Repair and renovation of Electrical Installation work at SNCU 2 and adjacent area of Chittaranjan Seva Sadan, Kolkata Rattierer Saathi Electrical Work
2024_WBPWD_766205_1
WBPWD/EE-II/KSHED/Q76/24-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
21 days
Kolkata
Please refer Tender documents.
3 documents required · 3 mandatory
₹15,280
O/o Exe. Engr., Kol. South Health El. Divn., PWDte
4 Apr 2025
29 Oct 2024
20 Dec 2024
29 Oct 2024
18 Dec 2024
6 Nov 2024
5 Nov 2024
Amount
Dismentling the existing old & damaged different type of light fittings , wires, cables, damaged rigid pipes, saddles etc. after disconnecting the internal connection as required and refixing the good ones as required as per direction of EIC.
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (approved make) partly in 20mm size PVC rigid conduit 'FR' (Brand approved by EIC) [for horizontal run & above false ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish [PVC Rigid Conduit only for horizontal run & above false ceiling and vertical run concealed]
Average run 10 mtr
On Board
S & F of double-door 6-Way TPN MCB DB in S.S enclosure with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish consisting with 1 no. 63A. FP MCB Isolator as Incommer & 18 nos 6-32A. SP MCB as Outgoing, complete with DIN Channel, Neutral Bar, Earth Bar and other accessories & connection with suitable size Cu wire with proper socketing incl. necessary earthing attachment with cable end box as per GS. (Make- Legrand/ LK/Schneider)
S & F of double-door 2+12 Way SPN MCB DB in S.S enclosure with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish consisting with 1 no. 40A. DP MCB Isolator as Incommer & 12 nos 6-32A. SP MCB as Outgoing, complete with DIN Channel, Neutral Bar, Earth Bar and other accessories & connection with suitable size Cu wire with proper socketing incl. necessary earthing attachment as per GS. (Make- Legrand/LK/Schneider)
Supply & Fixing Socket type fan regulator (Step type) (Brand approved by EIC) on existing sheet metal switch board with bakelite/perspex top cover by screw after making housing for regulator knob by cutting bakelite/perspex top cover incl. making necy. connections.
Supply & Fixing 240 V, 4 nos. 20A plug socket with separate 4 nos. 20A Piano key type switch, indicator & 16A kit-kat flush type fuse (Anchor) on sheet metal switch board embedded in wall incl. S & F 300x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.
Distribution wiring in 1.1 KV single core stranded 'FRLS' PVC insulated & unsheathed copper wire (RR Kabel/finolex/Havells) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required
2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm)
2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., cluding supplying sockets, tapes.
Supply & Laying of 4 core 25 sq.mm. PVC Ar./ Al. Cable (Glostar/Polycab/ Finolex) with 2 X 10 SWG GI wire through by saddling system on wall and mending good the damages to original finish as to G.S.
Supplying and fixing of 4 core 25 sq mm compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cable.
Finishing the end of 4 core 25 sq. mm XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials
S & F of 240 V 36/34 watt Recessed mounting LED ( 2' X 2') light fittings complete with all accessories including having provision suitable for2'x2' grid ceiling to be fixed in false ceiling by S&F GI wire from ceiling with anchor fasner or bullet, nut bolts etc. and necy. connection by 2x1.5 sq. mm PVC insulated Cu wire as per direction of EIC.Make- Philips Cat.No. RC370B LED36S-6500 G6 L60 W60 PSU OD S1 / Wipro,, lightin technology having similar specifications.
Supply & Fixing of single LED Tube light fitting complete with 1x 18/20 Watt tube lamp (LED ) 2100 lm[Make - Philips cat no. TMC 502 P 1x T-LED, Master LED tube model no. 1200mm 18W 865 T8 I-2100lm/ Crompton, wipro having similar specifications] suspended below the ceiling with S&F 2x20mm dia EI conduit up to 25 cm long with 'L' type MS clamp and making connection as to GS.
S/F of 240V, 85 Watt,1370 RPM,18" dia Wall Bracket fan having 4 nos. blade with metal body,base & blade(EPC India pvt ltd) incl. fixing with rag bolts, fastners etc. as per requirement as to GS.
S/F of 1200mm sweep AC ceiling fan complete with all accessories without regulator with Star rating -5(Make Crompton HS+ or HB+/ Usha striker plus)including engraving & painting departmental fan number on the body(upto 12 letters) with S/F dia down rod &making connection with 3 x 1.5 sqmm copper wire (Finolex/RR Kabel/Havells) as per the direction of E.I.C
S/F Wall mounted 240V, 920 RPM, 12" Exhaust Fan after cutting hole on wall with S/F nut, bolts & GI louver Shutter, mending good the damages & Making connection as per GS (EPC make Heavy Duty).
S/F Wall mounted 240V,1370 RPM, 9" Exhaust Fan after cutting hole on wall with S/F nut, bolts & GI louver Shutter, mending good the damages & Making connection as per GS (EPC make Heavy Duty).
Dismantling of 8 nos 1.5/2.0 Tr. Split Indoor unit and re-installation, Testing and commissioning at the original position after completion of Civil renovation work.
Dismantling of 10 nos 2'X2' powder coated aluminium defusser and 15 mtr. Long X 6" height continuous gril from the ceiling carefully and refixing the same at original position with necessary fixing arrangement as required.
Supply & Drawing of 1.1kV grade, 4Core 2.5 Sqmm PVC insulated unarmoured copper cable from the Timer Unit to ODU Unit and from ODU to IDU by MS saddle as to GS. (Make-Finolex/ Polycab/Gloster/Havells)
Thermal Duct Insulation with 13 mm thickness with fire retendent Al foil faced closed nitrul rubber insulation on ACP tap door with necessary pesting.(Make - Acoflex / Araflex /A Flex.
DRAIN PIPING :-Supply & laying of 1" dia.drain Water piping work out of UPVC/ HDPE hard pipes (Supreme, ISI Marked) incl. fitting , accessories bends, elbows, tees, flanges, tapings, etc. insulated with 9mm. Thick nitrile rubber tube insulation.
Defect Liabibility Period 1 (One) year
Make & model of each and every material to be approved by EIC
SIKDER ENTERPRISE (BID ID -5757881)
M/s Singh Electrical Works (BID ID -5873598)
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .