Loading…
Loading…
Tender Value
₹22.8 Cr
EMD Value
₹45.5 L
Closing Date
22 Jun 2026, 12:00 pm7d left
Gopal Kalawat
Municipal Corporation Panipat
Providing and Laying of Sewer and Storm Water Line in Bishan Swaroop Colony including restoration of damaged Streets/Roads and construction of 3.00 MLD Sewerage Treatment Plant (CM Announcement Code No. 27802 dated 07.07.2024) Design, construction,
2026_HRY_527664_1
2026D1AF5D78 A8C9 4F81 960D 106E255EA846286ULB
Open Tender
Civil Works
720 days
Panipat
2 documents required · 2 mandatory
₹20,000
₹45.5 L
Yes
9 Jun 2026
9 Jun 2026
22 Jun 2026
9 Jun 2026
22 Jun 2026
9 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | STP (SEWAGE TREATMENT PLANT): 3.00 MLD: Design, construction, erection, testing and commissioning of 3.00 MLD capacity Sewage Treatment Plant based on Sequential Batch Reactor (SBR) including Electrical, Mechanical, Piping and Instrumentation work with PLC and SCADA arrangement for STP integrated with MPS and other works contingent thereto including 3 months successful trial-run and thereafter 6 Years Defect Liability-cum-Maintenance Period as per detail and specifications mentioned in DNIT along with following provisions
1.1 2 No. High Mast of 9 mtr GI Octagonal pole of 4 mm thickness (T=100 mm, B=200mm, Base Plate = 320 x 320 x 20 mm), Window at 500 mm from Base Plate with 6 No. LED suitable size, outdoor type energy efficient lamps on each pole, 20 no. LED outdoor light with 7 m. high GI pole along road / path including all accessories, cable, wire etc complete in all respect.
1.2 Supply and fixing of 1 No. 3.65 m wide SS 304 main Gate along with1.25 m. wide wicket gate at STP to the entire satisfaction of Engineer-in-charge. (Total weight not less than 500 kg).
1.3 CC TV CAMERAS: Providing and Installing 6 CCTV Cameras (4 Cameras for STP and 2 Camera at MPS-1) within 96 hours of signing the agreement along with 120 days recording (DVR), 48 inch LED Screen, 16 Channel DVR at STP and MPS Site with connectors, cables, poles and power supply with online real-time output facility. The cameras at MPS and STP shall be synchronized at STP site complete in all respect.
PTZ speed dome 360 degree 50X zoom camera, CP Plus Internet Protocol minimum 5 MP WDR, Night vision color mode, IR range up to 150 m. CCTV Cameras should be installed and commissioned before starting of the work.Make: Sony / Canon / Panasonic / Samsung
1.4 EWQMS (Effluent water quality monitoring system): Supply, Installation, Testing, Commissioning, Operation and Comprehensive Annual Maintenance of effluent quality monitoring system at 3.00 MLD capacity STP for online (continuous) measurement of PH, Total Suspended Solids (TSS), Chemical Oxygen Demand (COD), Biological Oxygen Demand (BOD) by single analyzer with various sensors (spectral measurement in the UV-VIS range 200-720mm) performing reagent and chemical free analysis with automatic cleaning of censor, signal cables and power cables, local data acquisition and display of data on continuous basis for up linking the data to CPCB, HSPCB and PHED, TUV approved complete in all respect as per Central Pollution Control Board (CPCB) guidelines for online continuous monitoring system for effluents.
1.4.1 Multi-parameter measuring converter, for connecting up to 18 intelligent sensors Scope including 8 analog inputs / outputs (4 inputs and 4 outputs) (0/4-20Ma), wide- range power supply Optical COD/BOD and TSS probe with spectral processing of the UV-VIS range, for measurement in the outlet / effluent of 3.00 MLD capacity STP with integrated with automatic cleaning complete in all respect.
1.4.2 Robust digital pH/ORP sensor for pH/ORP electrodes, with built-in pre-amplifier and temperature sensor with Automatic Temperature Compensation (ATC) Cable length 100 Meter (minimum) complete in all respect.
1.4.3 Sensor adapter cable for all intelligent sensors, with IP68 water proof connection to the intelligent Sensor Net system. Cable length 100 meter (minimum) complete in all respect.
1.4.4 Data transfer to CPCB, HSPCB and PHED servers complete in all respect.
1.4.5 Providing GSM 3G, 4G modem with mobile network connectivity including network including complete in all respect.
`1.5 Providing and installation of online flow measurement at inlet , outlet and byepass including suitable size flow meter complete in all respect`
1.6 Conveyance of treated effluent from cholorine contact tank to effluent collection tank through suitable size DI K9 pipe along with cost of pipe, sluice valves, specials, material and labour complete in all respect. | 1 | Job | - | - |
| 2 | ANNEXE BUILDING: Construction of HT / LT Panel room, PLC room, Blower room and Lab cum Office building, Toilet block including doors, windows,finishing, electric, and sanitary fittings complete in all respect as per drawings approved by SE. The building will be built up with RCC frame structure and brick work as per specifications mentioned in attached additional documents including maintenance during 6 years Defect liability-cum-maintenance period after successful completion of trial run period of 3 months. | 250 | per | - | - |
| 3 | Supply and Pushing of MS casing pipe of specified thickness by trenchless method adopting micro-tunnelling or any suitable mechanical technology or technology approved by Railway below ground at all depth under running traffic condition as per railway standard including carrying out survey work at the job site for determining underground cable trenches like telephone, cable, water and sanitary lines and resistivity test for finding the soil strata using necessary equipment’s for completion of works, mobilizing of machineries and specialized crew at the job site complete in all respect, including excavation of driven pit and exit pit (upto 3 metre depth) with proper protection at three sites with shoring sheets and ISMB`s. Providing MS cutting edges for front shield and Constructing thrust bed at designated level. Necessary de-watering and providing concrete foundation at the base of the driven pit, PVC/Rubber saddle as per the requirement of Railway Authority, crane for handing of pipe and any other machinery, tools, and tackles required, construction of temporary works as per requirement and as per approved by railway authorities, specification and the direction of the Engineer. (Protective coating/ lining if done that will be paid extra) Note- 1. Manual Pipe jacking is not permitted for workmen safety reasons. 2. Length of pipe shall be measured in between the outer wall of two manholes / Inspection chambers. Pipe in the manhole/inspection chamber’s wall shall deemed to be included in the item of manhole/inspection chamber shall not be payable
700 mm dia 12 mm thick casing pipe (As per SOR (RUIDP) item no. 17.87.1.2) | 40 | Per Metre | - | - |
| 4 | `HT Metering Panel: Supply Indoor Type 11KV VCB Control Cubical Panel with vertical Isolation Type Breaker as per Relevant IS as amended up to Date and Additional Specifications, having Capacities as Mentioned Below, Single break trip free mechanism, manually charged and Auto/Manually closing breaker suitable for use on 11kv, 3 phase 50hz AC, Supply with short circuit fault level of 500 Amps Capacity, breaker featured with local ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 2NO plus 2NC and equipped with following switchgears and accessories including making suitable structure arrangement for installation, control wiring and connections etc. as reqd. (1 IC plus 2 OG)
a). VCB, 11KV, 630Amp, 50KA.
b). 1ph 11KV/110 Volts PT (indoor type) Class 0.2 Accuracy and 100 VA burden -3 no’s.
c). 33KV indoor dead type dual core dual ratio 3CTs of ratio 200-100/5-5 A of 15 VA burden, PS 5 P10 and accuracy class 0.2.
d). Control panel- Cubicle type control panel suitable for floor mounting made out of 1.63 mm CR sheet duly powder coated and with following relays.
e). Microprocessor based numerical relay for O/L, E/F and SC Protection suitable for above.
f). Master trip relay -2 no’s.
g). Indicator type Annunciator panel with buzzer.
h). Digital Volt Meter- 0-11 KV.
i). Digital Amp Meter- 0-100 Amp.
j). RYB/ Trip/Closing/Spring charged indicator lamp.
k). Fault Annunciator panel for O/L, WTI, OTI and Buchhloz Relay Alarm And Trip Auxiliary relay.
l). TNC Switch for Operation.
m). Multifunction Meter EM6400NG.
n). TCS Relay for Safe
` | 2 | Job | - | - |
| 5 | Providing, fixing, lointing, testing of Mechanical joints complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion ets up to the site.
400 mm nominal diameter | 4 | NO. | - | - |
| 6 | Providing, fixing, lointing, testing of Mechanical joints complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion ets up to the site.
250 mm nominal diameter | 2 | NO. | - | - |
| 7 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables. (50 Sqmm size) | 60 | Per Metre | - | - |
| 8 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables. (95 Sqmm size) | 120 | Per Metre | - | - |
| 9 | Providing and laying Double Flanged (Screwed/ Welded) Centrifugally (Spun) cast Iron, class B (IS 1536) complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion etc up to the site of work.
350 mm nominal diameter | 32 | Per Mtr. | - | - |
| 10 | Providing, fixing, lointing, testing of Mechanical joints complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion ets up to the site.
300 mm nominal diameter | 2 | NO. | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.02 MB
BOQ_606642.xls
BOQ • 0.30 MB