| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.5 LAccepted-AOC 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | L1 | Accepted-AOC Being the lowest bidder | |
| 2 | L2Rejected-AOC 53 VAISHAILI ENCLAVE SECTOR 9 INDIRA NAGAR LUCKNOW | LUCKNOW | L2 | Rejected-AOC Not being the lowest bidder | |
| 3 | Rejected-Technical | - | Rejected-Technical Not as per eNIT | |
| 4 | Rejected-Technical SAHU THEATRE BUILDING HAZRATGANJ LUCKNOW LUCKNOW UTTAR PRADESH 226001 | LUCKNOW | UTTAR PRADESH | 226001 | - | Rejected-Technical Not as per eNIT |
Tender Value
₹43.8 L
EMD Value
₹87,520
Closing Date
5 Sept 2018, 6:00 pmClosed
Asstt. General Manager(E-E)-II
Airports Authority of India, CCSI Airport, Lucknow
Provision of additional roof top based ductable Air Cooled Condensing Unit with AHU and associated works for the first floor SHA in Terminal-2 building at CCSI Airport Lucknow
2018_AAI_14326_1
AAI/LKO/AGM(E-E)-II/ eNIT-04/2018-19
Open Tender
Electrical Works
Item Rate
120 days
Lucknow Airport
As per eNIT
14 documents required · 14 mandatory
₹1,120
Revenue Collection (Lucknow Airport) A/C
₹87,520
20 Jan 2020
28 Aug 2018
11 Sept 2018
28 Aug 2018
5 Sept 2018
28 Aug 2018
28 Aug 2018 - 4 Sept 2018
Amount
Condensing Unit Supply of Air Cooled Condensing Unit, low Roof Load weight distribution, open chasis structure, comprising of Scroll Compressor with run time equilistion, built in time delay, continuous current monitoring module, digital setting of temperature level, Auto restart, Nominal cooling capacity-173.7kw (49.4TR), length(Approx.)-2980mm, width(Approx.)-2040mm, height(Approx.)-2492mm net weight-1800kg (Approx.), power consumption-56.6 KW(Approx.), scroll type-hermetic scroll, 100% volumetric efficiency, tube material-inner groved copper tube, tube size (od)-3/8 inch, face area 8.24 sqm, rows deep 3 nos., Cond Fan motor qty 2 nos, type-TE pad mounted, Speed 910rpm, power-1.9 KW, Class of insulation-F, Fan qty 2nos, dia-915mm(Approx.), refrigerant connection-2nos, liquid line Size-7/8 inch, suction line size-1-5/8inch, Hydrophobic blue/thermoguard coating, BMS Connectivity option. It shall be designed for the following capacity. Capacity-52.0 TR (Refrigerant R 407 C)
AHU Floor mounted Horizontal AHU's with 70 mm WG Static Pressure-DX Type Supply, Installation, Testing & commissioning of double skin air handiling unit of capacity 23400 cfm, 70 mm static, Direct Expansion Type and with suitable motor. The housing shall be constructed of 0.6 mm glavanized preplastified/powder coated sheet on outside and inside with 25+/-2 mm thick CFC free PUF foam of 40 +/-2 Kg/M3 density insulation in between panels complete with fan section with fan, provison for connection of rerurn duct, motor mounting arrangement inside the casings with motor, belt drive/ direct drive system enclosed. The unit shall have canopy, mixing chamber, anticorrosive blue hydrophallic coated cooling coil with access door & filter section with pre filters. Capacity-23400 CFM
Installation/Commissioning Installaiton, Testing and Commissioning of Condensing units with follwing activities. i)Lifting shifting of Units and out door units at respective locations. ii)Installation of indoor and out door units with necessary electrical connections, nitrogen flushing, pressure stand for 24-48 hrs and copper pipes connections as per BSL standards. iii)Vaccumising for approx. 3-4 Hrs as per specifications and guidelines for Ductable Acs. iv)Commissioning of condensing units with laid down procedures and guidelines of Manufacturer. Capacity 52.0 TR
Air Distribution Providing, Installation and Erection of pre-insulated and pre fabricated 9 mm thick nitrile rubber insulation double wall spiral Ducting (GSS-Round shape) with complete fittings on the existing truss of the ceiling .
24 Gauge
22 Gauge
Providing and fixing of Galvanised steel sheet duct, fabrication, installation, & testing of sheet metal ducts of follwing thickness including necessary supports hangers, nuts & bolts gaskets, splitters, clampers, vanes etc.
20 Gauge
22 Gauge
24 Gauge
Supply & installation of MS Volume Control Damper for supply air duct collars.
Supply & installation of GSS Volume Control Damper for supply air duct.
Supply of installation of Extruded Aluminium Powder coated supply/return air grillls without volume control dampers.
Supply & installation of flexible Canvass connection fire retardant of suitable size.
Supply & installation of high quality electromeric nitrile rubber insulation density shall not be less than 55Kg/m3 of ducts.
13 mm thick insulation (Supply air duct).
9 mm thick insulation (Return air duct).
Supply & Installation of exposed G.I. duct insulation with 50 mm thick EPS thermocol insulation, polythene to be used as water vapour barrier & its cladding will be of 26 Gauge G.I. Sheets.
MS Stand Supply & Installation of MS floor type Stand for Placement of AHU/Cond units with Vibration Pads etc
Copper Piping (Refrigerant Piping)
Providing and fixing of Copper Refrigerant Piping Thickness-19 SWG complete with fittings suction line insulated with 12 mm Superlon/Amaflex-Make Pallavi/Mandev-Size 7/8'' + 15/8
Suction line insulated with 12 mm SUPERLON/ARMAFLEX suction line.
Providing and fixing of suitable size expansion valve
Providing and fixing of suitable size liquid line valve
Providing and fixing of Suitable Catchall Drier
Providing and fixing of Elecronic Controller
Electrical Panels
Supply & installation of electrical panel for AHU's. It includes MCCB, all indicators, fuses, mccb/mcb's, contactor set, toggle switch etc.
Supply, & installation of electrical panel for Condensing Unit. It includes MCCB, all indicators, fuses, mccb/mcb's, contactor set, toggle switch etc.
Drain Pipe Supplying, laying, fixing, testing, & commissioning of GI medium class pipes complete with all necessary fittings such as elbow, reducers, etc and supports such as clamps etc. Duly insulated using 50 mm with expanded polystyrene TF quality density's 40 mm dia GI Pipe.
Cable Trays/ Cable racks/ pipe Racks.
Supply & Installation of GI Perforated Cable Tray for laying of Copper Refrigerant Piping, Control Cable & etc of size 40 X200X40 mm wide.
Supply and installation of GI Cover for the cable tray.
Electrical Power Cable Supply of LT power cable of 1.1 KV grade of following sizes aluminium conductor XLPE insulated PVC sheathed armoured cable confirming to IS 7098 Part-I-2011 with upto date ammendment as required.
3 Core X 16 sqmm
3.5 Core X 150 sqmm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on cable tray as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/ 40x3mm MS flat clamp)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/ 40x3mm MS flat clamp)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing masonry open duct as required.
Upto 35 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
Upto 35 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.
3 X 16 sq. mm (25 mm)
3½ X 150 sq. mm (50 mm)
Earthing Providing and fixing 25 mm x 5 mm GI Strip on surface or in recess for connections etc. as required.
KRISHNA REFRIGERATION
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .