Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.5 CrAccepted-AOC A 153 HQ CE EC KOLKATA LEKHAPANI POST TINSUKIA DIST ASSAM STATE | ₹6.5 Cr Quoted ₹6.6 Cr | L1 | Accepted-AOC Lowest bidder |
| 2 | L2₹6.7 Cr+₹11.4 L (1.74%)Rejected-Finance AT MAIN ROAD DANDAI PO PS DANDAI DIST GARHWA | LATEHAR | JHARKHAND | 822112 | ₹6.7 Cr+₹11.4 L (1.74%) | L2 | Rejected-Finance Other than lowest bidder |
| 3 | Rejected-Technical GATANGA MISSION CHARALI TEZPUR 784154 ASSAM | SONITPUR | ASSAM | 784154 | - | - | Rejected-Technical The firm is not enlisted in a(ii) category |
| Sl No | Description | Qty | Unit | M/s Singh enterprises L1 | ms singh construction L2 |
|---|---|---|---|---|---|
| 1.00 | SCHEDULE "A" Part - I
(BUILDINGS/STRUCTURES WORK)
Details of Buildings are given here-in-before:- | 1 | Lump sum | 4,29,00,000 ₹4,29,00,000 Lowest | 4,30,00,000 ₹4,30,00,000 |
| 2.00 | SCHEDULE "A" PART- II
(SITE CLEARANCE AND DEVELOPMENT)
Details of prepriced Schedule is given in tender documents | 1 | Lump sum | 12,90,000 ₹12,90,000 | 12,87,566 ₹12,87,566 Lowest |
| 3.00 | SCHEDULE "A" PART- III
( INTERNAL ELECTRIFICATION)
Details of prepriced Schedule is given in tender documents. | 1 | Lump sum | 28,500 ₹28,500 Lowest | 29,175 ₹29,175 |
| 4.00 | SCHEDULE "A" PART- IV
(ROADS)
Details of prepriced Schedule is given in tender documents. | 1 | Lump sum | 2,79,500 ₹2,79,500 Lowest | 2,89,496 ₹2,89,496 |
| 5.00 | SCHEDULE "A" PART- V
(EXTERNAL WATER SUPPLY)
Details of prepriced Schedule is given in tender documents | 1 | Lump sum | 6,07,550 ₹6,07,550 Lowest | 6,28,758 ₹6,28,758 |
| 6.00 | SCHEDULE "A" PART- VI
(EXTERNAL ELECTRIFICATION)
Details of prepriced Schedule is given in tender documents | 1 | Lump sum | 1,82,540 ₹1,82,540 Lowest | 1,98,226 ₹1,98,226 |
| 7.00SCHEDULE "A" PART -VII (MISCELLANEOUS ITEMS) Note:- This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col.' F ' signifies this fact only. | |||||
| 8.00 | INTERNAL ELECTRIFICATION
Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection including street light GI pipe bracket of medium grade 40mm dia. ,1.5m long bend to required size and shape including two coat of aluminum paint over a coat of red oxide primer complete in all respect all as specified and directed. | 2 | Each | 3,200 ₹6,400 | 3,000 ₹6,000 Lowest |
| 9.00 | M&L for earthing complete with galvanized steel earth plate electrode 600 mm X 600 mm X 6 mm thick buried directly in ground (earth pit not less than 2.25 Mtr deep below normal ground level with top edge of plate not less than 1.5 Mtr below normal ground level connected to galvanised earth lead wire 4.0 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No-3 SSR Part -1 2009 connected to earthing test point including earth wire protection pipe of dia 15 mm (medium grage), excavation and earth work, disposal of surplus spoil, provn of RCC cover 50 mm thick, reinforced with 8mm dia TMT bars @100 mm /C/C both ways with one handle for lifting made out of 10 mm dia TMT bar embedded in precast cover slab and PCC (1:3:6) type C-1 concrete pit, funnel with watering pipe 20 mm bore (light grade) testing on completion complete all as specified and directed.
[Note : (a) Proper earthing pit should be provided with pit cover.
(b) Excavation/earthwork is deemed to be included in the quoted rate.] | 2 | Each | 7,200 ₹14,400 Lowest | 7,500 ₹15,000 |
| 10.00 | EXTERNAL WATER SUPPLY
Supply and laying 3 layer ( inner antimicrobial, outer UV stabilized) ISI marked ,IS-15801, PP-R pipes SDR 11 (PN-10) and PP-R plain fittings in trenches/walls/ cellings or laying in floors complete of outer dia 160 mm size including all fittings complete all as specified and directed by Engr-in-charge. | 1,145 | RM | 3,200 ₹36,64,000 | 3,000 ₹34,35,000 Lowest |
Tender Value
₹4.7 Cr
EMD Value
₹5.4 L
Closing Date
31 Jul 2025, 6:00 pmClosed
CHIEF ENGINEER AF SHILLONG ZONE
HQ CHIEF ENGINEER AF SHILLONG ZONE MILITARY ENGINEER SERVICES ELEPHANT FALLS CAMP PO NONGLYER SHILLONG 793009
PROVISION OF RCC OH WATER TANK ALONG WITH IMPROVEMENT OF EXTERNAL WATER SUPPLY AT AFS DINJAN
2024_MES_680228_4
88661/DIN/E8
Open Tender
Civil Works
Lump-sum
545 days
Dinjan
As per tender documents
8 documents required · 8 mandatory
₹2,000
GE(AF) Mohanbari
₹5.4 L
Yes
20 Feb 2026
26 Jun 2025
2 Aug 2025
26 Jun 2025
31 Jul 2025
17 Jul 2025
Amount
SCHEDULE "A" Part - I (BUILDINGS/STRUCTURES WORK) Details of Buildings are given here-in-before:-
SCHEDULE "A" PART- II (SITE CLEARANCE AND DEVELOPMENT) Details of prepriced Schedule is given in tender documents
SCHEDULE "A" PART- III ( INTERNAL ELECTRIFICATION) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART- IV (ROADS) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART- V (EXTERNAL WATER SUPPLY) Details of prepriced Schedule is given in tender documents
SCHEDULE "A" PART- VI (EXTERNAL ELECTRIFICATION) Details of prepriced Schedule is given in tender documents
SCHEDULE "A" PART -VII (MISCELLANEOUS ITEMS) Note:- This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col.' F ' signifies this fact only.
INTERNAL ELECTRIFICATION Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection including street light GI pipe bracket of medium grade 40mm dia. ,1.5m long bend to required size and shape including two coat of aluminum paint over a coat of red oxide primer complete in all respect all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 600 mm X 600 mm X 6 mm thick buried directly in ground (earth pit not less than 2.25 Mtr deep below normal ground level with top edge of plate not less than 1.5 Mtr below normal ground level connected to galvanised earth lead wire 4.0 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No-3 SSR Part -1 2009 connected to earthing test point including earth wire protection pipe of dia 15 mm (medium grage), excavation and earth work, disposal of surplus spoil, provn of RCC cover 50 mm thick, reinforced with 8mm dia TMT bars @100 mm /C/C both ways with one handle for lifting made out of 10 mm dia TMT bar embedded in precast cover slab and PCC (1:3:6) type C-1 concrete pit, funnel with watering pipe 20 mm bore (light grade) testing on completion complete all as specified and directed. [Note : (a) Proper earthing pit should be provided with pit cover. (b) Excavation/earthwork is deemed to be included in the quoted rate.]
EXTERNAL WATER SUPPLY Supply and laying 3 layer ( inner antimicrobial, outer UV stabilized) ISI marked ,IS-15801, PP-R pipes SDR 11 (PN-10) and PP-R plain fittings in trenches/walls/ cellings or laying in floors complete of outer dia 160 mm size including all fittings complete all as specified and directed by Engr-in-charge.
Supply and laying 3 layer ( inner antimicrobial, outer UV stabilized) ISI marked ,IS-15801, PP-R pipes SDR 11 (PN-10) and PP-R plain fittings in trenches/walls/ cellings or laying in floors complete of outer dia 110 mm size including all fittings including taking down of existing old rusted/unserviceble 100/110mm dia GI Pipe with all old sluice valve, gate valve etc. complete all as specified and directed by Engr-in-charge.
Supply and laying 3 layer ( inner antimicrobial, outer UV stabilized) ISI marked ,IS-15801, PP-R pipes SDR 11 (PN-10) and PP-R plain fittings in trenches/walls/ cellings or laying in floors complete of outer dia 90 mm size including all fittings including taking down of existing old rusted/unserviceble 80/90 mm dia GI Pipe with all old sluice valve, gate valve etc. complete all as specified and directed by Engr-in-charge.
Supply and laying 3 layer ( inner antimicrobial, outer UV stabilized) ISI marked ,IS-15801, PP-R pipes SDR 11 (PN-10) and PP-R plain fittings in trenches/walls/ cellings or laying in floors complete of outer dia 63 mm size including all fittings including taking down of existing old rusted/unserviceble 50/63mm dia GI Pipe with all old sluice valve, gate valve etc.complete all as specified and directed by Engr-in-charge.
Supply and laying 3 layer ( inner antimicrobial, outer UV stabilized) ISI marked ,IS-15801, PP-R pipes SDR 11 (PN-10) and PP-R plain fittings in trenches/walls/ cellings or laying in floors complete of outer dia 32 mm size including all fittings and reducer for fitting with 20mm dia. float valve including taking down of existing old rusted/unserviceble 25/32mm dia GI Pipe with all old sluice valve, gate valve etc. complete all as specified and directed by Engr-in-charge.
Supply and fixing Sluice valve, flanged of class 1.6 PN , non-rising stainless steel Stem, bronze body seat ring 150 mm dia. complete all as specified and directed.
Supply and fixing Sluice valve, flanged of class 1.6 PN , non-rising stainless steel Stem, bronze body seat ring 100 mm dia. complete all as specified and directed.
Supply and fixing Sluice valve, flanged of class 1.0 PN , non-rising stainless steel Stem, bronze body seat ring 80 mm dia. complete all as specified and directed.
Material and Labour for constrution of valves pit chamber of size (900mm x 900mm x 900mm, internal ) using PCC (1:4:8) using 40 mm graded stone aggregate for foundation, 23 cm thick wall in CM (1:4), 10 mm thick rendering all around the brick work with CM 1:6, PCC (1:2:4) type B1 coping using 20 mm graded agregate for grouting, MS top sheet cover with locking arrangement including 50 mm pad lock with double key arrangement, MS frame out of 40 x 40x 5 mm thick angle iron, including painting of steel surface with two coats of synthetic enamel paint over a coat of red oxide primer finishing coat including necessary excavation in any type of soil, returing filling and removal of surplus soil to a distance not exceeding 50 mtrs, complete all as specifeid and directed.
Drilling of bore of 150mm and development of bore for 60 meter tube well below ground level by reverse rotary circulation method machine 150 mm bore size top to bottom by different cutters including all arrangement with appliances and excavation of pit for clay for circulation of water using bentonite or silty clay as per site of soil condition for settlement of bore hole for the depth upto 60 meter tube well below ground level from the top of the ground complete all as specified and directed.. (Note - (i) The quoted rate shall be deemed to be inclusive of the cost of drilling ,pumps and fittings. etc used in the process of drilling shall be provided by the contractor under his own arrengement for execution of the work. (ii) In case of non extraction of casing pipe due to failure of borewell the contractor will have no claim what so ever on this account)
Drilling of bore of 150mm and development of bore from 60 meter to 120 meter tube well below ground level by reverse rotary circulation method machine 150 mm bore size top to bottom by different cutters including all arrangement with appliances and excavation of pit for clay for circulation of water using bentonite or silty clay as per site of soil condition for settlement of bore hole for the depth from 60 meter to 120 meter tube well below ground level from the top of the ground complete all as specified and directed.. (Note - (i) The quoted rate shall be deemed to be inclusive of the cost of drilling ,pumps and fittings. etc used in the process of drilling shall be provided by the contractor under his own arrengement for execution of the work. (ii) In case of non extraction of casing pipe due to failure of borewell the contractor will have no claim what so ever on this account)
Drilling of bore of 150mm and development of bore from 120 meter to 180 meter tube well below ground level by reverse rotary circulation method machine 150 mm bore size top to bottom by different cutters including all arrangement with appliances and excavation of pit for clay for circulation of water using bentonite or silty clay as per site of soil condition for settlement of bore hole for the depth from 120 meter to 180 meter tube well below ground level from the top of the ground complete all as specified and directed.. (Note - (i) The quoted rate shall be deemed to be inclusive of the cost of drilling ,pumps and fittings. etc used in the process of drilling shall be provided by the contractor under his own arrengement for execution of the work. (ii) In case of non extraction of casing pipe due to failure of borewell the contractor will have no claim what so ever on this account)
Reaming of bore well from 150 mm dia to 525 mm dia. hole in three steps from 150 mm to 350 mm, 350 mm to 450 mm and 450 mm to 525 upto 60 m depth below the ground level from the top of ground complete all as complete and directed.
Reaming of bore well from 150 mm dia to 525 mm dia. hole in three steps from 150 mm to 350 mm, 350 mm to 450 mm and 450 mm to 525 from 60 m to 120 m depth below the ground level from the top of ground complete all as complete and directed.
Reaming of bore well from 150 mm dia to 525 mm dia. hole in three steps from 150 mm to 350 mm, 350 mm to 450 mm and 450 mm to 525 from 120 m to 180 m depth below the ground level from the top of ground complete all as complete and directed.
M & L for electric logging of bore well complete incl all tools and fixture required for same complete all as complete and directed.
Supply and fixing mild steel bail plug assembly suitable for 200 mm bore casing pipe internal threaded with strong iron hook, screwed and welded to casing pipe as per IS 2800 complete all as specified and directed.
Supply and fixing mild steel reducer suitable for 200x300 mm bore casing pipe fitted to casing pipe as per IS 2800 complete all as specified and directed.
Supplying assembling lowering and fixing mild steel ERW casing pipe 300 mm internal dia ISI marked having wall thickness 7.1 mm screwed and socketed in length upto 6 m, complete all as specified and directed.
Supplying assembling lowering and fixing mild steel ERW casing pipe 200 mm internal dia ISI marked having wall thickness 7.1 mm screwed and socketed in length upto 6 m, complete all as specified and directed.
Supplying assembling lowering and fixing low carbon galvanized (LCG) steel strainer pipe ( slotted pipe ) 200 mm nominal bore of wall thickness 7.10 mm cage type wire wound screen ‘V’ shaped profile in suitable length having slots of size 0.75 mm width including necessary end coupling, complete all as specified and directed.
Supply and filling pea gravel of size 2 to 4.5 mm for packing around the housing/assembly, slotted pipe of the bore well complete all as specified and as directed. Note:- Pea gravel shall be paid as per stack measurment carried out on site.
Development of tube well with air compressor also operated with DG set of capacity 150 psi /1000cum till sand/mud free water of potable qualily is obtained and to achieve minimum discharging capacity of 20000 LPH complete all as specified and as directed . (Note:- Compressor with accessories and fuel shall be arranged by the contractor and same is included in the unit quoted rate )
Yield testing of the tube well by suitable pump and motor for minimum discharge capaity of 20000 LPH for at least continuous 16 hour uninterrupted of run per day for three continuous days complete all as specified and directed. Note : 'V' notch and other equipment including pump set shall be arranged by the contractor and cost of same is to be included in the unit rate quoted)
Supply & fixing pressure gauge with isolation cock suitable for a working pressure of zero to 100 Kg/SqCm (Liquid based High Intensity), complete all as specified and as directed .
Supply, lowering, commissioning and testing of manufacturer assembled and electric driven submersible pump set mix flow type with high graded CI bowl, stainless steel shafts, bronze impellers etc. of pump dia. 200 mm capable to deliver 850 LPM clear water at 79 Meter head with electric motor 200 mm dia three phase 415 volt of cap 25 HP (18.5 KW) as per, OEM recommendations suitable for 100 mm delivery pipe complete all as specified and directed by Engr in charge.
Supplying, laying, jointing and testing of PVC insulated submersible cable of 10 Sqmm 3 core flat LT 1100 volt grade heavy duty ISI marked with copper conductor and overall served with an outer sheath of PVC complete along the column pipe or passing through pipes or laid under floor of through walls etc . complete all as specified and directed by Engr in charge.
S&F round strand steel wire rope RHO/LHO/RHL/LHL conforming to IS: 2266/02, 12 mm dia., 1770 N/mm² tensile strength and connected clamp nut bolts fixed complete all as specified and directed by Engr in charge.
Supply and lowering MS column pipe (medium grade) confirming to IS of size 100 mm dia bore approx 3 m length each duly both ends flanged/ drilled by welding with special provision such as MS clamps and MS flange (size shall be as per IS specifications) and should have two cuts for fixing submersible cable and connecting complete with rubber gasket and nuts bolts etc complete and painted internally and externally with two coat of non corrosive non toxic bituminous paint complete all as specified and directed by Engr-in-Charge.
Supply and fixing of double flanged CI ventury of size 100 mm dia including one No. ferrule at no pressure zone complete in existing line complete all as specified and directed by Engr-in-Charge.
M&L for chemical dosing pump operated on single phase 230V, 50 Hz power supply high pressure single head gear motored adjustable with self priming suitable for interchangeable pump tubes and sub assemblies, mechanical control adjustable from 5% to 100% with non clogging capacity, pumping against pressure of up to 100 psi ,mounting (vertical or horizontal) complete with 100 ltrs PE/FRP tank with lid, level Gauge and rain shed cowl complete all as specified and directed by Engr-in-Charge.
Designing supply,installation, testing commissioning iron removal pressure feed type filtration plant 10000 GPH to withstand to pressure 10 Kg/cm sq with catalytic and filtration media (as required size and grade/mesh to obtain potable water recommended parameters) including MS frontal pipe(duly welded) ,cocks, valves (inlet, outlet, back wash, rinse and bypass complete as per manufacture's instruction) provision of man hole, hand hole strainer including air vent system, coagulant feeder with accessories, oxidation chamber with media (MnO2) with all accessories suitable capacity with all fittings fixture, pressure gauge, RCC/PCC foundation as per OEM recommendation, drainage system and connected to rising and delievery system including painting and writing complete. The technical detail of oxidation chamber and multigrade filter are as given below-
Item No. 41.00 Contd... Oxidation Chamber Feed Flow- 45 cum/hr Operating pressure- 3.5 kg/sq cm Max allowable pressure drop- 1.5 Kg/sqcm vessel sie in mm- 800X 1000 mm Material of vessel- MS Frontal pipe line size- 100 mm Media Type- Maganese di oxide Thickness in mm-(Shell and dish ends)- 8 mm Media Quantity- 800 Kg Multigrade filter Flow rate- 45 cum/hr Operating pressure- 3.5 Kg/sq cm Max allowable pressure drop- 1.5 Kg/sqcm Continuous duty cycle- 48 hrs Backwash- 20 min Rinsing- 10 min Filtering media detail- Media type- Mixed Sand Depth of sand- 1600 Kg Depth of gravels support- 2000 Kg Gurenteed life of filtering media- one year Vessels Details- Type cylinder- Vertical Dimentions I mm ( DiaXHeight)- 1800X2300 mm Free boared for back wash- 50% Materials- MS, Thicness in mm (shell and dish end)- 8/10 mm
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed by Engr-in-Charge.
Chemical analysis (turbudity, PH total hardness, iron, chlorine, sulphates, Fluorides, Nitrates, Calcium, Arsenic) of raw water( before filteration and after filteration) for borewell from Govt approved laboratery including collection of water sample from newely constructed borewell at air force station dinjan and submission the sample at Govt laboratery, and submit the test report at AGE E/M subdivision mohanbari complete all as specified and directed by engr-in-charge.
Cutting or screwing existing steel/PPR tubing for alteration or additions suitable size for 110/160 mm dia complete all as specified and directed
Cutting or screwing existing steel/PPR tubing for alteration or additions suitable size for 90/63 mm dia complete all as specified and directed
Cutting or screwing existing steel tubing for alteration or additions suitable size for 32 mm dia complete all as specified and directed
M&L for providing, testing and commissioning of 150mm bore(Nominal bore) for medium class MS flanged pipe bearing specification as per IS: 1239 marked with all necessary fittings like tees, elbows, flanges, reducers, gaskets, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary MS structural supports & clamping arrangement complete all as specified and as directed.(For inlet/ outlet and washout line from filter to OH tank.)
EXTERNAL ELECTRIFICATION Supply, installation, testing and commissioning of silent engine generating set with accoustic enclosure as per latest CPCB Norms 415 volts 35 KVA, 3 phase, 0.8 Power Factor, 50 Hz, 1500 RPM, self excited, self regulated, brushless AC generator with Monitoring cum AMF panel including accoustic enclosure conforming to condition under BS,5514/ IS 10002 with latest ammendment in IS code and including the requirement mentioned below:- (A) Alternator:- Standard design alternator rated 35 KVA, 0.8 (lag) Power Factor AC, 3 Phase-4 wire, 415 volts, 50 Hz, 1500 RPM, self excited, self regulated, screen protected, IP 23 enclosure, brushless design with winding in pole faces, insulating class `H' and voltage regulation of +/- 1% at rated voltage from no load to full load. The alternator shall be conforming to BS 2613/ 5000.
Item No. 49.00 Contd... (B) Diesel Engine:- Adequate capacity of diesel engine after deducting site (AF Stn Dinjan) de-rating factor, liquid cooled to drive independently above alternator and accessories directly coupled through flexible coupling multi cylinder, multi stroke, direct injection, cold starting, 1500 RPM as per relevant ISI/ BS 5514 with standard accessories all as specified and required for safe handling and operation. Salient features of accessories shall be as under:- (i) Fly wheel with housing (ii) Cooling system : Moulded radiator with fan & belts. (iii) Cooling water pump : Centrifugal type belt driven (iv) Exhaust system : Exhaust system complete with exhaust pipe and asbestos rope for safe exhaust. (v) Exhaust gas: Turbo charge type (vi) Fuel system: Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by governor for speed/ frequency regulations, fuel filters, fuel hoses. (vii) Lub oil system :- (a) Lubricating oil filter (b) Lubricating oil pump (viii) Air Intake system :- (a) Air cleaner dry type (b) Air cleaner dry type (ix) Staring system : Electric self starter with suitable battery & lead as recommended by OEM including battery charging alternator. (x) Sailent features of accessories shall be as under:- (aa) Radiator with blower fan (ab) Corrosion inhibitor coolant (ac) Paper element filters for fuel, lub oil and by pass (ad) Electronic/ mechanical governor controlled direct fuel ijection system (xi) AVM pads built or separtely mounted to manufactrer base frames.
Item No. 49.00, 50.00 & 51.00 Contd... (E) Fuel Tank:- Minimum of capacity to run continuous 8 Hours on full load with necessary all fittings installed inside the enclosure. (F) Accoustic Enclosure:- Manufactured by OEM of DG set suitable for 35 KVA DG Set as per latest rules and regulations of Ministry of Environment & Forest and Pollution Control Board Norms with external emergency stop push button. (G) Testing:- The DG set shall be tested for a period not less than 12 hours continuously out of which at least one hour each on No Load and two hours each on 25%, 50% and 75 % of rated full load, four hours on rated full load and one hour on 10% in exceess of rated full load. Necessary load bank and all instruments, consumable stores like POL, diesel, engine oil, grease required for carrying out the tests including manpower shall be provided by the contractor and no extra payment shall be paid to the contractore for this. (H) Note:- (i) The DG set battary and Generator Monitoring Panel cum AMF Panel shall be inside the enclosure. (ii) The enclosure should be properly illluminated by suitable LED lamp fittings. (iii) Rate quoted shall be deemed to be inclusive of cable and terminations from Alternator to AMF Panel with necessary fixing arrangements. (iv) The quoted rate shall be deemed to be inclusive of first fill of oil and final successful acceptance test. The rate includes PCC foundation and frame work including necessary earth work as per OEM recommendation with extra 0.50 meter all around DG set as working space complete all as directed by Engr-in-Charge.
Supply, install, testing and commissioning of LT outdoor Feeder Pillar Box AC 415 V, 50 Hz 3 Phase 4 wire, totally enclosed self supporting structure / cubicle, fully compartmentalized type, weather proof, protection IP 54 suitable for outdoor use double door type, with bottom cable entry with suitable cable glands structure made out of 3.15 mm thick CRCA steel sheet of minimum size ( 1.2x1.0 x 0.6) m with angle iron frame work and legs of ISA 50X50X5 mm, with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter, changeover switch and MCCBs with sloping canopy at top, double hinged doors at front with suitable locking arrangement including louvers at sides duly powder coated complete for accomodating & including following accessories:- (For new RCC Tank pumphouse near DSC Md Accn)
M&L for earthing complete with galvanised steel earth plate 600mm x 600mm x6mm thick elecrode and 32mm x 6mm galvanised iron strip as earthing lead burried directly in ground vertically (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level, the earth plate surrounded by adequate quantity of charcoal dust and common salt to a packed thickness of 15 cm on all sides connected to GI strip 32mm x 6mm as earth lead by means of bolts, nuts, check nuts and washers (including welding) of galvanised iron or steel and connected to main switch board / panel/ test point at the other including necessary earth work in any type of soil, returning filling in and removal of surplus soil, concrete pit in PCC (1:3:6) type C1, pre cast RCC 1:2:4 type BI cover slab 54cm x 54cm x 5cm reinforce with 8mm dia bar TMT @150mm centre to centre both ways with one handle for lifting made out 8mm dia MS bar with wire mesh funnel, 20mm GI tubing medium grade for watering and 40mm GI tubing light grade for protection, test point, testing on completion all as shown in Electrical Plate No 3 of SSR Part-I complete all as specified and directed.
M&L for earthing complete with copper plate 600mm x 600mm x 3mm thick electrode and 20mm x 3mm copper strip as earthing lead burried directly in ground vertically (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level, the earth plate surrounded by adequate quantity of charcoal dust and common salt to a packed thickness of 15 cm on all sides connected to copper strip 20 x 3mm as earth lead by means of tinned copper/ brass bolts, nuts, check nuts and washers (including brazing) connected to main switch board / panel/ test point at the other including necessary earth work in any type of soil, returning filling in and removal of surplus soil, concrete pit in PCC (1:3:6) type C1, pre cast RCC 1:2:4 type BI cover slab 54cm x 54cm x 5cm reinforce with 8mm dia bar TMT @150mm centre to centre both ways with one handle for lifting made out 8mm dia MS bar with wire mesh funnel, 20mm GI tubing medium grade for watering and 40mm GI tubing light grade for protection, test point, testing on completion all as shown in Electrical Plate No 3 of SSR Part-I complete all as specified and directed.
Supply and fix LED street light 45 W with minimum lumen of 4500Lm, PF >0.95 new generation energy saving and environmental friendly long life made up of pressure diecast aluminium housing with high power LED as lighting source cover having driver compartment with IP66 protection and impact resistance with built-in surge protection device suitable for mounting pole including street light GI pipe bracket of medium grade 40mm dia. ,1.5m long bend to required size and shape including two coat of aluminum paint over a coat of red oxide primer complete in all respect all as specified and directed.
Supply and fixing cable junction boxes IP 66 “halogen free and weather proof” for outdoor installation (with metric knockouts for cable entry) of minimum size 225 x 295 x 125 mm for 16/25 sqmm fixed to pole /wall with suitable FI clamp 20X3 mm nuts, bolts and washers including provision of 01 No miniature circuit breaker (MCBs) single pole , 240 volts 10 kA, 10 Amps and including minium 200 Amps aluminium busbar (04 Nos) with nuts, bolts & washers complete all as specified and as directed.
Supply and fixing PVC insulated and PVC round sheathed, copper conductor industrial cable 1.5 sqmm, three core of copper conductor for connection of street light fittings on pole/ wall/ pillar from junction box including termination clip etc. complete in all respect including through GI tubing of size 20mm dia complete all as specified or directed.
Note:- Schedule of credit (Sch 'A' Part-VIII) amount of Rs 2,92,300.00 shall be deducted from the total quoted amount of BOQ.
ms singh construction (BID ID -3362678)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tenderdocument.rar
Tender Documents • 23.59 MB
Tenderdocument.pdf
Tender Documents • 2.71 MB
Tenderdocument_2.rar
Tender Documents • 10.21 MB
BOQ.xls
BOQ • 0.42 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .