CE, TMC on behalf of Director, TMC
Engineering Department, 6th floor, Service Block, TMH, Parel.
Upgradation modernization of electrical panel and substation Phase I, Annexe Building
2022_TMC_708333_1
TMC/ENG/Elect/UpgradPanel/2022
Open Tender
Electrical Works
Works
150 days
TMH, Parel
As per tender documents
7 documents required · 7 mandatory
₹0
₹1.2 L
Yes
TMH, Parel, Mumbai
24 Feb 2023
24 Aug 2022
26 Sept 2022
24 Aug 2022
21 Sept 2022
14 Sept 2022
24 Aug 2022 - 7 Sept 2022
9 Sept 2022
Amount
Cat (A) - Items to be supply and installation (M.V.PANELS)
Design, Supply, Installation, Testing & Commissioning of IP42 Cubical MV Panel in existing panel room as per Technical specification and in co-ordination with Engineer-in-charge. All MCCB should be of 3 Pole with Neutral link, Spreader Terminal, Phase barrier & Extended Rotary handle. a) 400 A MCCB 36 KA - 1 No. (As Incomer) b) 100 A MCCB 25 KA - 12 Nos. (Outgoing feeder)
Rerouting & Terminating In/Out cables in to new panel by taking shutdown in a shortest period. Relaying & End jointing of copper / aluminum conductor XLPE armoured cable by crimping method complete with supply of all joints materials like copper / aluminium lugs confirming to standard suitable for following cable size and connected to switchgear terminals with brass / cadmium plated nut bolts in approved manner, brass cable glands of suitable sizes, earthing connection etc., specified and required. a) 3.5 C x 185 sq.mm Al cable (2 Nos.) b) 3.5C x 95 sq.mm Al cable (10 Nos.)
Design, Supply, Installation, Testing & Commissioning of IP42 Cubical MV Panel in existing panel room as per Technical specification and in co-ordination with Engineer-in-charge. All MCCB should be of 3 Pole with Neutral link, Spreader Terminal, Phase barrier & Extended Rotary handle. a) 200 A MCCB 36 KA - 1 No. (As Incomer) b) 63 A MCCB 25 KA - 12 Nos. (Outgoing feeder)
Rerouting & Terminating In/Out cables in to new panel by taking shutdown in a shortest period. Relaying & End jointing of copper / aluminum conductor XLPE armoured cable by crimping method complete with supply of all joints materials like copper / aluminium lugs confirming to standard suitable for following cable size and connected to switchgear terminals with brass / cadmium plated nut bolts in approved manner, brass cable glands of suitable sizes, earthing connection etc., specified and required. a) 3.5 C x 185 - 300 sq.mm Al cable (1 Nos.) b) 3.5 C x 10 - 120 sq.mm Al cable (8 Nos.) c) 4C x 4 - 16 sq.mm Cu cable (8 Nos.)
Design, Supply, Installation, Testing & Commissioning of IP42 Cubical MV Panel in existing panel room as per Technical specification and in co-ordination with Engineer-in-charge. All MCCB should be of 3 Pole with Neutral link, Spreader Terminal, Phase barrier & Extended Rotary handle. a) 200 A MCCB 36 KA - 1 No. (As Incomer) b) 63 A MCCB 25 KA - 08 Nos. (Outgoing feeder)
Rerouting & Terminating In/Out cables in to new panel by taking shutdown in a shortest period. Relaying & End jointing of copper / aluminum conductor XLPE armoured cable by crimping method complete with supply of all joints materials like copper / aluminium lugs confirming to standard suitable for following cable size and connected to switchgear terminals with brass / cadmium plated nut bolts in approved manner, brass cable glands of suitable sizes, earthing connection etc., specified and required. a) 3.5 C x 185 - 300 sq.mm Al cable (1 Nos.) b) 3.5 C x 10 - 120 sq.mm Al cable (4 Nos.) c) 4C x 4 - 16 sq.mm Cu cable (6 Nos.)
Design, Supply, Installation, Testing & Commissioning of IP42 Cubical MV Panel in existing panel room as per Technical specification and in co-ordination with Engineer-in-charge. All MCCB should be of 3 Pole with Neutral link, Spreader Terminal, Phase barrier & Extended Rotary handle. a) 100 A MCCB 36 KA - 1 No. (As Incomer) b) 63 A MCCB 25 KA - 08 Nos. (Outgoing feeder)
Rerouting & Terminating In/Out cables in to new panel by taking shutdown in a shortest period. Relaying & End jointing of copper / aluminum conductor XLPE armoured cable by crimping method complete with supply of all joints materials like copper / aluminium lugs confirming to standard suitable for following cable size and connected to switchgear terminals with brass / cadmium plated nut bolts in approved manner, brass cable glands of suitable sizes, earthing connection etc., specified and required. a) 3.5 C x 185 - 300 sq.mm Al cable (1 Nos.) b) 3.5 C x 10 - 120 sq.mm Al cable (8 Nos.) c) 4C x 4 - 16 sq.mm Cu cable (2 Nos.)
Necessory filling as per site condition at each panel location floor crossing fire barrier of 2 hours rating duly tested as per UL1479 /ISO 834 shall be provided. Considering 3000mm X 1200mm X 200mm approx for each floor.
Cat (B) - Buy Back Items
Buy-Back (ie minus) Credit for existing panel 400A 12way (power panel at basement Annexe Block) with bus bars, all incoming & outgoing SFU’s from 63-400A and angle iron frame complete including its dismantling of existing panel 12 way (power panel at floor location of Annexe Block as shown by Engineer-in-charge) with SFU's of 63-400A, bus bars, cable, cable glands and interconnections complete with angle iron frame and making the site clear by making surface good and as per the instruction of Engineer-in-charge.
Buy-Back (ie minus) Credit for existing panel 200A 12way (power panel at different floor locations of Annexe Block) with bus bars, all incoming & outgoing SFU’s from 63-200A and angle iron frame complete including its dismantling of existing panel 12 way (power panel at floor location of Annexe Block as shown by Engineer-in-charge) with SFU's of 63-200A, bus bars, cable, cable glands and interconnections complete with angle iron frame and making the site clear by making surface good and as per the instruction of Engineer-in-charge.
Buy-Back (ie minus) Credit for existing panel 200A 8way (power panel at different floor locations of Annexe Block) with bus bars, all incoming & outgoing SFU’s from 63-200A and angle iron frame complete including its dismantling of existing panel 8 way (power panel at floor location of Annexe Block as shown by Engineer-in-charge) with SFU's of 63-200A, bus bars, cable, cable glands and interconnections complete with angle iron frame and making the site clear by making surface good and as per the instruction of Engineer-in-charge.
Buy-Back (ie minus) Credit for existing panel 200A 8way (power panel at different floor locations of Annexe Block) with bus bars, all incoming & outgoing SFU’s from 63-200A and angle iron frame complete including its dismantling of existing panel 8 way (power panel at floor location of Annexe Block as shown by Engineer-in-charge) with SFU's of 63-200A, bus bars, cable, cable glands and interconnections complete with angle iron frame and making the site clear by making surface good and as per the instruction of Engineer-in-charge.
Power Automation and Controls
JAMES ELECTRICALS PRIVATE LIMITED
JYOTI ELECTRO SYSTEMS PVT LTD
FRIENDS ELECTRICALS
Jaydeep Agency Corporation
Ramesh Electrical and Mechanical Works
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .