| 1 | L1₹1.1 CrAccepted-AOC 24 824 GOVERDHAN COLONY MAIN BHIND ROAD GOLE KA MANDIR | ₹1.1 Cr | L1 | Accepted-AOC Being L1 |
| 2 | L2₹1.2 Cr+₹9.1 L (7.99%)Rejected-Finance | ₹1.2 Cr+₹9.1 L (7.99%) | L2 | Rejected-Finance Being other than L1 |
| 3 | L3₹1.2 Cr+₹9.4 L (8.19%)Rejected-Finance 67 KAILASH VIHAR TIWARIPUR BAGIA JAJMAU KANPUR 208010 | KANPUR | KANPUR NAGAR | UTTAR PRADESH | 208010 | ₹1.2 Cr+₹9.4 L (8.19%) | L3 | Rejected-Finance Being other than L1 |
| 4 | L4₹1.3 Cr+₹18.3 L (16.0%)Rejected-Finance | ₹1.3 Cr+₹18.3 L (16.0%) | L4 | Rejected-Finance Being other than L1 |
| 5 | L5₹1.3 Cr+₹19.0 L (16.7%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | ₹1.3 Cr+₹19.0 L (16.7%) | L5 | Rejected-Finance Being other than L1 |
| Sl No | Description | Qty | Unit | anand enterprises L1 | M/s R.V. Constructions L8 | M/s Sohanil Construction L2 | KB PROJECTS L4 | Rama Electricals L7 | Ashirwad Contractor and Supplier L3 | Bharat Sales Corporation L6 | R D Bansal L5 | M.S CONSTRUCTIONS L9 | Vijaypower Generators Limited L10 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches not exceeding 1.5 m wide and n.exc. 1.5 m deep for foundation of poles/stay/cable etc including getting out in soft/loose soil complete all as specified and directed by Engr-in-Charge. | 3,200 | CUM | 140 ₹4,48,000 | 127 ₹4,06,400 | 125 ₹4,00,000 | 100 ₹3,20,000 Lowest | 200 ₹6,40,000 | 100 ₹3,20,000 Lowest | 140 ₹4,48,000 | 139 ₹4,44,800 | 110 ₹3,52,000 | 300 ₹9,60,000 |
| 2.00 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeking 25 cm in hard and dence soil. | 1,800 | CUM | 50 ₹90,000 | 46 ₹82,800 | 35 ₹63,000 | 28 ₹50,400 | 60 ₹1,08,000 | 55 ₹99,000 | 80 ₹1,44,000 | 30 ₹54,000 | 35 ₹63,000 | 21 ₹37,800 Lowest |
| 3.00 | Removing excavated material n.exc. 50m and depositing where directed at a level n.exc. 1.5 m above the starting point. | 1,400 | CUM | 40 ₹56,000 | 64 ₹89,600 | 45 ₹63,000 | 28 ₹39,200 | 60 ₹84,000 | 55 ₹77,000 | 40 ₹56,000 | 40 ₹56,000 | 35 ₹49,000 | 21 ₹29,400 Lowest |
| 4.00 | Supply and filling fine ganga sand to the full width of trench for cushioning of cable for cable protection including spreading and punning down complete all as specified and directed | 105 | CUM | 250 ₹26,250 | 820 ₹86,100 | 165 ₹17,325 Lowest | 1,000 ₹1,05,000 | 1,800 ₹1,89,000 | 650 ₹68,250 | 400 ₹42,000 | 900 ₹94,500 | 800 ₹84,000 | 900 ₹94,500 |
| 5.00 | M&L for all burnt old size bricks, sub class B brick laid dry flat with width equal to length of whole brick, as cable protection complete all as specified and directed. | 11.3 | 1000 Per Nos | 5,000 ₹56,500 | 4,600 ₹51,980 | 1,105 ₹12,486.5 Lowest | 8,200 ₹92,660 | 11,000 ₹1,24,300 | 3,500 ₹39,550 | 5,000 ₹56,500 | 6,000 ₹67,800 | 6,500 ₹73,450 | 6,600 ₹74,580 |
| 6.00 | Plain cement concrete 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete complete all as specified and directed. | 5 | CUM | 3,000 ₹15,000 | 4,600 ₹23,000 | 2,995 ₹14,975 Lowest | 6,040 ₹30,200 | 3,500 ₹17,500 | 3,200 ₹16,000 | 3,500 ₹17,500 | 6,000 ₹30,000 | 4,500 ₹22,500 | 8,400 ₹42,000 |
| 7.00 | Plain cement concrete (1: 2:4) type B-1 (using 20mm graded crushed stone aggregates ) as in stay filling or pole coping etc including necessary form work for rough finished surfaces complete all specified and directed. | 5 | Cum | 3,500 ₹17,500 | 5,230 ₹26,150 | 2,995 ₹14,975 Lowest | 6,400 ₹32,000 | 3,500 ₹17,500 | 3,200 ₹16,000 | 4,800 ₹24,000 | 8,500 ₹42,500 | 4,900 ₹24,500 | 9,000 ₹45,000 |
| 8.00 | M&L for double walled corrugated DWC HDPE pipe of outer dia 50mm and inner dia 38mm including 90 degree bends with coupler and rubber ring laid in trenches of size 50mm suitable for cable protection of size 2 core 10 sqmm to 3.5 core 50sqmm cable complete all as specified and directed. | 11,500 | RM | 52 ₹5,98,000 | 46 ₹5,29,000 | 45 ₹5,17,500 | 46 ₹5,29,000 | 58 ₹6,67,000 | 38 ₹4,37,000 Lowest | 49 ₹5,63,500 | 58 ₹6,67,000 | 78 ₹8,97,000 | 84 ₹9,66,000 |
| 9.00 | M&L for double walled corrugated DWC HDPE pipe of outer dia 90mm and inner dia 75mm including 90 degree bends with coupler and rubber ring laid in trenches of size 90mm suitable for cable protection of size 70sqmm to 95 cable complete all as specified and directed. | 900 | RM | 120 ₹1,08,000 | 91 ₹81,900 Lowest | 95 ₹85,500 | 136 ₹1,22,400 | 140 ₹1,26,000 | 99 ₹89,100 | 118 ₹1,06,200 | 139 ₹1,25,100 | 135 ₹1,21,500 | 165 ₹1,48,500 |
| 10.00 | S&F in replacement of GI tubing light grade 50mm dia with all fittings laid in trenches/fixed on wall/ceiling including dismantling of old pipe etc all as specified and directed. | 120 | RM | 200 ₹24,000 | 400 ₹48,000 | 195 ₹23,400 Lowest | 856 ₹1,02,720 | 450 ₹54,000 | 400 ₹48,000 | 200 ₹24,000 | 292 ₹35,040 | 415 ₹49,800 | 576 ₹69,120 |
Tender Value
₹1.5 Cr
EMD Value
₹2.2 L
Closing Date
20 Dec 2025, 6:00 pmClosed
Col Manav Pant, CWE
HQ CWE (AF) Chakeri, Kanpur
AUGMENTATION IMPROVEMENT TO ELECTRIC SUPPLY NETWORK AT AFS KANPUR
2025_MES_740935_1
CWE(AF)/CHK/EM/T-20 OF 2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE(AF) E/M CHAKERI
Please refer tender documents
8 documents required · 8 mandatory
₹1,000
GE (AF) E/M Chakeri
₹2.2 L
10 Mar 2026
21 Nov 2025
27 Dec 2025
21 Nov 2025
20 Dec 2025
13 Dec 2025
Amount
Excavation in trenches not exceeding 1.5 m wide and n.exc. 1.5 m deep for foundation of poles/stay/cable etc including getting out in soft/loose soil complete all as specified and directed by Engr-in-Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeking 25 cm in hard and dence soil.
Removing excavated material n.exc. 50m and depositing where directed at a level n.exc. 1.5 m above the starting point.
Supply and filling fine ganga sand to the full width of trench for cushioning of cable for cable protection including spreading and punning down complete all as specified and directed
M&L for all burnt old size bricks, sub class B brick laid dry flat with width equal to length of whole brick, as cable protection complete all as specified and directed.
Plain cement concrete 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete complete all as specified and directed.
Plain cement concrete (1: 2:4) type B-1 (using 20mm graded crushed stone aggregates ) as in stay filling or pole coping etc including necessary form work for rough finished surfaces complete all specified and directed.
M&L for double walled corrugated DWC HDPE pipe of outer dia 50mm and inner dia 38mm including 90 degree bends with coupler and rubber ring laid in trenches of size 50mm suitable for cable protection of size 2 core 10 sqmm to 3.5 core 50sqmm cable complete all as specified and directed.
M&L for double walled corrugated DWC HDPE pipe of outer dia 90mm and inner dia 75mm including 90 degree bends with coupler and rubber ring laid in trenches of size 90mm suitable for cable protection of size 70sqmm to 95 cable complete all as specified and directed.
S&F in replacement of GI tubing light grade 50mm dia with all fittings laid in trenches/fixed on wall/ceiling including dismantling of old pipe etc all as specified and directed.
S&F in replacement of GI tubing light grade 80mm dia with all fittings laid in trenches/fixed on wall/ceiling including dismantling of old pipe etc all as specified and directed.
S&F in replacement of GI tubing light grade 100mm dia with all fittings laid in trenches/fixed on wall/ceiling including dismantling of old pipe etc all as specified and directed.
Supply , laying and testing and commissioning of cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded Aluminium conductor of size 10 sqmm 4 core. laid in trench/ duct / along pole/wall etc including suitable size lugs, glands,Nut, bolts, washers & insulation tape etc making connection complete etc all as specified directed. Note : The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply , laying and testing commissioning of cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded Aluminium conductor of size 16 sqmm 4 core. laid in trench/ duct / along pole/wall etc including suitable size lugs, glands,Nut, bolts, washers & insulation tape etc making connection complete etc all as specified directed. Note : The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply , laying and testing commissioning of cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded Aluminium conductor of size 25 sqmm 4 core. laid in trench/ duct / along pole/wall etc including suitable size lugs, glands,Nut, bolts, washers & insulation tape etc making connection complete etc all as specified directed. Note : The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply , laying and testing commissioning of cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded Aluminium conductor of size 35 sqmm 3.5 core. laid in trench/ duct / along pole/wall etc including suitable size lugs, glands,Nut, bolts, washers & insulation tape etc making connection complete etc all as specified directed. Note : The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply , laying and testing commissioning of cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded Aluminium conductor of size 50 sqmm 3.5 core. laid in trench/ duct / along pole/wall etc including suitable size lugs, glands,Nut, bolts, washers & insulation tape etc making connection complete etc all as specified directed. Note : The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply , laying and testing commissioning of cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded Aluminium conductor of size 70 sqmm 3.5 core. laid in trench/ duct / along pole/wall etc including suitable size lugs, glands,Nut, bolts, washers & insulation tape etc making connection complete etc all as specified directed. Note : The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply , laying and testing commissioning of cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded Aluminium conductor of size 95 sqmm 3.5 core. laid in trench/ duct / along pole/wall etc including suitable size lugs, glands,Nut, bolts, washers & insulation tape etc making connection complete etc all as specified directed. Note : The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply , laying and testing commissioning of cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded Aluminium conductor of size 120 sqmm 3.5 core. laid in trench/ duct / along pole/wall etc including suitable size lugs, glands,Nut, bolts, washers & insulation tape etc making connection complete etc all as specified directed. Note : The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply , laying and testing commissioning of cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded Aluminium conductor of size 150 sqmm 3.5 core. laid in trench/ duct / along pole/wall etc including suitable size lugs, glands,Nut, bolts, washers & insulation tape etc making connection complete etc all as specified directed. Note : The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply , laying and testing commissioning of cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded Aluminium conductor of size 185 sqmm 3.5 core. laid in trench/ duct / along pole/wall etc including suitable size lugs, glands,Nut, bolts, washers & insulation tape etc making connection complete etc all as specified directed. Note : The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply , laying and testing commissioning of cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded Aluminium conductor of size 240 sqmm 3.5 core. laid in trench/ duct / along pole/wall etc including suitable size lugs, glands,Nut, bolts, washers & insulation tape etc making connection complete etc all as specified directed. Note : The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply , laying and testing commissioning of cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded Aluminium conductor of size 300 sqmm 4 core. laid in trench/ duct / along pole/wall etc including suitable size lugs, glands,Nut, bolts, washers & insulation tape etc making connection complete etc all as specified directed. Note : The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply , laying and testing commissioning of cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded Aluminium conductor of size 400 sqmm 4 core. laid in trench/ duct / along pole/wall etc including suitable size lugs, glands,Nut, bolts, washers & insulation tape etc making connection complete etc all as specified directed. Note : The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply and fixing insulated unsheathed PVC FRLS three core stranded copper conductor 1.5 sqmm x 2 + 1.5 sqmm for earth contuinity conductor drwan through steel conduit pipe of medium grade fixed to pole with fixing arrangement woking voltage 1100 volts grade 50HZ cconforming to IS-694 from junction box to street light fitting or for OH connections complete all as specified and directed. (Note : 7 Rm per pole )
S&F of pole box for street light dust and vermin proof make Sintex model GSJB 3020 complete with aluminum bus bar 04 nos. of capacity 100 amps on epoxy insulators including one MCB SP C series 06 amps 10 KA capacity for security light connection including suitable clamps & suitable size brass chrome plated glands-02 nos at bottom for cable entry and exit complete all as specified and directed. Note:- All cable connections shall be made with using suitable cable lugs.
Supply, installation, comissioning and testing in of out door type LT panel of approved make, CPRI approved, make, fabricated out of 3.15mm thick CRCA steel sheet powder coated, double door with and incl MS angle iron (40x40x6mm) base frame, cubical type mounted, dust and vermin proof, both side open and locking arrangement, danger board plate,Cable gand, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit,chamber for aluminium bus bars including aluminium busbars 4 Nos,2000 Amp on phase & neutral, 415 volts, properly insulated aluminium bus bar capacity insulated with colored PVC sleeves mounted on suitable insulators and separators, holes drilled for connections including panel shall be mounted on brick work plate form of size 250x400x600mm in two number duly plasterd and PCC coping work on top surface height shall be 60cm above the GL and 0.40 mtr all aroung the FPB complete all as specified and comprising of the followings:- INCOMING :-(a) ACB with intelligent release micropro2-3.1, 4 Pole, 415 V, Mannual drawout type ,1250Amps with breaking capacity 50 KA - 01 No OUTGOING :- (b) ACB with intelligent release micropro2-3.1, 4 Pole, 415 V, Mannual drawout type ,1000Amps with breaking capacity 50 KA - 01(c) MCCB 4 Pole, 415 V, adjustable thermal setting 100 Amps with breaking capacity 18 KA - 02No. (d) MCCB 4 Pole, 415 V, adjustable thermal setting 40Amps with breaking capacity 10 KA - 01No (e) MCCB 4 Pole, 415 V, adjustable thermal setting 60 Amps with breaking capacity 18 KA - 01 No (f) MCCB 4 Pole, 415 V, adjustable thermal setting 630 Amps with breaking capacity 36/37 KA - 01 No (g) Voltmeter, electronic, digital type,upto rating 0 - 500 volts, AC, 50 Hz - 1 No. (h) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (j) Current transformer 1250 / 5 amps rating, AC, 50 Hz - 3 Nos. (k) Phase indication LED lamps with toggle switch- 3 Nos (RYB). Note : Ics = 100% Icu for all MCCB, Location: Near N-4 old Substaion Make of MCCB: Legrand/Havells/ABB
Supply, installation, comissioning and testing of out door type LT panel of approved make, CPRI approved, make, fabricated out of 3.15mm thick CRCA steel sheet powder coated, double door with and incl MS angle iron (40x40x6mm) base frame, cubical type mounted, dust and vermin proof, both side open and locking arrangement, danger board plate,Cable gand, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit,chamber for aluminium bus bars including aluminium busbars 4 Nos,1500 Amp on phase & neutral, 415 volts, properly insulated aluminium bus bar capacity insulated with colored PVC sleeves mounted on suitable insulators and separators, holes drilled for connections including panel shall be mounted on brick work plate form of size 250x400x600mm in two nmber duly plasterd and PCC coping work on top surface height shall be 60cm above the GL and 0.40 mtr all aroung the FPB complete all as specified and comprising of the followings:- INCOMING :-(a) ACB with intelligent release micropro2-3.1, 4 Pole, 415 V, Mannual drawout type ,1000Amps with breaking capacity 50 KA - 01 OUTGOING :- (b) MCCB 4 Pole, 415 V, adjustable thermal setting 300 Amps with breaking capacity 36/37 KA - 01 No. (c) MCCB 4 Pole, 415 V, adjustable thermal setting 500 Amps with breaking capacity 36/37 KA - 02 No. (d) MCCB 4 Pole, 415 V, adjustable thermal setting 63 Amps with breaking capacity 10 KA - 02 No (e) MCCB 4 Pole, 415 V, adjustable thermal setting 160 Amps with breaking capacity 25 KA - 01 No (f) MCCB 4 Pole, 415 V, adjustable thermal setting 125 Amps with breaking capacity 25 KA - 01 No (g) Voltmeter, electronic, digital type,upto rating 0 - 500 volts, AC, 50 Hz - 1 No (h) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (j) Current transformer 1000 / 5 amps rating, AC, 50 Hz - 3 Nos. (k) Phase indication LED lamps with toggle switch - 3 Nos (RYB). Note : Ics = 100% Icu for all MCCB . Location : Near T 132 Block Make of MCCB : Legrand/ ABB/ Havells
Supply, installation, comissioning and testing of out door type LT panel of approved make, CPRI approved, make, fabricated out of 3.15mm thick CRCA steel sheet powder coated, double door with and incl MS angle iron (40x40x6mm) base frame, cubical type mounted, dust and vermin proof, both side open and locking arrangement, danger board plate,Cable gand, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit,chamber for aluminium bus bars including aluminium busbars 4 Nos,600 Amp on phase & neutral, 415 volts, properly insulated aluminium bus bar capacity insulated with colored PVC sleeves mounted on suitable insulators and separators, holes drilled for connections including panel shall be mounted on brick work plate formm of size 250x400x600mm in two nmber duly plasterd and PCC coping work om top surface height shall be 60cm above the GL and 0.40 mtr all aroung the FPB complete all as specified and comprising of the followings:- INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting ,400 Amps with breaking capacity 36/37 KA - 01 No OUTGOING :- (b) MCCB 4 Pole, 415 V, adjustable thermal setting 200 Amps with breaking capacity 25 KA - 02 No. (c) MCCB 4 Pole, 415 V, adjustable thermal setting 125 Amps with breaking capacity 25 KA - 02 No. (d) Voltmeter, electronic, digital type, upto rating 0 - 500 volts, AC, 50 Hz - 1 No (e) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (f) Current transformer 400 / 5 amps rating, AC, 50 Hz - 3 Nos. (g) Phase indication LED lamps with toggle switch - 3 Nos (RYB). Note : Ics = 100% Icu for all MCCB, Location: Near T-86 Block, Make of MCCB : Legrand /ABB/ Havells/C&S
Supply, installation, comissioning and testing of out door type LT panel of approved make, CPRI approved, make, fabricated out of 3.15mm thick CRCA steel sheet powder coated, double door with and incl MS angle iron (40x40x6mm) base frame, cubical type mounted, dust and vermin proof, both side open and locking arrangement, danger board plate,Cable gand, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit,chamber for aluminium bus bars including aluminium busbars 4 Nos,600 Amp on phase & neutral, 415 volts, properly insulated aluminium bus bar capacity insulated with colored PVC sleeves mounted on suitable insulators and separators, holes drilled for connections including panel shall be mounted on brick work plate from of size 250x400x600mm in two nmber duly plasterd and PCC coping work om top surface height shall be 60 cmabove the GL and 0.40 mtr all aroung the FPB complete all as specified and comprising of the followings:- INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting ,400 Amps with breaking capacity 36/37 KA - 01 No OUTGOING :- (b) MCCB 4 Pole, 415 V, adjustable thermal setting 250 Amps with breaking capacity 25 KA - 02 No. (c) MCCB 4 Pole, 415 V, adjustable thermal setting 150 Amps with breaking capacity 18 KA - 01 (d) Voltmeter, electronic, digital type,upto rating 0 - 500 volts, AC, 50 Hz - 1 No (e) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (f) Current transformer 400 / 5 amps rating, AC, 50 Hz - 3 Nos. (g) Phase indication LED lamps with toggle switch - 3 Nos (RYB). Note : Ics = 100% Icu for all MCCB. Location : Near T-100 block, Make of MCCB:- Legrand/Havells/ABB/C&S
Supply, installation, comissioning and teasting of out door type LT panel of approved make, CPRI approved, make, fabricated out of 3.15mm thick CRCA steel sheet powder coated, double door with and incl MS angle iron (40x40x6mm) base frame, cubical type mounted, dust and vermin proof, both side open and locking arrangement, danger board plate,Cable gand, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit,chamber for aluminium bus bars including aluminium busbars 4 Nos,400 Amp on phase & neutral, 415 volts, properly insulated aluminium bus bar capacity insulated with colored PVC sleeves mounted on suitable insulators and separators, holes drilled for connections including panel shall be mounted on brick work plate form of size 250x400x600mm in two nmber duly plasterd and PCC coping work om top surface height shall be 60cm above the GL and 0.40 mtr all aroung the FPB complete all as specified and comprising of the followings:- INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting ,250 Amps with breaking capacity 35/36 KA - 01 No OUTGOING :- (b) MCCB 4 Pole, 415 V, adjustable thermal setting 150 Amps with breaking capacity 18 KA - 02 No. (c) MCCB 4 Pole, 415 V, adjustable thermal setting 100 Amps with breaking capacity 18 KA - 01 No. (d) Voltmeter, electronic, digital type, upto rating 0 - 500 volts, AC, 50 Hz - 1 No (e) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (f) Current transformer 250 / 5 amps rating, AC, 50 Hz - 3 Nos. (g) Phase indication LED lamps with toggle switch- 3 Nos (RYB). Note : Ics = 100% Icu for all MCCB. Location:- Near T-112 Block, Make of MCCB:- Legrand/Havells/C&S/ABB
Supply, installation, comissioning and testing in replacement of out door type LT panel of approved make, CPRI approved, make, fabricated out of 3.15mm thick CRCA steel sheet powder coated, double door with and incl MS angle iron (40x40x6mm) base frame, cubical type mounted, dust and vermin proof, both side open and locking arrangement, danger board plate,Cable gand, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit,chamber for aluminium bus bars including aluminium busbars 4 Nos,200 Amp on phase & neutral, 415 volts, properly insulated aluminium bus bar capacity insulated with colored PVC sleeves mounted on suitable insulators and separators, holes drilled for connections including panel shall be mounted on brick work plate form of size 250x400x600mm in two nmber duly plasterd and PCC coping work om top surface height shall be 60cm above the GL and 0.40 mtr all aroung the FPB complete all as specified and comprising of the followings:- INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting ,125 Amps with breaking capacity 25 KA - 01 No OUTGOING :- (b) MCCB 4 Pole, 415 V, adjustable thermal setting 63 Amps with breaking capacity 10 KA - 03 No. (c) Voltmeter, electronic, digital type, upto rating 0 - 500 volts, AC, 50 Hz - 1 No (d) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (e) Current transformer 125 / 5 amps rating, AC, 50 Hz - 3 Nos. (f) Phase indication LED lamps with toggle switch - 3 Nos (RYB). Note : Ics = 100% Icu for all MCCB. Make of MCCB :- Legrand/Havells/C&S/ABB, Location :- Near T-96 bolck, Near T-127 bolck, Near T-110 block & Near T-108 bolck
Supply, installation, comissioning and testing in replacement of out door type LT panel of approved make, CPRI approved, make, fabricated out of 3.15mm thick CRCA steel sheet powder coated, double door with and incl MS angle iron (40x40x6mm) base frame, cubical type mounted, dust and vermin proof, both side open and locking arrangement, danger board plate,Cable gand, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit,chamber for aluminium bus bars including aluminium busbars 4 Nos,150 Amp on phase & neutral, 415 volts, properly insulated aluminium bus bar capacity insulated with colored PVC sleeves mounted on suitable insulators and separators, holes drilled for connections including panel shall be mounted on brick work plate form of size 250x400x600mm in two number duly plasterd and PCC coping work om top surface height shall be 60cm above the GL and 0.40 mtr all aroung the FPB complete all as specified and comprising of the followings:- INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting ,100 Amps with breaking capacity 16/18A - 01 No OUTGOING :- (b) MCCB 4 Pole, 415 V, adjustable thermal setting ,63 Amps with breaking capacity 10 KA - 02 No . (c) MCCB 4 Pole, 415 V, adjustable thermal setting ,40 Amps with breaking capacity 10 KA - 01 No (d) Voltmeter, electronic, digital type, upto rating 0 - 500 volts, AC, 50 Hz - 1 No (e) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (f) Current transformer 100 / 5 amps rating, AC, 50 Hz - 3 Nos. (g) Phase indication LED lamps with toggle switch- 3 Nos (RYB). Note : Ics = 100% Icu for all MCCB. Make of MCCB :- Legrand/Havells/C&S/ABB, Location :- NearT-82 bolck, Near T-87 bolck
Supply, installation, comissioning and testing in replacement of out door type LT panel of approved make, CPRI approved, make, fabricated out of 3.15mm thick CRCA steel sheet powder coated, double door with and incl MS angle iron (40x40x6mm) base frame, cubical type mounted, dust and vermin proof, both side open and locking arrangement, danger board plate,Cable gand, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit,chamber for aluminium bus bars including aluminium busbars 4 Nos,300 Amp on phase & neutral, 415 volts, properly insulated aluminium bus bar capacity insulated with colored PVC sleeves mounted on suitable insulators and separators, holes drilled for connections including panel shall be mounted on brick work plate form of size 250x400x600mm in two number duly plasterd and PCC coping work om top surface height shall be 60cm above the GL and 0.40 mtr all aroung the FPB complete all as specified and comprising of the followings:- INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting ,200 Amps with breaking capacity 25 KA - 01 No OUTGOING :- (b) MCCB 4 Pole, 415 V, adjustable thermal setting ,63 Amps with breaking capacity 10 KA - 05 No (c) Voltmeter, electronic, digital type,upto rating 0 - 500 volts, AC, 50 Hz - 1 No (d) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (e) Current transformer 200 / 5 amps rating, AC, 50 Hz - 3 Nos. (f) Phase indication LED lamps with toggle switch - 3 Nos (RYB). Note : Ics = 100% Icu for all MCCB. Make of MCCB :- Legrand/Havells/C&S/ABB, Location :- Near T-100 Block, Near T-97 Block
Supply, installation, comissioning and testing of out door type LT panel of approved make, CPRI approved, make, fabricated out of 3.15mm thick CRCA steel sheet powder coated, double door with and incl MS angle iron (40x40x6mm) base frame, cubical type mounted, dust and vermin proof, both side open and locking arrangement, danger board plate,Cable gand, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit,chamber for aluminium bus bars including aluminium busbars 4 Nos,240 Amp on phase & neutral, 415 volts, properly insulated aluminium bus bar capacity insulated with colored PVC sleeves mounted on suitable insulators and separators, holes drilled for connections including panel shall be mounted on brick work plate form of size 250x400x600mm in two number duly plasterd and PCC coping work om top surface height shall be 60cm above the GL and 0.40 mtr all aroung the FPB complete all as specified and comprising of the followings:- INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting ,160 Amps with breaking capacity 25 KA - 01 No OUTGOING :- (b) MCCB 4 Pole, 415 V, adjustable thermal setting 63 Amps with breaking capacity 10 KA - 04 No. (c) Voltmeter, electronic, digital type upto rating 0 - 500 volts, AC, 50 Hz - 1 No (d) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (e) Current transformer 160 / 5 amps rating, AC, 50 Hz - 3 Nos. (f) Phase indication LED lamps with toggle switch- 3 Nos (RYB). Note : Ics = 100% Icu for all MCCB. Make of MCCB :- Legrand/Havells/C&S/ABB, Location :- Near T-85 block, Near T-83 Block & Near T-126 Block
Supply, installation, comissioning and testing of out door type LT panel of approved make, CPRI approved, make, fabricated out of 3.15mm thick CRCA steel sheet powder coated, double door with and incl MS angle iron (40x40x6mm) base frame, cubical type mounted, dust and vermin proof, both side open and locking arrangement, danger board plate,Cable gand, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit,chamber for aluminium bus bars including aluminium busbars 4 Nos, 1000 Amp on phase & neutral, 415 volts, properly insulated aluminium bus bar capacity insulated with colored PVC sleeves mounted on suitable insulators and separators, holes drilled for connections including panel shall be mounted on brick work plate form of size 250x400x600mm in two number duly plasterd and PCC coping work om top surface height shall be 0.6. mtr above the GL and 0.40 mtr all aroung the FPB complete all as specified and comprising of the followings:- INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting ,630 Amps with breaking capacity 65 KA - 01 No OUTGOING :- (b) MCCB 4 Pole, 415 V, adjustable thermal setting 63 Amps with breaking capacity 10KA - 01 No. (c) MCCB 4 Pole, 415 V, adjustable thermal setting 250 Amps with breaking capacity 35/36 KA - 01 No (d) MCCB 4 Pole, 415 V, adjustable thermal setting 100 Amps with breaking capacity 18KA - 01 No (e) MCCB 4 Pole, 415 V, adjustable thermal setting 500 Amps with breaking capacity 36/37 KA - 01 No. ( f) Voltmeter, electronic, digital type, upto rating 0 - 500 volts, AC, 50 Hz - 1 No (g) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (h) Current transformer 630 / 5 amps rating, AC, 50 Hz - 3 Nos. (j) Phase indication LED lamps with toggle switch- 3 Nos (RYB). Note : Ics = 100% Icu for all MCCB. Make of MCCB :- Legrand/Havells/C&S/ABB, Location :- Near KV-3 school
Supply, installation, comissioning and testing of out door type LT panel of approved make, CPRI approved, make, fabricated out of 3.15mm thick CRCA steel sheet powder coated, double door with and incl MS angle iron (40x40x6mm) base frame, cubical type mounted, dust and vermin proof, both side open and locking arrangement, danger board plate,Cable gand, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit,chamber for aluminium bus bars including aluminium busbars 4 Nos,600 Amp on phase & neutral, 415 volts, properly insulated aluminium bus bar capacity insulated with colored PVC sleeves mounted on suitable insulators and separators, holes drilled for connections including panel shall be mounted on brick work plate from of size 250x400x600mm in two number duly plasterd and PCC coping work om top surface height shall be 60cm above the GL and 0.40 mtr all aroung the FPB complete all as specified and comprising of the followings:- INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting ,400 Amps with breaking capacity 36/37 KA - 01 No OUTGOING :- (b) MCCB 4 Pole, 415 V, adjustable thermal setting 63 Amps with breaking capacity 10KA - 04 No. (c) MCCB 4 Pole, 415 V, adjustable thermal setting 350 Amps with breaking capacity 25KA - 01 No. - 01 No ( d) Voltmeter, electronic, digital type,upto rating 0 - 500 volts, AC, 50 Hz - 1 No (e) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (f) Current transformer 400 / 5 amps rating, AC, 50 Hz - 3 Nos. (g) Phase indication LED lamps with toggle switch - 3 Nos (RYB). Note : Ics = 100% Icu for all MCCB. Make of MCCB :- Legrand/Havells/C&S/ABB, Location : - Near T-193 block
Supply, installation, comissioning and testing of out door type LT panel of approved make, CPRI approved, make, fabricated out of 3.15mm thick CRCA steel sheet powder coated, double door with and incl MS angle iron (40x40x6mm) base frame, cubical type mounted, dust and vermin proof, both side open and locking arrangement, danger board plate,Cable gand, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit,chamber for aluminium bus bars including aluminium busbars 4 Nos,240 Amp on phase & neutral, 415 volts, properly insulated aluminium bus bar capacity insulated with colored PVC sleeves mounted on suitable insulators and separators, holes drilled for connections including panel shall be mounted on brick work plate form of size 250x400x600mm in two number duly plasterd and PCC coping work om top surface height shall be 60 cm above the GL and 0.40 mtr all aroung the FPB complete all as specified and comprising of the followings:- INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting ,160 Amps with breaking capacity 25 KA - 01 No OUTGOING :- (b) MCCB 4 Pole, 415 V, adjustable thermal setting 63 Amps with breaking capacity 10KA - 04 No. (c) MCCB 4 Pole, 415 V, adjustable thermal setting 40 Amps with breaking capacity 10 KA - 01 No ( d) Voltmeter, electronic, digital type upto rating 0 - 500 volts, AC, 50 Hz - 1 No (e) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (f) Current transformer 160 / 5 amps rating, AC, 50 Hz - 3 Nos. (g) Phase indication LED lamps with toggle switch - 3 Nos (RYB). Note : Ics = 100% Icu for all MCCB. Make of MCCB :- Legrand/Havells/C&S/ABB, Location:- Near MES block
Supply, installation, comissioning and testing out door type LT panel of approved make, CPRI approved, make, fabricated out of 3.15mm thick CRCA steel sheet powder coated, double door with and incl MS angle iron (40x40x6mm) base frame, cubical type mounted, dust and vermin proof, both side open and locking arrangement, danger board plate,Cable gand, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit,chamber for aluminium bus bars including aluminium busbars 4 Nos,400 Amp on phase & neutral, 415 volts, properly insulated aluminium bus bar capacity insulated with colored PVC sleeves mounted on suitable insulators and separators, holes drilled for connections including panel shall be mounted on brick work plate from of size 250x400x600mm in two number duly plasterd and PCC coping work om top surface height shall be .6. mtr above the GL and 0.40 mtr all aroung the FPB complete all as specified and comprising of the followings:- INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting 320 Amps with breaking capacity 36 KA - 01 No OUTGOING :- (b) MCCB 4 Pole, 415 V, adjustable thermal setting 63 Amps with breaking capacity 10KA - 05 No. (c) MCCB 4 Pole, 415 V, adjustable thermal setting 200 Amps with breaking capacity 25 KA - 01 No (d) Voltmeter, electronic, digital type upto rating 0 - 500 volts, AC, 50 Hz - 1 No (e) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (f) Current transformer 320 / 5 amps rating, AC, 50 Hz - 3 Nos. (g) Phase indication LED lamps with toggle switch - 3 Nos (RYB). Note : Ics = 100% Icu for all MCCB. Make of MCCB :- Legrand/Havells/C&S/ABB, Location :- Near T-194 block
Supply, installation, commissioning and testing of LT feeder piller box outdoor type, made out of 3.15mm thick CRCA sheet metal, double door type and sitable MS angle iron base frame, cubical type floor mounted 3 phase 4 wire, 415V properly insulated aluminium bus bar-04 Nos having capacity 400 Amps on phase and neutral, dustand vermin proof, both side open with locking arrangement, danger board plate, duly painted internally and externally with powder coated, RYB indication lamp with Digital multifunction meter, suitable size platf built with brick work in CM (1:4) 15mm thick plastering in CM (1:6), 0.6Mtrs height from GFL, incl lugs, gland , thimble and nut bolts etc electric connection complete etc all as specified and directed by EIC . Incoming and Outgoing : (i) MCCB 250 Amps, 36/37KA , 4P, 415V - 01 No, (ii) RYB inidication lamp (iii) Digital type Volt meter and Ammeter. Note : Ics = 100% Icu for MCCB. Make of MCCB :- Legrand/Havells/C&S/ABB
Supply, installation, commissioning and testing of LT feeder piller box outdoor type, made out of 3.15mm thick CRCA sheet metal, double door type and sitable MS angle iron base frame, cubical type floor mounted 3 phase 4 wire, 415V properly insulated aluminium bus bar-04 Nos having capacity 600 Amps on phase and neutral, dustand vermin proof, both side open with locking arrangement, danger board plate, duly painted internally and externally with powder coated, RYB indication lamp with Digital multifunction meter, suitable size platf built with brick work in CM (1:4) 15mm thick plastering in CM (1:6), 0.6Mtrs height from GFL, incl lugs, gland , thimble and nut bolts etc electric connection complete etc all as specified and directed by EIC . Incoming and Outgoing : (i) MCCB 400 Amps, 36/37KA , 4P, 415V - 01 No, (ii) RYB inidication lamp (iii) Digital type Volt meter and Ammeter. Note : Ics = 100% Icu for MCCB. Make of MCCB :- Legrand/Havells/C&S/ABB
M&L for making horizantal boring 60cm deep below road crossing for passing of LT cable in suitable size GI pipe complete all as specified and directed by EIC.
Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge of the plate not less than 1.5 mtr below ground level connected to galvanised iron strip 25×4mm means of bolts, nuts check nut & washers of galvanised iron or steel & connected to main switch including complete excavation and earth work in soft/loose soil and disposal of surplus soil to a distance not exc 50 meters, PCC Chamber (1:3:6) type C-2 precast RCC cover with frame, funnel wire mesh, 20mm bore light grade galvanised iron or steel pipe for water, charcoal or coke and salt in alternative layers of 15cm compacted thickness all round the earth electrode complete alll as shown in electrical plate No 3 of SSR part-I including welding with suitble electrode and testing complete all as directed. NOTE :- (i) Main earthing strip from earth plate electrodeto test point upto length of 7.5 mtrs length shall deem to be included in the unit rate quoted against this item. (ii) M&L Tubing GI med grade 40mm dia for protection of earthing strip and passing the Road/passes and etc.shall deem to be included in the unit rate quoted against this item.
Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge of the plate not less than 1.5 mtr below ground level connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel & connected to main switch including complete excavation and earth work in soft/loose soil and disposal of surplus soil to a distance not exc 50 meters, PCC Chamber (1:3:6) type C-2 precast RCC cover with frame, funnel wire mesh, 20mm bore light grade galvanised iron or steel pipe for water, charcoal or coke and salt in alternative layers of 15cm compacted thickness all round the earth electrode complete alll as shown in electrical plate No 3 of SSR part-I including welding with suitble electrode and testing complete all as directed. NOTE :- (i) Main earthing strip from earth plate electrodeto test point upto length of 7.5 mtrs length shall deem to be included in the unit rate quoted against this item. (ii) M&L Tubing GI med grade 40mm dia for protection of earthing strip and passing the Road/passes and etc.shall deem to be included in the unit rate quoted against this item.
Dismantling of cross arm of MS Channel or angle section etc. complete
Dismantling of insulator any type and size complete etc
Dismantling of ACSR any type and size complete etc
Dismantling stay assembly complete
S & F in repair of MCCB FP 63 Amps,10KA, Ics = 100% Icu,complete all as specified and directed.
S&F in repair of double door type TPN DB 4 Way ,240V with 200A busbar , with metalic double door type IP 43 IK 09 protection suitable for housing MCCB's all as specified and directed by EIC.Make: Legrand/ Schinder/ ABB/Seimens. Note : DBs shall be concealed in wall where ever posible including making good the surface to match with surrounding complete all as specified and directed.
M/s Sohanil Construction (BID ID -3502709)
Ashirwad Contractor and Supplier (BID ID -3503340)
KB PROJECTS (BID ID -3502900)
R D Bansal (BID ID -3503658)
Bharat Sales Corporation (BID ID -3503377)
Rama Electricals (BID ID -3502941)
M/s R.V. Constructions (BID ID -3502550)
M.S CONSTRUCTIONS (BID ID -3503803)
Vijaypower Generators Limited (BID ID -3503859)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.58 MB
TENDERT20AUGMENTATION21NOV.pdf
Tender Documents • 1.40 MB
BOQ_829670.xls
BOQ • 1.19 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .