GE (UTILITY) SECUNDERABAD
GE UTILITY SECUNDERABAD MUDFORT SECUNDERABAD-500003
REPAIR/ REPLACEMENT MAINTENANCE OF LT SWITCH GEAR, PANEL, APFC PANEL, CAPACITOR BANK AND CONNECTED ITEM AT CERTAIN LOCATION OF OR MD/ JCO MD ACCN OF TRISHUL LINE AREA, SANJAY LINE AREA, LAKE LINE AREA AND CERTAIN AREA UNDER AGE EM I OF GE(U) SECUND
2026_MES_788055_1
GE (U)/SEC/TOKEN/M53 OF 2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
SECUNDERABAD
As per Tender Document
8 documents required · 8 mandatory
₹500
GE (UTILITY) SECUNDERABAD
₹96,000
Yes
5 Sept 2026
5 Sept 2026
3 Oct 2026
5 Sept 2026
26 Sept 2026
19 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 500 Amps rating for phase and neutral 4 strips with colour | 4 | Each job | 99 | ₹396 |
| 1.01 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- | - | - | - | - |
| 1.02 | MCCB 4pole, 315 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) | - | - | - | - |
| 1.03 | MCCB 4pole, 100 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 06 No (Outgoing) | - | - | - | - |
| 1.04 | Digital Ammeter 0 to 500Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set | - | - | - | - |
| 1.05 | Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set | - | - | - | - |
| 1.06 | Indicator lamp R, Y, B LED type with 3 Nos of 2A HRC fuses - 01 Set | - | - | - | - |
| 2 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 400 Amps rating for phase and neutral 4 strips with colour | 2 | Each job | 99 | ₹198 |
| 2.01 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- | - | - | - | - |
| 2.02 | MCCB 4pole, 315 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) | - | - | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.16 MB
M53_8659_Tender.pdf
Tender Documents • 0.45 MB
BOQ_883252.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .