| Sl No | Description | Qty | Unit | Computer Gallery L1 | Creative Projects L3 | KALPANA ELECTRONICS L2 |
|---|---|---|---|---|---|---|
| 1.00Supply, Installation,Testing & Commisioning of Microprocessor based Intelligent, addressable 4 Loops fire alarm control panel ( VDS / UL / FM / ULC approved ) fully networkable with each loop capable of taking 120 devices, 1/4 VGA display character alphanumeric liquid crystal display.The panel shall be soft addressable type.The panel shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. | ||||||
| 1.01The panel shall have in built rectifier, provision for external & internal printer { if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required. | ||||||
| 1.02 | The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system and BMS( RS 485 ). The panel should have modbus output & ready to communicate with remote computer. The system must be preloaded with licenced software. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor) | 1 | Item | 1,80,000 ₹1,80,000 | 2,55,000 ₹2,55,000 | 2,10,000 ₹2,10,000 |
| 2.00 | Supply, Installation,Testing & Commisioning of Analog Addressable Intelligent multisensor detector (VDS/UL/FM/ULC approved) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as perrecommended standard. (Note: Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a froup will be as per latest recommended standards) without any additional cost). (Approved Make:- Esser / Cerberus Pro / Bosch / Johnson cntrols / Notifer / Edward / Secutron / Securiton / Apollo/ Morley/ System Sensor) | 45 | Each | 2,050 ₹92,250 | 2,750 ₹1,23,750 | 2,650 ₹1,19,250 |
| 3.00 | Supply, Installation,Testing & Commisioning of Addressable Heat detector (Fixed temperature cum rate of rise) (VDS/UL/FM/ULC approved) with twist lackable removal base , built in fault isolator drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard (Note: Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a froup will be as per latest recommended standards) without any additional cost).
(Approved Make:- Esser/ Cerberus Pro / Bosch / Johnson Controls / Notifer / Edward / Secutron / Securiton / Apollo / Morley / System Sensor) | 5 | Each | 2,050 ₹10,250 | 2,300 ₹11,500 | 1,000 ₹5,000 |
| 4.00 | Supply, Installation,Testing & Commisioning of Addressable Manual Call Point (VDS/UL/FM/ULC approved) soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make:- Esser / Cerberus Pro / Bosch / JohnsonControls / Notifer / Edward / Secutron / Securiton / Apollo / Morley / System Sensor) | 4 | Each | 3,500 ₹14,000 | 3,600 ₹14,400 | 4,250 ₹17,000 |
| 5.00 | Supply, Installation,Testing & Commisioning of Addressable Loop Powerd Hooter (sound output of minimum 90db) cum strobe (strength of light 10 cd) complete with inbuilt isolator and IP65 base and (VDS/UL/FM/ULC approved)(Approved Make:- Esser / Cerberus Pro / Bosch / JohnsonControls / Notifer / Edward / Secutron / Securiton / Apollo / Morley / System Sensor) | 4 | Each | 4,000 ₹16,000 | 9,550 ₹38,200 | 8,450 ₹33,800 |
| 6.00 | Supply, Installation,Testing & Commisioning of Addressable transponder/ Monitor Modules (VDS/UL/FM/ULC approved) for monitoring flow switches/Fire exit doors/AHU/Lift etc complete as required. (Approved Make:- Esser / Cerberus Pro / Bosch / JohnsonControls / Notifer / Edward / Secutron / Securiton / Apollo / Morley / System Sensor) | 2 | Each | 1,000 ₹2,000 | 500 ₹1,000 | 100 ₹200 |
| 7.00 | Supply, Installation,Testing & Commisioning of Addressable relay Modules (VDS/UL & FM approved) for switching/ integration of Lift / AHU etc complete as required. (Approved Make:- Esser / Cerberus Pro / Bosch / JohnsonControls / Notifer / Edward / Secutron / Securiton / Apollo / Morley / System Sensor) | 2 | Each | 100 ₹200 | 500 ₹1,000 | 100 ₹200 |
| 8.00 | Supply and Laying of 2 Core 1.5sqmm FRLS shielded copper Cable (For Loop) (Make:- Finolex/RR Kable/Polycab) with 20mm NB PVC rigid conduit pipe (Make:- Precision / AKG / ATUL / VIP / Universal / BEC / Polycab) on the surface of the wall. | 2,000 | RM | 90 ₹1,80,000 | 40 ₹80,000 | 60 ₹1,20,000 |
Tender Value
Refer Docs
EMD Value
₹12,000
Closing Date
19 Jan 2026, 12:00 pmClosed
EE/DED
Opposite of PWD Inspection Bungalow Kachari Road, Siliguri 734001, District Darjeeling
Special Repair and Renovation of EI Work at the existing Excise Office cum Barrack within DM Office Compound, Darjeeling in the district of Darjeeling - SITC of Fire Detection system.
2025_WBPWD_981360_1
WBPWD/EE/DED/e-NIT-75 of 2025-26
Open Tender
FIRE FIGHTING ORG
DARJEELING
Please refer Tender documents.
4 documents required · 4 mandatory
₹12,000
11 Mar 2026
31 Dec 2025
21 Jan 2026
31 Dec 2025
19 Jan 2026
31 Dec 2025
Supply, Installation,Testing & Commisioning of Microprocessor based Intelligent, addressable 4 Loops fire alarm control panel ( VDS / UL / FM / ULC approved ) fully networkable with each loop capable of taking 120 devices, 1/4 VGA display character alphanumeric liquid crystal display.The panel shall be soft addressable type.The panel shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards.
The panel shall have in built rectifier, provision for external & internal printer { if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system and BMS( RS 485 ). The panel should have modbus output & ready to communicate with remote computer. The system must be preloaded with licenced software. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor)
Supply, Installation,Testing & Commisioning of Analog Addressable Intelligent multisensor detector (VDS/UL/FM/ULC approved) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as perrecommended standard. (Note: Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a froup will be as per latest recommended standards) without any additional cost). (Approved Make:- Esser / Cerberus Pro / Bosch / Johnson cntrols / Notifer / Edward / Secutron / Securiton / Apollo/ Morley/ System Sensor)
Supply, Installation,Testing & Commisioning of Addressable Heat detector (Fixed temperature cum rate of rise) (VDS/UL/FM/ULC approved) with twist lackable removal base , built in fault isolator drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard (Note: Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a froup will be as per latest recommended standards) without any additional cost). (Approved Make:- Esser/ Cerberus Pro / Bosch / Johnson Controls / Notifer / Edward / Secutron / Securiton / Apollo / Morley / System Sensor)
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point (VDS/UL/FM/ULC approved) soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make:- Esser / Cerberus Pro / Bosch / JohnsonControls / Notifer / Edward / Secutron / Securiton / Apollo / Morley / System Sensor)
Supply, Installation,Testing & Commisioning of Addressable Loop Powerd Hooter (sound output of minimum 90db) cum strobe (strength of light 10 cd) complete with inbuilt isolator and IP65 base and (VDS/UL/FM/ULC approved)(Approved Make:- Esser / Cerberus Pro / Bosch / JohnsonControls / Notifer / Edward / Secutron / Securiton / Apollo / Morley / System Sensor)
Supply, Installation,Testing & Commisioning of Addressable transponder/ Monitor Modules (VDS/UL/FM/ULC approved) for monitoring flow switches/Fire exit doors/AHU/Lift etc complete as required. (Approved Make:- Esser / Cerberus Pro / Bosch / JohnsonControls / Notifer / Edward / Secutron / Securiton / Apollo / Morley / System Sensor)
Supply, Installation,Testing & Commisioning of Addressable relay Modules (VDS/UL & FM approved) for switching/ integration of Lift / AHU etc complete as required. (Approved Make:- Esser / Cerberus Pro / Bosch / JohnsonControls / Notifer / Edward / Secutron / Securiton / Apollo / Morley / System Sensor)
Supply and Laying of 2 Core 1.5sqmm FRLS shielded copper Cable (For Loop) (Make:- Finolex/RR Kable/Polycab) with 20mm NB PVC rigid conduit pipe (Make:- Precision / AKG / ATUL / VIP / Universal / BEC / Polycab) on the surface of the wall.
NOTE: 1. The Fire Alarm system shall comply with latest requirements of ---1. National Fire protection Association (NFPA) Standards. 2. IS 2189 3. NFPA 70 National Electrical Code 4. NFPA 72 National Fire Alarm Code 5. Local Statutory Regulations 6. Manufacturer Recommendation.
TESTS: 1.The system shall be tested and commissioned by a qualified competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.
Terms and condition The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.56 MB
WBF2911.pdf
Tender Documents • 0.50 MB
BOQ_2393276.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid