil work if any.
Cable Termination/ Plug for terminating in 145kV, 1250A, SF6 gas insulated Feeder bay module 2 Nos. (Normally cable sizes is 1x800 Sq. mm per phase (3 nos cable for each feeder +1No.spare, exact size shall be decided during detailed engineering)
Cable Termination/ Plug for terminating in 145kV, 1250A, SF6 gas insulated Transformer bay module 2 Nos. (Normally cable sizes is 1x800 Sq. mm per phase (3 nos cable for each transformer+1No spare, exact size shall be decided during detailed engineering)
Cable Termination/ Plug for terminating in Metal clad switchgear panels for 2 Nos. (50 MVA Transformer) panels (Normally cable sizes is 2x630 Sq. mm per phase (6 nos cable for each transformer exact size shall be decided during detailed engineering)
Cable Termination/ Plug for terminating in Metal clad switchgear panels for 8+1 Nos. (Outgoing Feeders+Cap Bank) panels (Normally cable sizes is 400 Sq. mm exact size shall be decided during detailed engineering)
Cable Termination/ Plug for terminating in Metal clad switchgear panels for 1 Nos. (Station Transformer) panel (Normally cable sizes is 35 Sq. mm exact size shall be decided during detailed engineering)
Add: Any other item bidder may require to complete the 36 kV Metal Clad GIS indoor Switchboard as per specification requirements
132 KV & 33 kV XLPE Cables & Accessories
1C,800 Sq. mm, Al., 132 kV XLPE Armoured Cable laying alongwith accosciated accessories and required material as per laying method adopted etc. (This include 24 lengths of cable with suitable
Under ground laying / installation of 08No. 76/132 KV (E), Single Core 800 Sq. mm XLPE insulated Power Cable (@ 03No. per Ckt. plus 01No. Spare) in Trefoil formation alongwith 02Nos. earth continuity cable (@ 1No. per circuit) and 02No. FOAC cable (@ 1No. per circuit) within HDPE pipe (One pipe per FOAC cable) and installation with hardware (like ties/clips/cleats, conduits, HDPE ducts, supports, fittings, accessories etc), phase identification tag, pre warning tape, route marker, HDPE pipe etc.), testing, installation etc. and associated civil works:-
With open excavated trench (about of size 0.85M wide & 2.25M deep per circuit) in any type of soil, casting RCC side walls of size 0.6Mx0.05M, filling 0.25M sand before and upto 0.6M after laying cables, laying precasted RCC slab of size 0.6Mx0.05M over sand, back filling rest trench with natural soil and compaction (inclusive of all requisite materials (like sand, pre cast slabs, trefoil clamps mounted at min. 3Mtr. spacing)
Laying/dressing/erection/connection of 8No. 76/132 KV (E), Single Core 800 Sq. mm XLPE insulated Power Cable (@ 3No. per Ckt. plus 1No. spare) in Trefoil formation, 2Nos. earth continuity cable (@ 1No. per circuit) and 2No. FOAC cable (@ 1No. per circuit) inclusive of all requisite material (like clamps, phase identification tag, construction of maintenance free earth pits seperately for each Ligthening Arrestors, supply & erection of G.I. earthing strip per phase, chamber, earthing connections, jumpering of conductors of overhead portion of the line etc.on tower structure including erection of Surge Arrester & FOAC cable in HDPE pipe & termination of fibers and required fabrication work if required for mounting.
3 C, 35 Sq. mm. Al., 33 kV XLPE Cable with Suitable Outdoor & Indoor Terminations [3+3]for connecting the HV side of Substation Transformer to O/G of 36 kV Metal Clad GIS Switchgear
1C, 630 Sq. mm, Al., 33 kV XLPE Armoured Cable alongwith accosciated accessories and required material as per laying method adopted etc. (This include 12 lengths of cable with suitable Outdoor & Indoor [12+12] end Terminations)
3 C, 400 Sq. mm. Al., 33 kV XLPE Cable with Suitable Outdoor & Indoor Terminations [3+3]for connecting Outgoing feeder & Cap Bank to O/G of 36 kV Metal Clad GIS Switchgear (9+4spare lengths of cable with suitable Outdoor & Indoor end Terminations)
33 kV XLPE Cable Termination support structure for Connecting to 33 kV Side of 132/33 kV Transformer including 33 kV Class LAs (3 Nos.), Supporting PI String (3 Nos.), nut bolts, fixing accessories etc. as per drawing appended in Section-I
Add: Any other item bidder may require to complete the 33 kV XLPE Cable system as per specification requirements
C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II)
132 kV C&R Panel For feederType SAS-FCRA
132 kV C&R Panel For Bus Coupler Type SAS-BCRA
132 kV C&R Panel For Transformer Type SAS-TCRA
132 kV C&R Panel for Bus Bar Type SAS-BBRA
Substation SAS Netorking Panel SAS-NW
Station HMI [Industrial grade Computer with 23"LED monitor as per specification requirements] With inbuilt storage capacity for Minimum 3Years Substation Data
Station HMI (Hot Standby)[Industrial grade Computer with 23"LED monitor as per specification requirements] With inbuilt storage capacity for Minimum 3Years Substation Data
HMI View Node[Industrial grad Computer with 23"LED monitor as per specification requirements]With inbuilt storage capacity for Minimum 3Years Substation Data
DR Work Station[Industrial grade Computer with 23"LED monitor as per specification requirements] With inbuilt storage capacity for Minimum 3Years Substation Data
70'' Wall Mounted LED Display in Control Room
A3 Size Color Laser Printer
Mono Crome Laser Printer
One Remote Workstation with HMI[Industrial grade Computer with 23"LED monitor as per specification requirements] With inbuilt storage capacity for Minimum 3Years Substation Data & Laser Printer (A4 Size) for RCC
Hardware Gateways (for data transmission to SCADA C/R, SLDC & SUB SLDC)Multy Protocol,multy control centre support with Minimum Four (4) control centre connectivity
Modems (both sending and Receiving End) for communication to SCADA C/R &SLDC & Sub SLDC [Specify the Break Up with Quantity and Unit Prices for various items considered for this component of Price Scehdule]
Software: Application as well as System Software as per specification requirements for various hardware elements for meeting of functional requirement of the specification.[Specify the Break Up with Quantity and Unit Prices for various items considered for this component of Price Scehdule]
Substation LAN Commnication Infrastructure
Ethernet Switches:
132 kV Side C&R and Network Panels:12 Nos.{6 Port (4 Nos. 10/100 BaseFX + 2 No. 10/100/1000 Base FX)}, 2 Nos. {24 Port 10/100 Mbps + 2 port 10/100/1000 Base FX}]
33 kV Side C&R Panels: 2 Nos.{16 Port (4 Nos. 10/100 BaseFX + 2 No. 10/100/1000 Base FX)}
Other Items : Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the substation LAN as per specification requirements. [Specify the Break Up with Quantity and Unit Prices for various items considered for this compo
Inverter (3 kVA Capacity) to be operatable on 230VAC and 220 VDC as per availability of supply (Normally on AC)
Inverter (1 kVA Capacity) to be operatable on 230VAC and 220 VDC as per availability of supply (Normally on AC)
Add: Any other item bidder may require to complete the C&R Panels and SAS system as per specification requirements
Lightening (Surge) Arrestors
132kV class of 120kv rating LAs with grading ring discharge counter with milli ammeter including inverted LA of line
33kV class of 30kV/36kV rating LAs
Add: Any other item bidder may require to complete the Surge Arrester installation as per specification requirements
Solid core Insulators (BPI)
145 kV Class Solid core (Post) Insulator (if required)
33 kV class Solid core (Post) Insulator
33 kV Spacial P I set With Insulator for capacitor bank
132 kV Disc Insulator String Suspension type alongwith suitable hardware
Isolators
Horizontal double break (HDB)motor operated 33kV isolator complete with all fittings, accessories, terminal connectors and all other items (as specified in technical specification for 1250A/800A HDB isolator with single earth switch)
Horizontal double break (HDB)motor operated 33kV isolator complete with all fittings, accessories, terminal connectors and all other items (as specified in technical specification for 1250/800A HDB isolator without earth switch)
Add: Any other item bidder may require to complete the Isolator Installation as per specification requirements
Batteries & Battery Charger
Batteries (Sizing shall be as per requirement of technical specification)
220 V/300AH VRLA
48 V/300AH VRLA
Battery Charger System
220 V Float cum Boost
48 V Float Cum Boost
Add: Any other item bidder may require to complete the Battery & Battery Charger as per specification requirements
Lighting System
Lighting fixtures (1X 400 W) for illumination of outdoor switchyard including the cost of sodium vapour lamps with all accessories and required cables, complete in all respects.
Lighting fixtures (2X 400 W) for illumination of outdoor switchyard including the cost of sodium vapour lamps with all accessories and required cables, complete in all respects.
1 x 11w LED lamps emergency light with Battery operated portable type with builtin battery and battery charger suitable for 6 hours operation.
Outdoor Lighting poles with Lamps & Lighting Fixtures etc. complete
GLS lamps of 100 w for operation on 220 V DC for Emergency lighting
Lighting & Electrical Fixtures with Lamps, indoor/ outdoor receptles, G.I. Conduit, Junction Boxes, pull out boxes, wiring, Switchboard, Switches etc. for control room building and GIS Hall [not covered under the civil works][Specify the Break Up with Quantity and Unit Prices for various items considered for this component of Price Scehdule]
Lightning Cum Lighting Masts. Approximate Unit Weight 2.68MT for each Mast
Add: Any other item bidder may require to complete the Lighting System as per specification requirements
Fire Fighting System
Nitrogen Injection Fire Protection System for Power Transformer complete in all respects.
Fire Fighting equipment with necessary mounting standsDCP Type. :
DCP Type
ii) 10 Kg. Trolly Mounted
iii)75Kg, Trolly Mounted
Carbon di oxide type
6 Liters.
22.5 Liters.
Foam Type
9 Liters
50Ltr, Trolley Mounted ( Cylinder Type)
Sand type
Set Of Fire Buckets Comprising 6 Nos Buckets, Capacity-9Kg , Each with Stand ( Set )
Add: Any other item bidder may require to complete the fire figting system as per specification requirements
Air Conditioning System
High Wall Split AC units of 2 TR Capacity complete with Indoor, Outdoor Units and required accessories, Stablizers etc.
Add: Any other item bidder may require to complete the Air Conditioning system as per specification requirements
LT Switchgear
LT AC Main Panel
LT AC Distribution Board
Main Lighting Distribution Board
Emergency Lighting Distribution Board
DG Incoming Board
220V DCDB
48V DCDB with Switching Cubicle
Add: Any other item bidder may require to complete the LT Switchgear Installation as per specification requirements
Earthing System
Installation & testing of the following including jointing, equipment termination, fixing & clamping with accessories & hardware required such as saddle, clamps, cleats, plugs, screws, nuts, bolts, washers and welding, brazing etc.Earth electrodes installation directly driven/drilled (40 to 50 mm dia) into earth including excavation (irrespective of type of soil encountered) backfilling with bentonite soil (to be arranged by contractor) welding to earth conductor etc. Providing of steel risers and making earth mat (duly buried at a depth as per design approved) including backfilling with black cotton soil (to be arranged by the contractor) welding etc. and bolting of risers to the structure at desired place. Eathing of GIS Indoor equipments of 145/36kV Class by cupper flat Considering flat size asper design approved
40 mm Dia MS Rod
3m, 20 mm Dia MS Rod Electrode
3m, 40 mm Dia MS Rod Electrode
3m, 42 mm Dia Safe Earthing Electrodes
3m, 60 mm Dia Safe Earthing Electrodes
50X12 mm GS Flat
50X6 mm GS Flat
50 X 6 mm MS Flat
25 X 3 mm GS Flat
Preparation of earthing pits (1.5X1.5.X3 Mtrs.) as per drawing attached with bid document, which includes excavation (Irrespective of the soil encountered) embedding of 4 No. GI Pipes of size 40 mm dia, 3 Mtrs. Long, back filling with B.C. soil (to be arranged by the contractor) free from boulders and harmful mixture. These GI pipes are to be welded with MS flats by making mesh frame and cutting of pipes as also making holes in the pipe for water seepage. The earth pit is to be connected with earth mesh of MS flat.
Add: Any other item bidder may require to complete the Earthing System as per specification requirements
1.1kV Grade PVC insulated Al. conductor power cables and copper conductor armoured control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room building]
Power Cable(PVC)
3.5Cx150 sq.mm
3.5Cx70 sq.mm
3.5Cx35 sq.mm
4Cx16 sq.mm
4Cx6 sq.mm
2Cx6 sq.mm
1Cx6 sq. mm
Laying of Control Cable (PVC)(armoured/unarmoured) on racks/cable trays/ angle support overhead racks conduits including dressing of cables with accessories for copper conductor & armoured control cables. Cable terminations including fixing of cable glands, lugs etc. for each type of control/ power cables, including terminations at both ends. I.R. value between cores and I.R. value with respect to its armouring is to be verified. The continuity of all cores is also to be verified. Both work to be done before connecting cable to the terminal block. Making suitable hole in bottom/side plate of C&R panel, AC/DC Board, Marshaling box for fixing cable glands in addition to cable gland holes already provided. The hole should be free from burrs. Fixing all cables in respective cable glands and re-fixing gland plate to its original place. All cable identification plate is to be provided on both ends of each cable. Stripping of outer insulation cover, armoring etc. of cable, fixing ferrules on each core at both ends. Stripping all cores to suitable length, making eye, crimping terminal lugs (as the case may be) and fixing it to terminal block as per drawing followed by proper bending/ dressing of all cores.
2Core 2.5 Sq.mm armoured
4Core 2.5 Sq.mm armoured
8Core 2.5 Sq.mm armoured
12 Core 2.5 Sq.mm armoured
19 Core 2.5 Sq.mm armoured
Conduits, Cable Trays, Cable Tags, Cable Racks & Supports, Cable Glands, Cable Lugs, Gland Plates, Junction Boxes [Specify the Break Up with Quantity and Unit Prices for various items considered for this component of Price Scehdule][Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room building]
Add: Any other item bidder may require to complete the Power & Control Cables as per specification requirements
DIESEL GENERATOR SET
DG Set along with enclosure and control panel (25 kVA)
Add: Any other item bidder may require to complete the 25 kVA DG Set as per specification requirements
GST @18% on Schedule A4
Bidder Name
Amount
KANOHAR ELECTRICALS LIMITED(GSTN-NA)
Description of Work / Item(s)
145kV GIS EQUIPMENTS (All the three phase in single enclosure)
145kV, 1250A, SF6 gas insulated Transformer bay module each comprising of SF6 gas insulated circuit breaker, current transformer , bus-bar disconnectors with common earthing switch, line disconnector with safety earthing switch, Lightening Arrestor, SF6 gas monitoring system for complete bay, local control cubicle, SF6 Gas Insulated terminal connection for connecting Power Transformer with GIS through XLPE cable complete with all accessories. . Other accessories/items if any to complete transformer bay module alongwith XLPE Cable interconnection and terminations as indicated in the Tentative SLD/ Layout of substation and as per technical specifications.
145kV, 1250A, SF6 gas insulated Feeder bay module each comprising of SF6 gas insulated circuit breaker, current transformer , bus-bar disconnectors with common earthing switch, line disconnector with saftey grounding switch, high speed fault making grounding switch, Lightening Arrestor, SF6 gas monitoring system for complete bay, local control cubicle, SF6 Gas Insulated terminal connection for connecting outdoor equipments with GIS through XLPE Cable complete with all accessories. Other accessories/items if any to complete feeder bay module alongwith XLPE Cable interconnection duct and terminations as indicated in the Tentaive SLD/ Layout of substation and as per technical specifications.
145kV, 1250A, SF6 gas insulated As a Spare module used as Transformer / Feeder Bay module each comprising of SF6 gas insulated circuit breaker, current transformer , bus-bar disconnectors with common earthing switch, line disconnector with safety earthing switch, Lightening Arrestor,SF6 gas monitoring system for complete bay, local control cubicle,
Double Bus Arrangement, 145kV, 3 Phase, SF6 gas insulated metal enclosed 2500A bus bars running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer complete disconnector with safety earthing switch, local control cubicle (if required), SF6 gas monitoring system etc. for the complete bus as indicated in the TentativeSLD/ Layout of substation and as per technical specifications.
145kV, 2500A, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated circuit breaker, current transformer, disconnectors with safety earthing switches, Local control cubicle, SF6 gas monitoring system for complete bay etc. as indicated in the Tentaive SLD/ Layout of substation and as per technical specifications. .
132kV Lightenig Arrestor(out door)
Suitable Capcity EOT Crane for GIS Hall/ Building(Minimum of 5 T Ratting)
Ventilation system for GIS Hall/ Building (as per technical specification)
132 kV Post Insulator
Add: Any other item bidder may require to complete the 132 kV Indoor GIS Switchgear Equipments as per specification requirements
36 kV Metal Clad GIS Indoor Switchboard(For indoor installation of modular design alongwith BCU based Control & Protection system.)
Metal clad Double Bus Indoor GIS Switchboard Including Incomer Transformer Feeder Bays alongwith all associated accessories CTs,LAs. Disconnector switches without earth switch bus side , Control Cubicle and Complete with the Control & Protection schemes [ 36 kV, 2500A, 31.5 kA Class]
Metal clad Double Bus Indoor GIS Switchboard Including. Outgoing Feeder bays alongwith all associated accessories CTs,LAs, Feeder Bays alongwith all associated accessories CTs,LAs. Disconnector switches , Control Cubicle and Complete with the Control & Protection schemes [ 36 kV, 1250A, 31.5 kA Class]
Metal clad Double Bus Indoor GIS Switchboard Including 1 Nos. 1x12MVAR Capacitor bank bayalongwith all associated accessories. CTs,LAs. Disconnector switches ,Control Cubicle and Complete with the Control & Protection schemes [ 36 kV,2000A, 31.5 kA Class]
Metal clad Double Bus Indoor GIS Switchboard Including 1 No. bus-Coupler bay CTs. Control Cubicle and Complete with the Control & Protection schemes [ 36 kV, 2500A, 31.5 kA Class]
Metal clad Double Bus Indoor GIS Switchboard Including 1 No. Station Transformer bayalongwith all associated accessories CTs. Disconnector switches , Control Cubicle and Complete with the Control & Protection schemes [ 36 kV, 1250A, 31.5 kA Class]
Metal clad Double Bus Indoor GIS Switchboard Including 2 Nos. PTs (one for each Bus) associated accessories Control Cubicle and Complete with the Control
33 kV Lightening arrestor(out door)
36 kV Lightening arrestor for capacitor bank(out door)
3 Ph.1250A, Isolator motorised(without E/S) With Insulator ) HDB (AIS) for Transformer Incommer(out door)Individualy phase wise operated
3 Ph.1250A, Isolator (with E/S) With Insulator motorised Gantry mounted) HDB (AIS)(out door) Individualy phase wise operated
3 Ph. 800 A,Isolator motorised (with E/S) With Insulator HDB (AIS) for Cap bank Individualy phase wise operated
3 Ph. 800 A, Isolator motorised (without E/S) With Insulator HDB (AIS) (out door)Individualy phase wise operated
33 kV Solid Core Insulators for substation work
33 kV Special P I structures with set of 3 insulators(for Cap Bank)
36kV 12MVAR Capacitor Bank with structures and accessories(SET)
Add: Any other item bidder may require to complete the 33 kV Indoor GIS Switchgear Equipments as per specification requirements
C&R Panels & SAS system (Complete in all respect,)
132 kV C&R Feeder Panel (Type SAS-FCRA)
132 kV C&R BUS Coupler Panel (Type SAS-BCRA)
132 kV C&R Panel Transformer Panel(Type SAS-TCRA)
132 kV C&R Panel (Busbar proection panel) (Type SAS-BBRA)
Substation SAS Netorking Panel (Type-SAS-NW)
Station HMI [Industrial grade Computer with 23"LED monitor as per specification requirements] With inbuilt storage capacity for Minimum 3Years Substation Data
Station HMI (Hot Standby)[Industrial grade Computer with 23"LED monitor as per specification requirements] With inbuilt storage capacity for Minimum 3Years Substation Data
HMI View Node[Industrial grad Computer with 23"LED monitor as per specification requirements]With inbuilt storage capacity for Minimum 3Years Substation Data
DR Work Station[Industrial grade Computer with 23"LED monitor as per specification requirements] With inbuilt storage capacity for Minimum 3Years Substation Data
70'' Wall Mounted LED Display in Control Room
A3 Size Color Laser Printer
Mono Crome Laser Printer
One Remote Workstation with HMI[Industrial grade Computer with 23"LED monitor as per specification requirements] With inbuilt storage capacity for Minimum 3Years Substation Data & Laser Printer (A4 Size) for RCC
Hardware Gateways (for data transmission to SCADA C/R, SLDC & SUB SLDC)Multy Protocol,multy control centre support with Minimum Four (4) control centre connectivity
Modems (both sending and Receiving End) for communication to SCADA C/R, SLDC & SUB SLDC) [Specify the Break Up with Quantity and Unit Prices for various items considered for this component of Price Scehdule]
Software: Application as well as System Software as per specification requirements for various hardware elements for meeting of functional requirement of the specification.[Specify the Break Up with Quantity and Unit Prices for various items considered for this component of Price Scehdule]
Substation & LAN Communication infra Structure
Ethernet Switches:
132 kV Side C&R and Network Panels:12/16 Nos.{6 Port (4 Nos. 10/100 BaseFX + 2 No. 10/100/1000 Base FX)}, 2 Nos. {24 Port 10/100 Mbps + 2 port 10/100/1000 Base FX}](No of Ethernat Switches & Port are indicative . These should be as per requirement)
33 kV Side C&R Panels: 2 Nos.{16 Port (4 Nos. 10/100 BaseFX + 2 No. 10/100/1000 Base FX)}(No of Ethernat Switches & Port are indicative . These should be as per requirement)
Other Items:
Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the substation LAN as per specification requirements.
Inverter (3 kVA Capacity) to be operatable on 230VAC and 220 VDC as per availability of supply (Normally on AC)With Auto change over
Inverter (1 kVA Capacity) to be operatable on 230VAC and 220 VDC as per availability of supply (Normally on AC)With Auto change over
Add: Any other item bidder may require to complete the C&R Panels and SAS system as per specification requirements
TRANSFORMER & ASSOCIATED EQUIP.
50 MVA 132/33KV Transformer (with Oil and associated equipments)
Oil filtration Machine (500 Gl.per Hr.)
Oil Storage Tank (10 KL)
Fabricated GalvanisedSteel Structures
Total Fabricated GalvanisedSteel Structures weight
GI Foundation bolts, Nut bolt & washers etc. (10%of above)
Busbar, Cabling, Screening & Hardware Material
Zebra Conductor (in Kms)
76/132 kV(E), Single Core 800 Sq. mm. Aluminium conductor XLPE insulated, Lead Alloy-E sheathed, Copper wire screened, overall HDPE outer sheathed power cable (Short circuit current of 40kA for Screen & Armour combined)
Earthing/Sheath bonding Cable 6.6 kV 1Cx300 sq. mm. Copper conductor, XLPE insulated cable
Supply of 1Cx185 sq mm Copper conductor, XLPE insulated Earth continuity cable connecting earth pit to earth pit (1.1 kV class)
Fibre Optic Approach Cable ( DWSM - Dual window single mode, 24F) - with installation hardware like ties / clips / cleats, conduits, HDPE ducts, supports, fittings, accessories etc)
Three phase earth Link Box with SVL for each circuit of 132KV Cable
Three phase earth Link Box without SVL for each circuit of 132KV Cable
132kv class Dry type self supporting Composite type Polymeric Premolded End Termination for power cable. Suitable for erection on transmission line tower .
132kV Class-3 Lightening Arrestor with all the accessories and clamp and connectors suitable to install on tower
132KV class suitable for 76/132 kV(E), Single Core 800 Sq. mm. Aluminium conductor XLPE insulated, Lead Alloy-E sheathed, Copper wire screened, overall HDPE outer sheathed power cable Indoor Terminations in GIS module
132kv class Dry type self supporting Composite type Polymeric Premolded End Termination for power cable. Suitable for connecting power transformer on supporting structure.
3 C, 35 Sq. mm. Al., 33 kV XLPE Cable with Suitable Outdoor & Indoor Terminations [3+3]for connecting the HV side of Substation Transformer to O/G of 36 kV Metal Clad GIS Switchgear which includes Outdoor & Indoor termination kit.
1C, 630 Sq. mm, Al., 33 kV XLPE Armoured Cable alongwith accosciated accessories and required material as per laying method adopted etc. (This include 12+6 spare lengths of cable with suitable Outdoor & Indoor [18+18] end Terminations) which includes Outdoor & Indoor termination kit.
3C, 400 Sq. mm, Al., 33 kV XLPE Armoured Cable alongwith accosciated accessories and required material as per laying method adopted etc. for connecting the Outgoing feeder gentry isolators to O/G of 36 kV Metal Clad GIS Switchgear (This include 9+4spare lengths of cable with suitable Outdoor & Indoor end Termination kit)
Add: Any other item bidder may require to complete the 33 kV & 132 KV XLPE Cable system as per specification requirements
90 kn 132kv Single Tension string for Single Panther
70 kn 132kv Single Suspension string Single Zebra
Junction Box (36 Ways)
4 Inch IPS ALTube
Earthing System
40 mm Dia MS Rod
3m, 20 mm Dia MS Rod Electrode
3m, 40 mm Dia MS Rod Electrode
3m, 42 mm Dia Safe Earthing Electrodes
3m, 60 mm Dia Safe Earthing Electrodes
50X12 mm GS Flat
50X6 mm GS Flat
50 X 6 mm MS Flat
25 X 3 mm GS Flat
50x 8 copper flat
GI Pipe 40 mm Dia., 4mm Thk along with clamp for Earth Pit(in Mtrs)
Add: Any other item bidder may require to complete the Earthing System as per specification requirements
Fire Fighting System
Nitrogen Injection Fire Protection System for Power Transformer complete in all respects.
Fire Fighting equipment with necessary mounting stands.
DCP Type
ii) 10 Kg. Trolly Mounted
iii)75Kg, Trolly Mounted
Carbon di oxide type
6 Liters.
22.5 Liters.
Foam Type
9 Liters
50Ltr, Trolley Mounted ( Cylinder Type)
Sand type
Set Of Fire Buckets Comprising 6 Nos Buckets, Capacity-9Kg , Each with Stand ( Set )
Add: Any other item bidder may require to complete the fire figting system as per specification requirements
AC/DC SUPPLY
L T Distribution Box
25KVA DG Set Complete with all accessories
Station Transformer,200KVA,33/0.4KV
R S Joist 175X85, 11Mtr Long for Station Transformer
MS Channel 100X50X6, 6Mtr Long for Station Transformer
33kV D.O. Set
220Volt 300Ah Battery Set VRLA Type
48Volt 300Ah Battery Set VRLA Type
220Volt Battery Charger
48Volt Battery Charger
AC Distribution Boxes 415Volt
DC Distribution Boxes 220 Volts
DC Distribution Boxes 48 Volts with switching cubicle
LT AC Main Panel
Main Lighting Distribution Board
Emergency Lighting Distribution Board
DG Incoming Board
Lighting System
Lighting fixtures (1X 400 W) for illumination of outdoor switchyard including the cost of sodium vapour lamps with all accessories and required cables, complete in all respects.
Lighting fixtures (2X 400 W) for illumination of outdoor switchyard including the cost of sodium vapour lamps with all accessories and required cables, complete in all respects.
1 x 11w LED lamps emergency light with Battery operated portable type with builtin battery and battery charger suitable for 6 hours operation.
Outdoor Lighting poles with Lamps & Lighting Fixtures etc. complete
GLS lamps of 100 w for operation on 220 V DC for Emergency lighting
Lightning Cum Lighting Masts. Approximate Unit Weight 2.68MT for each Mast
Add: Any other item bidder may require to complete the Lighting System as per specification requirements
Air Conditioning System
High Wall Split AC units of 2 TR Capacity complete with Indoor, Outdoor Units and required accessories, Stablizers etc.
Add: Any other item bidder may require to complete the Air Conditioning system as per specification requirements
Power Cable (PVC)
3.5Cx150 sq.mm
3.5Cx70 sq.mm
3.5Cx35 sq.mm
4Cx16 sq.mm
4Cx6 sq.mm
2Cx6 sq.mm
1Cx6 sq. mm
Control cable
2Core 2.5 Sq.mm armoured
4Core 2.5 Sq.mm armoured
8Core 2.5 Sq.mm armoured
12Core 2.5 Sq.mm armoured
19 Core 2.5 Sq.mm armoured
Add: Any other item bidder may require to complete the Power & Control Cables as per specification requirements
SUB STATION CLAMPS
T CLAMPS ZEBRA Run -ZEBRA Tap
P.G.CLAMPS
ZEBRA -ZEBRA
ZEBRA –PANTHER
Earth Wire Clamp
Testing & Maintenance Equipment for GIS
Insulation Rubber mat (1mX2mX 12 mm)
Isulation Rubber Gloves (15 kV Tested)
Portable Discharge Rod
Portable SG6 Gas handing plant as per Specification
Partial Discharge Monitoring System (Portable)
Dew Point meter
SF6 Gas Leak Detector
SF6 gas purity detector / analyzer for SO2, H2O, CF4, AIR etc
Air / gas humidity tester,
Breaker timing measurement kit with all necessary attachment required for CB housed in SF6 gas filled metallic enclosur
Aluminum Ladder
Cartwheel mounted aluminum ladder
Self supporting aluminum ladder
Furniture for Control Room Building:
Junior executive table with three drawings on right side One Cup board left side with prelaminated decolam top 20mm thick over painted M.S. Frame ( 4 ½ feet x 2 ½ feetx 2 ½ feet).
Control Desk Type Table for Control room accomodating the Main and Redundant Computer System monitors, Workstations, printer, Logger, Maintenance/Engineering Terimnal, telephones etc.
Steel tubular “S” type with continuous and one feet dia 14guage pipe, cane seat backing, teak wood with quality cane.
Five Leg Revolving Chair with arms
Steel Almirah of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 18 guage with three way locking system.
Steel Almirah (with Glass doors) of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 18 guage with three way locking system.
Minor Almirah of size 4 ½ feet x30 inch x 17 inch with three shelves making four compartments in 18 guage with three waylocking system.
Steel rack of size 5 feet x 3 feet x 16 inches with six shelves making five compartments ( 22 guage).
Steel file trays of size 16 inches x11 inches x 3 inches of guage 14 SWG.
Steel stools of size 15 inch x15 inch x 18 inch square pipe 16 guage
Steel waste paper baskets of size 12 inch x 10 inch x 10 inch.
Short bench of 4 feet x 14 inch x 1 ½ inch with laminated top.
Key board (wooden)
First Aid Box
Shock Treatment Chart
Substation Name Board [Size and Color etc. be got approved from owner]
Danger Plate [Size and Color etc. be got approved from owner]
Water Cooler (Storage type, Storage Capacity 40 Ltr, Cooling Capcity 20 Ltr./hr) and Water Purifier/Filter
GST On Schedule-A1 @18%
stage.html
html • 0.02 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.66 MB
Snapbiddtd24022022TR352021.pdf
Tender Documents • 0.65 MB
BOQ_216548.xls
BOQ • 0.62 MB
Download all tender documents and submit your bid