Executive Engineer (Electrical)
Executive Engineer (Electrical), Works Department, IIT Delhi, Hauz Khas, New Delhi - 110016
Servicing of ACBs in main LT Panels installed in various D.G. set rooms at IIT Delhi
2022_IIT_720755_1
IITD/WORKS(SP-4000)/2022
Open Tender
Miscellaneous Works
Works
30 days
IIT Delhi, Hauz Khas, New Delhi
As per tender document
12 documents required · 12 mandatory
₹0
₹8,005
21 Dec 2022
31 Oct 2022
17 Nov 2022
31 Oct 2022
16 Nov 2022
31 Oct 2022
Amount
One time overhauling and servicing of L&T make Air Circuit Breaker with C-Power maintenance kit consists of consumables like greases, cleaning spray, dusters, scrubber and hardware etc. by L&T authorized service centre minutely as per OEM scope of work for servicing for the following:
Overhauling and Servicing upto 1600A
Overhauling and Servicing 3200A to 4000A
Annexure-A REGULAR MAINTENANCE SERVICE Scope of work: Air Circuit Breaker:
(i) Cleaning of breaker with CRC-226 (ii) Removal of old grease and re-greasing the same complete as required. (iii) Checking the reset mechanism, tripping of breaker through push button. (iv) Checking tripping of ACB through protection release. (v) Tripping of ACB manually through volt metric release. (vi) Checking of presence and proper tightning of hardware. (vii) Checking of Ready-To-Close (RTC) (viii) Checking condition and alignment of jaw contact with breaker terminals. (ix) Checking condition of safety shutter. (x) Checking condition of ACB wiring and replace if required.
(xi) Checking working of anti pumping device in case of EDO ACB. (xii) Checking alignment of SIC and it's operation. (xiii) Checking condition of arc chutes. (xiv) Checking U/V release pick up & drop off. (xv) Checking ACB tripping through shunt release. (xvi) Checking motor operation in case of EDO ACB. (xvii) Checking closing coil operation in case of EDO ACB. (xviii) Checking continuity and proper changeover of aux contact block. (xix) Testing of release by L&T Simulation kit for overload, short circuit and Earth Fault. (xx) Setting of release as per the load and Checking the healthiness of CTs. (xxi) Visual observation of bus bar and wiring. (xxii) Any parts found defective shall be replaced by the contractor but items shall either be supplied by IIT Delhi or can be supplied by the contractor at extra cost after the approval of Engineer-In-Charge.
Consumables and reporting: (i) Maintenance kit needs to be purchased from our approved service centre. Require one maintenance kit per ACB. (ii) In case of any faulty part taken out of any switchgear and replaced, the same shall be handed over to IIT Delhi. (iii) Any other defect observed during service, which will affect the performance of switchgear shall be recorded by the contractor and shall give a copy of the same to IIT Delhi for records and further action. (iv) The cost of spares and consumables has not been included in the service charges. These must be provided by customers.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .