| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.9 LAccepted-AOC | L1 | Accepted-AOC Accepted due to lowest rate quoted | |
| 2 | L2₹32.3 L+₹3.3 L (11.5%)Rejected-Finance A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | L2 | Rejected-Finance Rejected due to highest rate quoted |
| Sl No | Description | Qty | Unit | D P ENTERPRISES L1 | M/S ADHIKARI CONSTRUCTION CO. L2 |
|---|---|---|---|---|---|
| 1.00 | M&L and T&P for attending complaints related to ceiling Fan, exhaust fan, wall fan, padestal fan etc any sweep, any type, any make fixed at different locations including taking down and refixing, cleaning all dirt, dust etc, replacement of connection lead/wire checking for loose connections in circuit, oiling and greasing split/window pins & other minor items,unserviceable screws assembly,bearing, re-fixing and testing to make it functional complete all as specified and as directed. Note :- 1. Cost of capacitor, connecting wire,regulator,ball bearing ,gun metal bush,ceiling rose etc shall be measured and paid under relevant item . 2.Cost of petty stores such as grease, lubricating oil ,lock nut , cross pin, checknuts,rubber seal etc are deemed to be included in quoted rate. | 500 | Each complaint | 30 ₹15,000 Lowest | 49 ₹24,500 |
| 2.00 | M&L and T&P for attending complaints related to Geyser any capacity Inspection and maintenance of water heater (Geyser) of capacity, 25 to 50 litres including performing the following task at different locations at AF Stn Rajokri.
(a) Removing Geyser & flow unit & heating element & cleaning the inner, tank with suitable acid/Replacement of defective connection lead .
(b) Checking and setting of thermostat between 50 to 55 ˚ C.
(c) Check working of NRV stop cock, pressure release valve and servicing carefully to make it functional
(d) Repairing of earthing connection, power switch, socket connection replacement of indicator lamp to make it functional
(e) Examine water leakage and rectifying as required and replacement of rubber washer gasket etc to make it functional
(f) Inspect over flow vent pipe, safety valve and remove blockage if required to make it functional.
(g) Any other item required for making Geyser serviceable will be measured & paid seperately under respective items. | 450 | Each complaint | 30 ₹13,500 Lowest | 49 ₹22,050 |
| 3.00Common Notes for Item No 1 & 2- (a) At least 01 electrician with 01 helper has to be deployed for day to day complaint rectification of Fan and Geyser at airforce station Rajokri (b) Contractor must insure sufficient store and T&P for geyser such as pipe wrench,screw driver etc and T&P for fan repair such as bearing puller, Plier,Tester and screw driver etc for attending complaint and stationary such as complaint slips, Registers etc.(c) Obtain user signature on complaint slip and register & submitting the records to the office of Engr-in-charge. | |||||
| 4.00 | M&L rewinding of burnt coils of ceiling fan motor, AC, 230 volt of 1200/1400 mm with super enamel copper winding wire of proper gauge, weight etc (having same nos of turns), winding using insulating materials varnishing, heating, baking, replacement of bearing, bush, shaft etc, re-assembling the fan after making it functional and testing ,maintain the speed of fan complete all as specified and as directed | 150 | Each | 400 ₹60,000 | 299 ₹44,850 Lowest |
| 5.00 | All as per Serial Item No 4 here in above but exhaust fan upto 450mm size/sweep | 30 | Each | 400 ₹12,000 | 399 ₹11,970 Lowest |
| 6.00 | All as per Serial Item No 4 here-in-above but Wall Mounting fan upto 750mm size/sweep | 15 | Each | 400 ₹6,000 Lowest | 499 ₹7,485 |
| 7.00 | All as per Serial Item No 4 here-in-above but Pedestal fan of any sweep/size. | 10 | Each | 400 ₹4,000 Lowest | 499 ₹4,990 |
| 8.00 | All as per Serial Item No 4 here-in-above but cabin fan of any sweep/size. | 10 | Each | 400 ₹4,000 Lowest | 499 ₹4,990 |
| 9.00 | M&L for spray painting of ceiling fan ,exhaust fan wall mounted,Pedestal fan of any size any type with one coat of synthetic enamelled paint after cleaning and making good the old damaged paint all as directed by Engineer- in Charge. | 50 | Each | 30 ₹1,500 Lowest | 49 ₹2,450 |
| 10.00 | Supply only Fan capacitor up to 1.5 µF complete all as specified and as directed. Make- Tibcon/Bajaj/Havells | 10 | Each | 30 ₹300 | 29 ₹290 Lowest |
Tender Value
₹44.5 L
EMD Value
₹89,000
Closing Date
28 Jul 2025, 6:00 pmClosed
GE (AF) GURGAON
GE (AF) GURGAON
REPAIR/MAINTENANCE OF INTERNAL ELECTRIC WIRING/LIGHT FITTING AND FIXTURES AND HOT WATER SYSTEM GEYSER FANS SUCH AS CEILING FAN WALL MOUNTED FANS EXHAUST FANS AND OTHER ALLIED WORKS IN DOMESTIC AND TECHNICAL AREA AND REPAIR/MAINTENANCE OF E/M INSTALL
2025_MES_717687_1
GE/GUR-/NIT-46/2025-26
Open Tender
Civil Works
Item Rate
270 days
GE (AF) GURGAON
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) GURGAON
₹89,000
23 Sept 2025
30 Jun 2025
30 Jul 2025
30 Jun 2025
28 Jul 2025
14 Jul 2025
Amount
M&L and T&P for attending complaints related to ceiling Fan, exhaust fan, wall fan, padestal fan etc any sweep, any type, any make fixed at different locations including taking down and refixing, cleaning all dirt, dust etc, replacement of connection lead/wire checking for loose connections in circuit, oiling and greasing split/window pins & other minor items,unserviceable screws assembly,bearing, re-fixing and testing to make it functional complete all as specified and as directed. Note :- 1. Cost of capacitor, connecting wire,regulator,ball bearing ,gun metal bush,ceiling rose etc shall be measured and paid under relevant item . 2.Cost of petty stores such as grease, lubricating oil ,lock nut , cross pin, checknuts,rubber seal etc are deemed to be included in quoted rate.
M&L and T&P for attending complaints related to Geyser any capacity Inspection and maintenance of water heater (Geyser) of capacity, 25 to 50 litres including performing the following task at different locations at AF Stn Rajokri. (a) Removing Geyser & flow unit & heating element & cleaning the inner, tank with suitable acid/Replacement of defective connection lead . (b) Checking and setting of thermostat between 50 to 55 ˚ C. (c) Check working of NRV stop cock, pressure release valve and servicing carefully to make it functional (d) Repairing of earthing connection, power switch, socket connection replacement of indicator lamp to make it functional (e) Examine water leakage and rectifying as required and replacement of rubber washer gasket etc to make it functional (f) Inspect over flow vent pipe, safety valve and remove blockage if required to make it functional. (g) Any other item required for making Geyser serviceable will be measured & paid seperately under respective items.
Common Notes for Item No 1 & 2- (a) At least 01 electrician with 01 helper has to be deployed for day to day complaint rectification of Fan and Geyser at airforce station Rajokri (b) Contractor must insure sufficient store and T&P for geyser such as pipe wrench,screw driver etc and T&P for fan repair such as bearing puller, Plier,Tester and screw driver etc for attending complaint and stationary such as complaint slips, Registers etc.(c) Obtain user signature on complaint slip and register & submitting the records to the office of Engr-in-charge.
M&L rewinding of burnt coils of ceiling fan motor, AC, 230 volt of 1200/1400 mm with super enamel copper winding wire of proper gauge, weight etc (having same nos of turns), winding using insulating materials varnishing, heating, baking, replacement of bearing, bush, shaft etc, re-assembling the fan after making it functional and testing ,maintain the speed of fan complete all as specified and as directed
All as per Serial Item No 4 here in above but exhaust fan upto 450mm size/sweep
All as per Serial Item No 4 here-in-above but Wall Mounting fan upto 750mm size/sweep
All as per Serial Item No 4 here-in-above but Pedestal fan of any sweep/size.
All as per Serial Item No 4 here-in-above but cabin fan of any sweep/size.
M&L for spray painting of ceiling fan ,exhaust fan wall mounted,Pedestal fan of any size any type with one coat of synthetic enamelled paint after cleaning and making good the old damaged paint all as directed by Engineer- in Charge.
Supply only Fan capacitor up to 1.5 µF complete all as specified and as directed. Make- Tibcon/Bajaj/Havells
Supply only Fan capacitor 2.5 µF complete all as specified and as directed. Make- Tibcon/Bajaj/Havells
Supply only Fan capacitor 3.15 µF complete all as specified and as directed. Make- Tibcon/Bajaj/Havells
Supply only Fan capacitor 4 µF complete all as specified and as directed. Make- Tibcon/Bajaj/Havells
Supply only ball bearing/shaft suitable/as per existing sample for exhaust fan, ceiling fan and pedestal fan/wallmounted fan/cabin fan etc complete all as specified and as directed. MAKE : NBC, SKF
Supply only Gun metal bush for ceiling fan/exhaust fan of any size/make/sweep complete all as specified and as directed
Supply and fixing ‘U’ clamps for hanging ceiling fan with all nuts & bolts, washer, suitable size with rubber reel complete all as specified and as directed
Supply and Fix in repairs ceiling fan canopy with nut and bolt of suitable size all as directed and specified.
Supply and fix in replacement of down rod for ceiling fan made out of 15 mm dia MS pipe complete with holes, slotted or threaded from 0.75 mtr to 1.5 mtr long all as specified and directed.
S & F nuts, bolts, washers, of any shape or size as directed including one coat of synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed .
S & F in replacemenmt of Fan blade for ceiling fan 1200/1400 mm sweep as per existing model complete all as specified and directed.
S & F replacement of Fan blade for Exhaust fan metal type any sweep as per as per existing model complete all as specified and directed.
S & F replacement of Fan blade for wall mounted fan any sweep as per as per existing model complete all as specified and directed.
S&F in replacement of metallic exhaust fan louvers of any shape (square or round as per site requirement ) upto 450 mm sweep complete all as specified and directed.
S&F ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) with remote complete all as specified and as directed by Engr-in-Charge. Make- Orient/Crompton/Havells
Supply and fix heavy duty copper wound exhaust fan, steel body ,AC single Phase. 230V of size 300 mm sweep 1400 RPM Double bearing with, 04 nos blades,frame,legs and louver complete with making arrangement for fixing of exhaust fan on steel/Aluminium frame window/ making opening in brick wall as per site requirement and also making good the disturbed surfaces as per matching to existing complete all as specified and as directed by Engr-in-Charge Make:- Crompton/Havells/Orient
Supply & fix wall mounting fans 230 volts single phase oscillating 400 mm sweep suitable for wall mounting complete all as specified and as directed by Engr-in-Charge. Make- Orient/Crompton/Havells
S&F plastic body ventilation fan 250 mm 50 Hz , 240 volt 1250 RPM with copper wound motor including all fixing accessories complete all as specified and directed.Make- Orient/Crompton/Havells
Supply and fix heavy duty copper wound exhaust fan, steel body AC single Phase. 230V of size 450 mm sweep 1400 RPM Double bearing with, 04 nos blades,frame,legs and louver complete with making arrangement for fixing of exhaust fan on steel/Aluminium frame window/ making opening in brick wall as per site requirement and also making good to disturbed surfaces as per matching to existing complete all as specified and as directed by Engr-in-Charge Make:- Crompton/Havells/Orient
Supply and fix heavy duty copper wound exhaust fan, steel body AC single Phase. 230V of size 380 mm sweep 1400 RPM Double bearing with, 04 nos blades,frame,legs and louver complete with making arrangement for fixing of exhaust fan on steel/Aluminium frame window/ making opening in brick wall as per site requirement and also making good the disturbed surfaces as per matching to existing complete all as specified and as directed by Engr-in-Charge Make:- Crompton/Havells/Orient
Supply only Geyser flow unit / assembley made of stainles steel to match with existing shape/size or as per sample suitable for 25 to 50 litres capacity including safety valve as directed by Engr-in-charge.
Supply only copper heating element of rating 1.5 KW to 2 KW to geyser 25 to 50 litres capacity, any type (normal and modular type), make / as per sample complete all as specified and as directed. Make - Theeta
Supply only Thermostat as per sample suitable for 50 to 25 litres capacity of geyser complete all as specified and directed.
Supply only Flexible SS braided connection heavy duty 15 mm dia, length up to 750 mm long with union at both ends for 15 mm dia pipe complete all as specified and as directed
Supply only Red and green indicator lamp as per existing size and shape complete all as specified and directed.
Supply only Plug top, 3 pin, 15Amps all as specified and as directed. Make-Anchor/cona/havells
Supply and fixing modular type AC box 3 module with 20 Amp single pole MCB including 15 amp modular socket complete all as specified and directed by the Engr-in-charge. Make : - Legrand, Havells, Indo asian
Supply only Anchor bolt type fastner brass size 10mm upto 150mm in length complete all as specified and directed.
Dismentling the flow unit, inlet/outlet pipe of Geyser & taking out to repair the inner copper/steel tank of capacity 25/35/50 litres storage capacity by brazing at different spots after cleaning rusted leaking spots and making the tank leak proof including refixing, re-assembling & testing complete all as specified and as directed
Material and labour for painting of geyser of 25 to 50 litres capacity with synthetic enamel spray paint with two coats of paint over one coat of red oxide primer including preparation of old surfaces complete all as specified and as directed
Supplying & Fixing of vertical type non return valve made of Brass size 15 mm complete all as specified and as directed
Supply & Fix insulation for 25 to 50 Ltrs geyser as per existing insulating material in required quantity for each geyser complete all as specified and as directed by Engineer-in charge.
S&F in replacement of Sheet metal enclosure factory made shutter type distribution board 2way (when MCBs are to be used) single pole and neutral, 240 Volts, with 200 Amp rated busbar, IP 43/IK09 (MCBs are to be measured & paid separately) complete all as specified and directed.
Supply & Fix in replacement of stainless steel water storage tank for upto 50 Ltrs capacity geyser as per existing gauge and shape complete all as specified and as directed by Engineer-in charge.
Supply & Fix in replacement of outer body 18 gauge complete with bottom and top cover matching the existing type and size for upto 50 Ltrs capacity geyser. Complete all as specifed & directed
Supply and fix electric water heater, storage type with Stainless steel tank and outer body made out of ABS & PP, heating element of 2 kw storage capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostat, NRV, SS braided connection pipe of suitable length etc complete all as specified and as directed by Engr-in-Charge. Make:-Racold /Havells/Crompton
S&F in replacement of metal clad plug top 240 volts 20 Amps with two phase pins and one neutral pins and one earth pin complete all as specified and directed
S&F in replacement of metal clad socket 240 volts 20 Amps to fix two phase and neutral pins and one earth pin complete all as specified and directed
M&L for making arrangement for fixing of exhaust fan on steel/Aluminium frame window/ making opening in brick wall as per site requirement and also making good to disturbed surfaces as per matching to existing complete all as specified and directed.
Taking down carefully copper / aluminium point wiring light / fan, socket or power point complete including fittings such as switches, sockets, ceiling rose, bell push bell buzzer lamp holder bracket etc. removing from site and making good disturbed surface of wall, floor etc complete all as specified and as directed.
M & L for replacement of concealed point wiring complete with PVC insulated and unsheathed FRLS cable of 1.5 sqmm (nominal area) with multi stranded copper conductor single core 1100 volts grade in and including rigid PVC conduit ISI marked medium grade not less than 20 mm dia, with MS stove enamelled sunken boxes (normal and modular type as required) including earth dolly with plastic laminated sheet top cover (cover plate with frame in case of modular) of approved make and colour including 1.5 sqmm multi stranded FRLS copper conductor cable of green colour as continuous earth wire with lugs and accesseries and making good disturbed surfaces of walls/floor etc complete all as specified and directed for the followings :-
One light / fan point controlled by one way switch
One 5 Amp socket outlet on independent board.
One 5 Amp socket outlet on same board.
One bell/buzzer point controlled by one bell push
One light point controlled by two 2-way switch
All as per above item No-47 here in before but using 2.5 sqmm single core multi stranded copper conductor PVC insulated and unsheathed, FRLS cable for 15 Amp socket outlet on independent board including 2.5 sqmm multi stranded copper conductor cable of green colour as continuous earth wire with lugs etc as required complete all as specified and as directed.
M&L for replacement of point wiring in casing caping on sufraces of wall/ceiling floor etc complete with PVC insulated and unsheathed FRLS cable of 1.5 sqmm (nominal area) with multi stranded copper conductor single core 1100 volts grade with PVC rectangular block of suitable size including 1.5 sqmm multi stranded FRLS copper conductor cable of green colour as continuous earth wire with lugs and accesseries and making good disturbed surfaces of walls/floor etc complete all as specified and as directed for the followings :-
One light / fan point controlled by one way switch
One 5 Amps socket out let point controlled by one 1-way switch on independent board.
One 5 Amps socket out let point controlled by one 1-way switch on same board.
One bell/buzzer point controlled by one bell push
One light point controlled by two 2-way switch
All as per above item no 49 here in befor but using 2.5 sqmm single core multi stranded copper conductor PVC insulated and unsheathed, FRLS cable for 15 Amp socket outlet on independent board including 2.5 sqmm multi stranded copper conductor cable of green colour as continuous earth wire with lugs etc as required complete all as specified and as directed.
M & L for replacement of existing conduit point wiring complete with PVC insulated and unsheathed FRLS cable of 1.5 sqmm (nominal area) with multi stranded copper conductor single core 1100 volts grade drawn through existing conduitwith MS stove enamelled sunken boxes (normal and modular type as required) including earth dolly with plastic laminated sheet top cover ( cover plate with frame in case of modular) of approved make and colour including 1.5 sqmm multi stranded FRLS copper conductor cable of green colour as continuous earth wire with lugs and accesseries and making good disturbed surfaces of walls/floor etc complete all as specified and directed for the followings :-
One light / fan point controlled by one switch.
One bell point controlled by one bell Push
One 5 Amps socket out let point controlled by one switch on independent board.
One 5 Amps socket out let point controlled by one switch on same board.
All as per item No. 51 but with 2.5 Sqmm nominal cross sectional area electric cable for 15 Amps socket outlet point controlled by one switch on independent board complete.
S&F in replacement switch piano type 5 amp one way 240 volts AC 50 hz ISI Marked complete all as specified and directed by Engineer-in-Charge.
S&F in replacement switch piano type15 Amps one way 240 volts AC 50 hz ISI Marked complete all as specified and directed by Engineer-in-Charge.
S&F in replacement socket outlet 3 pin 5 Amps 240 volts AC 50 hz ISI marked flush type complete all as specified and directed by Engineer-in-Charge.
S&F in replacement socket outlet 2-in-1, 6 pin 5 amp and 15 amps 240 volts AC 50 hz ISI marked all as specified and directed.
S&F in replacement socket outlet 6A-2/3 Pin combined 2 module 240 volts AC 50 hz ISI marked modular type complete all as specified and directed.
S&F in replacement socket outlet 6A/16A-2/3 pin combined 2 module 240 volts AC 50 hz ISI marked modular type complete all as specified and directed.
S&F in replacement switch 6 amps modular type one one way 240 volts AC 50 hz ISI marked complete all as directed.
S&F in replacement switch 16 amps modular type one one way 240 volts AC 50 hz marked complete all as directed.
S&F in replacement electronic fan regulator Step type complete all as specified and directed.
S&F in replacement bell push flush type 5 amp one way 240 volts AC 50 hz ISI Marked complete all as specified and directed.
S&F in replacement modular type bell push 6 amp one module 240 volt ISI marked complete all as specified and directed.
S&F in replacement Bell, DING DONG AC 230 Volts single pole type complete all as specified and as directed.
S & F in replacement of Lamp holder bakalite type with back plate suitable for batten fittings complete all as specified as directed
S&F in replacement of ceiling rose surface bakelite 63 x50mm three terminals complete all as specified and as directed.
S & F in replacement of sub main wiring with PVC insulated, FRLS unsheathed two single core cable 1100 volts grade with stranded copper conductor of size 4.0 sqmm (Nominal area) drawn in and including PVC conduit of suitable size as directed with and including one run of 4.0 sqmm multi stranded copper conductor single core PVC insulated, unsheathed cable of green colour as continuous earth wire including lugs etc connected and tested complete all as specified and as directed. Note: (i) Two runs of 4.0 sqmm cable and one run of 4.0 sqmm cable of earth continuity conductor and conduit shall be a unit length.
S & F in replacement of sub main wiring with PVC insulated, FRLS, unsheathed two single core cable 1100 volts grade with stranded copper conductor of size 6.0 sqmm (Nominal area) drawn in and including PVC conduit of suitable size as directed with and including one run of 6.0 sqmm multi stranded copper conductor single core PVC insulated, unsheathed cable of green colour as continuous earth wire including lugs etc connected and tested complete all as specified and as directed. Note: (i) Two runs of 6.0 sqmm cable and one run of 6.0 sqmm cable of earth continuity conductor and conduit shall be a unit length. Common Note For Item No- 67&68- (i) if the contractor fail to make good the disturbed surface of wall and do not match with existing surface of wall to the entire satisfaction of Engr-in-Charge a recovery of Rs 50 per RM shall be made from payment due to contractor.
S & F in replacement of Rigid non-metallic PVC conduit 25 mm (external dia) ISI marked (on surface) incl of all accessories and all fittings such as Tees bends, elbows, reducers, bell mouth, tube ends and fixing accossories such as couplers lock nuts, saddles, pipe hook etc complete all as specified and as directed.
S&F in replacement of sheet metal enclosure double door concealed suitable for SPN distribution boards when MCB to be used having 200 Amp rated bus bar 12 ways 240 V including fixing in new location with connection of circuit and submain as per site requirement complete all as specified and as directed . Note- (a) MCBs are to be measured and paid seperately. (b)Make of MCBs and DB should be same.(c) Extra circuit length where DBs are to be shifted from existing location to new location shall deemed to be included in the quoted rate. Make-Havells/Indoasian/Legrand,
S&F in replacement of sheet metal enclosure double door concealed suitable for SPN distribution boards when MCB to be used having 200 Amp rated bus bar 8 ways 240 V including fixing in new location with connection of circuit and submain as per site requirement complete all as specified and as directed . Note- (a) MCBs are to be measured and paid seperately. (b)Make of MCBs and DB should be same.(c) Extra circuit length where DBs are to be shifted from existing location to new location shall deemed to be included in the quoted rate. Make-Havells/Indoasian/Legrand,
S&F in replacement of sheet metal enclosure double door concealed suitable for SPN distribution boards when MCB to be used having 200 Amp rated bus bar 4 ways 240 V including fixing in new location with connection of circuit and submain as per site requirement complete all as specified and as directed . Note- (a) MCBs are to be measured and paid seperately. (b)Make of MCBs and DB should be same.(c) Extra circuit length where DBs are to be shifted from existing location to new location shall deemed to be included in the quoted rate. Make-Havells/ Indoasian/Legrand,
S&F in replacement of single pole and neutral enclosure with 2 pin and metal earth plug and socket complete with one single pole MCB 25 Amp complete all as specified and as directed.Make-Havells/Indoasian/Legrand
S&F in replacement of Double door three phase distribution board 4 way IP 54 IK 09 loadline VTPN with 125 Amp MCCB to be used as incomer and made out of CRCA sheets 1.6 mm thick, phosphatised powder coated with copper Bus Bar 250 Amps, 415 V, Earth Stud, Din Rail, Polymide terminal blocks for incoming and outgoing circuits, inbuilt loose wire box ,ground terminal blocks ,duly prewired with thimbled flame retardant copper conductors and poly layer for protection complete all as specified and directed (Note:-(a) Rate of MCCB and MCBs are included in quoted rate. (b) capacity of Single pole MCB shall be provided as per requirement and direction. (c) Make of MCB /MCCB and DB should be same. Make-Havells/Indoasian/Legrand.
S&F in replacement of Double door distribution board 6 way TPN when MCB to be used as incomer powder coated with Bus Bar 200 Amps, 415 V, Earth Stud, Din Rail, complete all as specified and directed (Note- (a) MCBs are to be measured and paid seperately. (b)Make of MCBs and DB should be same.) Make-Havells/Indoasian/Legrand.
S&F in replacement MCB SP 6 to 32 Amps, 240 volts curve 'B',breaking capacity 10KA, all as specified.
S&F in replacement MCB SPN 16 to 40 Amps, 240 volts, curve 'B', breaking capacity 10 KA, all as specified.
S&F in replacement MCB SPN 40 to 63 Amps, 240 volts, curve 'C', breaking capacity 10 KA, all as specified.
S&F in replacement MCB TPN 40 to 100 Amps, 415 volts, curve 'B', breaking capacity 10 KA, all as specified.
S&F in replacement MCCB , 125 Amps, 4Pole with adjustable thermal magnetic release type setting knob and rupturing capacity 16 kA complete all as specified and directed.
S & F In replacement of modular switch 2 way, 6 Amp,1 module ISI Marked complete all as specified and as directed.
S & F in replacement of modular Fan Regulator fan step regulator,120W- single module ISI Marked complete all as specified as as directed.
S & F In replacement of Piano type switch 2 way, 5 Amp,1 module ISI Marked complete all as specified and as directed.
S&F in modular blanking plate, 1 module ISI Marked complete all as specified and as directed.
S&F in replacement metal flush box 3 module all as specified and directed.
S&F in replacement metal flush box 6 module all as specified and directed.
S&F in replacement metal flush box 8 module all as specified and directed.
S&F in replacement for white cover plate with frame, 3 module all as specified and directed.
S&F in replacement for white cover plate with frame, 6 module all as specified and directed.
S&F in replacement for white cover plate with frame, 8 module all as specified and directed.
Supply and fixing in repair of Earthing to DBs with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to main earth lead 4.0 sqmm galvanised iron wire by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.3 of MES Schedule pt-I 2009, GI earth lead shall be protected by GI pipe 15 mm dia medium grade and connected to distribution board including excavation in any type of soil,returning filling, disposal of soil, providing charcoal dust and common salt upto top edge of earth plate, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion complete all as specified and as directed.Note- cost of 7.5 RM of GI wire shall be included in quoted rate
M & L in repair for Earth continuity conductor or main earthing lead of 4.0 Sqmm galvanized iron wire, buried in ground or fixed to wall in and including 15 mm bore GI pipe medium grade for protection of earth wire complete all as specified and directed.
S&F in replacement enviroment friendly,ultra modern,energy saving surface mounted decorative 12 Watt LED bulkhead fitting PC housing ,high efficient LEDs with opal diffuser and IP65 protectio, lumen efficacy 85 lm/watt with colour temerature 3500K/6500K as per site requirement, THD≤ 20 CRI>80,2.5 kV surge protection all as specified and directed. Make- Surya/crompton/Jaquar
S&F 09 watt LED bulb with B22 Base cap, 1200 lumens ,Colour rating Index 80,colour temp F 6500K,satrtup time less than 2 sec,In built surge 3.0 kV, voltage range 140V to 270 V , Lamp life 15000 hours complete all as specified and directed.
S&F 12 watt LED bulb with B22 Base cap, 1200 lumens ,Colour rating Index 80,colour temp F 6500K,satrtup time less than 2 sec,In built surge 3.0 kV, voltage range 140V to 270 V , Lamp life 15000 hours complete all as specified and directed.
S&F in replacement of enviroment friendly indoor decorative 20 Watt LED polycarbonate Batten with opal diffuser , operating voltage range 140v to 270 V, Driver efficiency 88%, lumen efficiency =100 lm/watt , THD≤ 20 CRI>80 , colour temperature 6500 K, inbuilt surge protection = 2.5 Kv, isolation=3.75, and with zero mercury content including all accessaries all as specified and directed. Make- Surya/crompton/Jaquar
S&F in replacement of enviroment friendly indoor decorative 9/10 Watt LED polycarbonate Batten with opal diffuser , operating voltage range 140v to 270 V, Driver efficiency 88%, lumen efficiency =100 lm/watt , THD≤ 20 CRI>80 , colour temperature 6500 K, inbuilt surge protection = 2.5 Kv, isolation=3.75, and with zero mercury content including all accessaries all as specified and directed. Make- Surya/crompton/Jaquar
S & F in replacement enviroment friendly recess/pendent/Surface mounting as required at site 36 watt LED flat panel 2'x2' fabricated CRCA sheet steel duly powder coated housing cool white with high efficient LEDs & glare free opal diffuser PF>0.95 , lumen efficacy>100 lm/W, THD<10% operating range 220v to 240V,CRI>80 including connection with existing wire and all accessaries all as specified and directed. Make- Surya/Halonix/orient
S & F in replacement enviroment friendly recess/pendent/Surface mounting 24 watt LED flat panel 1'x1' fabricated CRCA sheet steel duly powder coated housing cool white with high efficient LEDs & glare free opal diffuser PF>0.95 , lumen efficacy>100 lm/W, THD<10% operating range 220v to 240V,CRI>80 including connection with existing wire and all accessaries all as specified and directed. Make- Surya/Halonix/orient
S&F in replacement of enviroment friendly indoor decorative 5/6 Watt LED polycarbonate Batten with opal diffuser , operating voltage range 140v to 270 V, Driver efficiency 88%, lumen efficiency =100 lm/watt , THD≤ 20 CRI>80 , colour temperature 6500 K, inbuilt surge protection = 2.5 Kv, isolation=3.75, and with zero mercury content including all accessaries all as specified and directed. Make- Surya/Halonix/orient
S & F in repair plastic laminated bakelite sheet cover of Hylam brand including cutting holes for switches, sockets etc as pre requirement including fixing with machine screws and washer complete of following sizes:-
(a) 10" x 12" size
(b) 8" x 10" size
(c) 8" x 6" size
(d) 7" x 4" size
(e) 4" x 4" size
S&F in replacement of Energy meter Box Flame retardent polycarbonate body including all fixing arrangement like DIN rails mounting plate connection boxes fastning screw protection plate extra suitable to accomodate single Phase/three phase energy meter with locking arragement as per site rwquirement complete all as specified and directed.
M&L for flame proof wiring with single core PVC insulated and unsheathed 1100 volt grade FRLS electric cable with multi stranded copper conductor of size 2.5 Sqmm phase and neutral drawn in and including ERW rigid steel stove enameled black conduit heavy duty ISI marked of size 20mm dia on surface/wall/ceiling including all flame proof conduct fittings and accessories such as tees junction boxes, bends duly tested by CMRI Dhanbad suitable for one light /fan point controlled by one flame proof rotary switch SP one way and including drawing continuous earth wire FRLS PVC insulated unsheathed 1100v grade cable with stranded copper conductor of size 1.5 Sqmm and connected to earth dolly complete all as specified and directed by Engrs-in-Charge.
Supply and fixing flame proof/weather proof direct entry type rotary switch single pole on & OFF rotary motion switch in cast aluminum alloy LM-6 enclosure epoxy powder coated single pole 230Volts 10 Amps, AC ON/OFF switch operated externally by Knob having 02 Nos of M-20 cable entries, earthing terminals suitable for mounting on Wall/Steel structure etc all as specified and directed. Make : Flexpro/Sudhir/Baliga/Shyam.
Supply and fixing LED light fitting 1x16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver,holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete all as specified and as directed size. Note :- (a) All fittings shall be ISI marked and shall have approval of CMRI Dhanbad . (b) Original Test certificate of Manufacturer shall be produced by Contractor .
M&L for fixing PVC gang box for mounting one switch and one socket of 5 Amps including all accessoriese complete all as specifies and directed.
M&L for fixing PVC gang box for mounting one switch and one socket of 15 Amps including all accessoriese complete all as specifies and directed.
Supply and fixing of PVC Casing capping 20/25mm ISI marked all as specified and as directed by Engineer-in-charge.
S&F in replacement of Cable PVC insulated unsheathed single core 1100V FRLS grade stranded flexible copper conductor of size 1.5 sqmm complete all as specified and directed. Make:- Finolex/Havells/Grandlay
Supply and fixing in replacement of Cable PVC insulated unsheathed single core 1100V FRLS grade stranded flexible copper conductor of size 2.5 sqmm complete all as specified and directed. Make:- Finolex/Havells/Grandlay
Supply and fixing in replacement of Cable PVC insulated unsheathed twin core of 23/0.0076 size flexible copper conductor complete all as specified and directed.
Supply and fixing in replacement of Cable PVC insulated unarmoured three core 1100V FRLS grade stranded flexible copper conductor of size 2.5 sqmm complete all as specified and directed. Make:- Finolex/Havells/Grandlay
Supply and fixing 25 mtr long 2.5 cm wide and atleast .125 mm wall thickness self adhesive PVC insulated electrical tape roll of good quality complete all as specified and directed.
Supply and fixing of PVC round shape junction box cover of suitable size including fcomplete all as specified and as directed.
Taking down light fittings of any type any size any location complete all as specifed and directed.
Taking down DB including old U/s MCB/MCCB of any size any type from any location complete all as specifed and directed.
S&F in replacement of recesses/surface mounted square/round shape slim downlighter of 12 watt capacity with colour temperature 3500/6500 K as required, Lumens 780, CRI more than 80 including all accessories and ring for mountiong on ceiling complete all as specified and directed.Make- orient, Philips, Halonix
S&F in replacement of old unserviceable decorative type wall mounted with new wall comet light fitting with LED bulb pin type B22 cap 3500 K complete all as specified and directed. Make- Philips 30575 or equivalent
Supply & Fix in replacement of copper wound Fan motor for exhaust Fan upto 300mm sweep metal body any sweep complete as per matching to existing type and gauge cpmplete all as specified and directed.
Supply & Fix in replacement of copper wound Fan motor for Ventilating Fan PVC body 250/200 mm sweep with front lock & capacitor complete as per existing model and gauge complete all as specified and directed.
Supply and fixing in replacement post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 class protection with aluminium die cast housing cum heat sink circular canopy and clear acrylic cover for 360 degree indirect uniform glare free light distribution impact and corrosion resistant operating voltage range 140v to 270 V, total system lumen not less than 3200 lumens lumen efficiency =80 lm/watt , THD≤ 20 CRI>80 , colour temperature 3500/ 6500 K as required, inbuilt surge protection = 5 Kv, 50000 Hrs burning hours including grouting in post by using suitable dia mediun grade GI pipe complete all as specified and directed..
Supply and fixing LED Bollard 8 watt 230 watt volts AC outdoor type with decorative for 360 degree indirect light IP 65 class protection with aluminium die cast housing cum heat sink circular at the top and opaque acrylic cover for 360 degree indirect uniform glare free light distribution impact and corrosion resistant operating voltage range 140v to 270 V, total system lumen not less than 3200 lumens lumen efficiency =80 lm/watt , THD≤ 20 CRI>80 , colour temperature 3500/6500 K as required, inbuilt surge protection = 5 Kv, 50000 Hrs burning hours complet all as specified and directed. Note- Earth work and PCC shall be included in quoted rate.
supply and fixing plastic body ventilation fan 200 mm as required 50 Hz , 240 volt 1250 RPM with copper wound motor including all fixing accessories complete all as specified and directed.Make- Orient/Crompton/Havells
S & F in replacement of sub main wiring with PVC insulated, FRLS unsheathed two single core cable 1100 volts grade with stranded copper conductor of size 10.0 sqmm (Nominal area) drawn in and including PVC conduit of suitable size as directed with and including one run of 10.0 sqmm multi stranded copper conductor single core PVC insulated, unsheathed cable of green colour as continuous earth wire including lugs etc connected and tested complete all as specified and as directed.Note:(i) Two runs of 10.0 sqmm cable and one run of 10.0 sqmm cable of earth continuity conductor and conduit shall be a unit length.
S & F in replacement of sub main wiring with PVC insulated, FRLS unsheathed two single core cable 1100 volts grade with stranded copper conductor of size 2.5 sqmm (Nominal area) drawn in and including PVC conduit of suitable size as directed with and including one run of 2.5 sqmm multi stranded copper conductor single core PVC insulated, unsheathed cable of green colour as continuous earth wire including lugs etc connected and tested complete all as specified and as directed.Note: (i) Two runs of 2.5sqmm cable and one run of 2.5 sqmm cable of earth continuity conductor and conduit shall be a unit length.
S & F in replacement of sub main wiring with PVC insulated, FRLS unsheathed two single core cable 1100 volts grade with stranded copper conductor of size 1.5 sqmm (Nominal area) drawn in and including PVC conduit of suitable size as directed with and including one run of 1.5 sqmm multi stranded copper conductor single core PVC insulated, unsheathed cable of green colour as continuous earth wire including lugs etc connected and tested complete all as specified and as directed.Note: (i) Two runs of 1.5 sqmm cable and one run of 1.5 sqmm cable of earth continuity conductor and conduit shall be a unit length.
S&F of Flameproof cum Waterproof LED Bulk Head light fitting of 70W, IP66 protection of Cast Aluminum alloy material and Heat and Impact resistance toughen 'A' clear glass having Anti corrosive epoxy powder coated finish complete with all accessories pre wired and including connecting up with three core flexible copper conductor cable with suitable size complete all as specified and as directed.
S&F in replacement metal flush box 4 module all as specified and directed.
S&F in replacement for white cover plate with frame, 4 module all as specified and directed.
S&F in replacement metal flush box 12 module all as specified and directed.
S&F in replacement for white cover plate with frame, 12 module all as specified and directed.
S&F in replacement of enviroment friendly indoor decorative three in one 20 Watt LED polycarbonate Batten with opal diffuser , operating voltage range 140v to 270 V, Driver efficiency 88%, lumen efficiency =100 lm/watt , THD≤ 20 CRI>80 , three in one colour temperature (6500k/4000K/3500 K) operated by single switch, inbuilt surge protection = 2.5 Kv, isolation=3.75, and with zero mercury content including all accessaries all as specified and directed.
S&F in replacement of enviroment friendly outdoor decorative wall light two way up and down 6 Watt LED operating voltage range 140 v to 270 V, colour temperature (4000K/3500 K) operated by single switch including all accessaries all as specified and directed.
Supply , laying & testing in repair for XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete of size 120 Sqmm nominal cross section x 3.5 core complete all as specified and directed
Ditto but of size 6 sqmmx 2 core
Supply and fixing of GI tubing, light grade, 40 mm bore with all fitting laid in trenches / pole / wall for protection of cables in repairs complete.
Supply and fixing of GI tubing, light grade, 80 mm bore with all fitting laid in trenches / pole / wall for protection of cables in repairs complete.
S&F in replacement of Danger notice plate of 1.6mm thick mild steel sheet vitreous enameled white with letter figures and conventional skull and bones in signal red colour and fix with MS clamp/Nut bolt for LT complete all as specified.
Supply & fix single pointed air termination aluminium rod 12mm dia, 300 mm long complete all as specified and directed
M&L for preparation of old steel painted surfaces of LT panels of any type and size by brushing/changing stain, greasy spots with thinner and apply two coats of spray painting with super enameled paint with colour of users choice approved by Dept. and writing the distribution area/location with white paint as directed complete all as specified and directed
Excavation in trenches in soft/loose soil not exceeding 1.5 meter wide & not exc 1.5 mtr deep and getting out for taking out/laying cable, poles & stay etc complete all as specified and directed by engr-in-charge.
Returning, filling in including spreading levelling watering and well ramming in layers not exceeding 25cm thick after the cable have been laid and tested complete all as specified and directed by Engr-in-Charge..
Removal of excavated surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed by Engr-in-Charge.
M & L for dry sand cushioning to underground cables with 8cm thick before laying of cables and 15cm thick after laying ( total 23 cm ) and compaction till 18 cm thick for measurement purpose complete all as specified and directed .
Material labour for common burnt clay bricks, sub class 'B' grade laid in trenches for protection of UG cables perpendicular to the direction of the cables complete all as specified and as directed by Engr-in-Charge
M&L for glow sign board of size 4ft x 6ft madeup of metallic GI sheet and main cover with acrylic sheet consisting of LED light 20 watt of suitable numbers fixing on wall or with fixing arrangement on SS pipe 50mm dia. support including provision of PCC 1:2:4 type B-1 for grouting the same including excav and earth work as per site requirement complete all as specified and directed . Note :- Writing words/symbols/sketches of size and colour to be decided as per user's requirement & deemed to be included in quoted rate
Supply and fixing in replacement LED type flood light 120 watt 230 watt volts AC outdoor type with t IP 65 class protection with aluminium die cast housing glare free light distribution impact and corrosion resistant operating voltage range 140v to 270 V, total lumen efficiency =80 lm/watt , THD≤ 20 CRI>80 , colour temperature 6500 K, inbuilt surge protection = 5 Kv, 50000 Hrs burning hours complet all as specified and directed..
Supply and fixing in replacement post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 class protection with aluminium die cast housing cum heat sink circular canopy and clear acrylic cover for 360 degree indirect uniform glare free light distribution impact and corrosion resistant operating voltage range 140v to 270 V, total system lumen not less than 3200 lumens lumen efficiency =80 lm/watt , THD≤ 20 CRI>80 , colour temperature 3500 K, inbuilt surge protection = 5 Kv, 50000 Hrs burning hours including gountong of light grade pipe of suitable length on post complet all as specified and directed..
S& F in replacement of Solar Street Light fitting 20 watt all in one made with High Efficiency Mono Crystalline Solar PV Module, Lithium Ferro Phosphate battery with in-built BMS technology, High Efficacy LED, MPPT Solar Charge Controller and Aluminium Extruded body & is specially progrmmed to automatically control the dimming and brightness of light, which increases the backup time complete all as specified and directed.
M&L for cutting,clearing bushes/small plants and grass surrounding the E/M installations and removing the debris to a distance of 50m complete all as specified and as directed by Engr-in-charge.
M&L in repair/replacement for Earthing to machinary with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to main earth strip of size 32x6mm galvanised iron strip by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.3 of MES Schedule pt-I 2009, GI earth lead shall be protected by GI pipe 40 mm dia medium grade and connected to machinary including excavation in any type of soil,returning filling, disposal of soil, providing charcoal dust and common salt upto top edge of earth plate, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion complete all as specified and as directed.
Supply and fix GI strip of size 32x6 mm for Earth continuity conductor or main earthing lead fixed wall with saddles and fixing screws etc. or laid underground as in grid connection of earthing complete all as specified and directed.
Supply and fix aluminium strip of size 25x3.15 mm for Earth continuity conductor or main earthing lead fixed to wall/ roof with saddles and fixing screws etc. for roof conductors and down conductors above ground or any other indicated situation complete all as specified and directed.Note:- Two lengths of strips shall be jointed together by overlapping not less than 100 mm both ends through welding/brazing.
M&L for test point terminal block in replacement made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex.head screw complete all as specified and directed by Engineer-in-Charge.
Material Labour And T&P for tree pruning near LT pole for clearing the conductor/light fitting by means of ladder/hydra as per directed location complete all as specified and directed.
S&F in replacement of sheet metal enclosure double door concealed suitable for SPN distribution boards when MCB to be used having 200 Amp rated bus bar 8 ways 240 V including fixing in new location with connection of circuit and submain as per site requirement complete all as specified and as directed . Note- (a) MCBs are to be measured and paid seperately. (b)Make of MCBs and DB should be same.(c) Extra circuit length where DBs are to be shifted from existing location to new location shall deemed to be included in the quoted rate. Make-Havells/Indoasian/Legrand,
M/S ADHIKARI CONSTRUCTION CO. (BID ID -3371802)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .