| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.1 CrAccepted-AOC OPP SHRI NAVNIKETAN H S SCHOOL CHHOLA KANCHI BHOPAL M P | BHOPAL | MADHYA PRADESH | 462010 | ₹8.1 Cr Quoted ₹8.2 Cr | L1 | Accepted-AOC Being Lowest and overall reasonable |
| 2 | L2₹9.1 Cr+₹88 L (10.7%)Rejected-Finance | ₹9.1 Cr+₹88 L (10.7%) | L2 | Rejected-Finance Being NOT Lowest |
| 3 | L3₹10.9 Cr+₹2.6 Cr (32.2%)Rejected-Finance | ₹10.9 Cr+₹2.6 Cr (32.2%) | L3 | Rejected-Finance Being NOT Lowest |
Tender Value
₹8.7 Cr
EMD Value
₹7.6 L
Closing Date
28 May 2022, 6:00 pmClosed
HQ CHIEF ENGINEER BHOPAL ZONE, BHOPAL
HQ CHIEF ENGINEER BHOPAL ZONE, MILITARY ENGINEER SERVICES, SULTANIA INFANTRY LINES, BHOPAL - 462001
PROVN OF OTM ACCN FOR 21 CORPS DENTAL UNIT AT BHOPAL.
2022_MES_507852_1
CEBZ/TOKEN/17 OF 2021-22
Open Tender
Civil Works
Lump-sum
540 days
BHOPAL
As per NIT
5 documents required · 5 mandatory
₹3,000
Yes
GE DRONCHAL
₹7.6 L
Yes
HQ CHIEF ENGINEER BHOPAL ZONE, BHOPAL
27 Jul 2022
14 Feb 2022
4 Jun 2022
14 Feb 2022
28 May 2022
12 May 2022
3 Mar 2022
Amount
Note:-(i) Please refer schedule 'A' notes before quoting the tender. (ii) Amount of Schedule of credit shall be deducted off line by the department.
GENERAL SUMMARY
Lump sum price worked out by the contractor for BUILDING WORK as listed in Schedule ‘A’ Part- I (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for INTERNAL WATER SUPPLY as listed in Schedule ‘A’ Part- II (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for INTERNAL ELECTRIFICATION as listed in Schedule ‘A’ Part- III (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for EXTERNAL WATER SUPPLY as listed in Schedule ‘A’ Part- IV (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for HOT WATER SUPPLY as listed in Schedule ‘A’ Part- V (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for EXTERNAL ELETRIC SUPPLY as listed in Schedule ‘A’ Part- VI (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for ROAD/CULVERT as listed in Schedule ‘A’ Part- VII (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for AREA DRAINAGE as listed in Schedule ‘A’ Part- VIII (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for SEWAGE DISPOSAL as listed in Schedule ‘A’ Part-IX (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for SECURITY FENCING AND GATE as listed in Schedule ‘A’ Part- X (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for RETAINING WALL as listed in Schedule ‘A’ Part- XI (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for FIRE DETECTION AND ALARM SYSTEM as listed in Schedule ‘A’ Part- XII (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for EXACAVATION, EARTH WORK & SITE DEVELOPMENT as listed in Schedule ‘A’ Part- XIII (Ref prepriced schedule attached seperately)
PRIME COST SUM Provide Prime cost sum for "Designing, supply and fixing Medical Gas System" for Sch "A" Part- I Serial Item No.1 (Corps Dental Unit Bldg) complete . (i) Add/deduct __________% (Contractor to quote lumpsum amount which will be converted to percentage over /below) NOTE:- Amount quoted by the contractor shall not exceed 15% above the amount inserted in Col-6. However contractor may quote lower amount than inserted in Col-6. If contractor quotes amount more than 15% then it will be reduced/revised to 15% only.
PROVISIONAL LUMP SUM NOTE:- (a) This sum shall be executed wholly or in part as directed by the GE and the work shall be carried out to the extent ordered in writing by the GE. The work under provisional lump sum shall be measured and paid for at the applicable (or prorata) rate in MES schedule adjusted by the percentage quoted by the contractor. (Contractor to quote lumpsum amount which will be converted to percentage over /below)
Serial Iterm No.2.15 (Contd/-):- (A) Provide provisional lump sum for :- (a) Cabinet/working platform with counter top, alongwith requiste accessories and sink with drain board and pillar tap as required and all as directed by GE for the following rooms :- (i) Recovery Room with day care centre - 01 No (ii) Autoclave - 01 No (iii) Specialist Surgery Room (1) to (4) - 04 Nos (iv) General Surgery - 01 No (v) Dental Hygenist Surgery (1) to (5) - 05 Nos (vi) Ceramic room - 01 No (vii) Dental mech lab + casting room + acrysliation room + pack and issue room - 01 No (viii) CAD/CAM room, inplants, MF prosthesis, ortho appl, dressing room, etc - 01 No (i) Add/deduct _____% (Contractor to quote lumpsum amount which will be converted to percentage over/below)
SCH 'A' Pt - XIV (MISCELLANEOUS ITEMS)
INTERNAL ELETRIFICATION NOTE:- For items of internal Electrifications notes given at the beginning of Sch ‘A’ Part-III (internal Electrification) shall also be applicable.
M&L for Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with 1.5sq mm nominal cross sectional area PVC insulated unsheathed multi-stranded FRLSH copper conductor 1100 volts grade, drawn in and including medium grade, rigid PVC concealed conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked with valid CML No.(IS-9537-1983 for conduits and IS:3419:1976 for conduit accessories), and including provision of modular metal flush boxes with modular frame plate and white cover for housing switch, sockets, regulators, etc including 1.5 Sq mm nominal cross sectional area PVC insulated unsheathed multi-stranded FRLSH copper conductor cable as earth continuity conductor to common earth dolly complete all as specified and directed for the following:- NOTE:- The quoted unit rate is deemed to be inclusive of cost of metal flush boxes, modular white cover plates, modular frame plates, etc.
One light point/ bell point controlled by one 5/6 amps one way modular switch.
One ceiling /exhaust fan point controlled by one modular switch and regulator.
One bell/buzzer point controlled by one modular bell push.
One light point controlled by two 5/6 amps two way modular switchs.
One Socket outlet, three/five pin, 5 Amp, controlled by one 5/6 amps one way modular switch or modular switch/socket combination 5 amps, 5 pin on the same board with other switches, sockets, fan regulators, etc.
One Socket outlet, three/five pin, 5 Amp, controlled by one 5/6 amps one way modular switch or modular switch/socket combination 5 amps, 5 pin on independent board.
M&L for Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi-stranded copper FRLSH conductor 2.5 Sq. mm nominal cross-sectional area, single core, PVC insulated and unsheathed cable 1100 volts grade, ISI-694 marked with valid CML No., drawn in and including medium grade, PVC concealed conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked with valid CML No.(IS-9537-1983 for conduits and IS:3419:1976 for conduit accessories) with and including provision of modular metal flush boxes with modular frame plate and white cover for housing switch, sockets, regulators, etc including 1.5 Sq mm nominal cross sectional area PVC insulated unsheathed multi-stranded FRLSH copper conductor cable as earth continuity conductor to common earth dolly complete all as specified and directed for one 3/5 pin amps 15/16 Amp socket outlet independent complete all as specified and directed.
S&F LED lamp 9/10 W, Pin type B 22, 230V AC, 50 Hz single phase including bakelite batton holder with all fitting fixing accessories complete all as specified and directed. Notes: 1. Warranty for replacement of each LED shall not be less than 05 years from the date of purchase. 2. Date of Purchase shall be marked on each fixture with permanent marker for redeeming warrenty benifits.
S&F 2 X LED lamp 1W, Pin type, 230V AC, 50 Hz single phase (red & green colour) including bakelite batton holder with all fitting fixing accessories complete all as specified and directed. Notes: 1. Warranty for replacement of each LED shall not be less than 05 years from the date of purchase. 2. Date of Purchase shall be marked on each fixture with permanent marker for redeeming warrenty benifits.
S&F Air Ventilation fan 200mm sweep, 230V, AC, 50 Hz, single phase, plastic body complete with all fittings all as specified and directed.
S&F Air Ventilation fan 150mm sweep, 230V, AC, 50 Hz, single phase, plastic body complete with all fittings all as specified and directed.
Design, supplying, installing, testing and commissioning LT power distribution panel board, powder coated, indoor, double door, IP - 53 type panel board, factory fabricated cubical type, weather vermin proof with locking arrangement; fabricated and made out of MS CRCA sheet 2.00mm thick for outer shell & 2.0 mm thick for inner shell, ISMC 75 x 40mm for base alongwith angle iron frame made out of 50 x 50 x 6mm angle iron complete with 400 Amps rated aluminium bus bar 4 strip naturally cooled inside sepreate chamber and compartmentalised cabinet for housing and mounting MCCBs, metering eqipments prewired with suitble size of copper conductor duly marked the incoming & all outgoing controls and comprising with the following:-
S&F LED street light fitting, minimum capacity of 25W, made up of pressure die cast aluminium housing with high efficency LED as lighting source and lens with toughned glass having bottom seperate driver compartment with IP 66 protection and impact resistance of IK 07, etc and all accessories prewired with & including mounting bracket of 40mm bore light grade pipe of required length and shape including bending, forging or welding, etc and suitable bolts, nuts, washeres, etc and connecting with PVC insulated multi stranded copper flexible cable of size 0.5 sqmm, three core from ceiling rose to fitting complete all as specified and directed. Notes: 1. Warranty for replacement of each LED shall not be less than 05 years from the date of purchase. 2. Date of Purchase shall be marked on each fixture with permanent marker for redeeming warrenty benifits.
S&F in replacement VTPN, 8 way, Distribution board, double door, vertical type including fixing and connecting of MCCBs/MCBs/ Isolator/ELCBs, etc factory made, confirming to IS: 13032 fabricated out of CRCA sheet not less than 1.2 mm thick fitted with DIN channel, neutral link and 200 Amps 440 volts rated bus bar. DB shall be semi glossy finished with epoxy polyester based powder paint sprayed and baked at high temperature, between powder painting process the sheet steel having to go through the anti-rust conditioning in not less than seven tank process to ensure smooth finish and protection against corrosive atmosphere. The DB shall be double door type with hinged door with locking arrangement. The DB shall be of same make as MCBs /Isolator. DB shall also be provided with label marking indicating the incoming and outgoing circuits. The DB shall be of IP 43 protection class complete all as specified and as directed. NOTE:- MCCBs/MCBs shall be measured and paid seperatly.
S&F in replacement VTPN, 6 way, Distribution board, double door, vertical type including fixing and connecting of MCCBs/MCBs/ Isolator/ELCBs, etc factory made, confirming to IS: 13032 fabricated out of CRCA sheet not less than 1.2 mm thick fitted with DIN channel, neutral link and 200 Amps 440 volts rated bus bar. DB shall be semi glossy finished with epoxy polyester based powder paint sprayed and baked at high temperature, between powder painting process the sheet steel having to go through the anti-rust conditioning in not less than seven tank process to ensure smooth finish and protection against corrosive atmosphere. The DB shall be double door type with hinged door with locking arrangement. The DB shall be of same make as MCBs /Isolator. DB shall also be provided with label marking indicating the incoming and outgoing circuits. The DB shall be of IP 43 protection class complete all as specified and as directed. NOTE:- MCCBs/MCBs shall be measured and paid seperatly.
S&F MCCB, TPN, 200A, 35 kA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting including spreader terminals and phase barriers complete all as specified and directed.
S&F MCCB, TPN, 80A, 16 kA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting including spreader terminals and phase barriers complete all as specified and directed.
S&F MCCB, TP, 32 A, 16 kA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting including spreader terminals and phase barriers complete all as specified and directed.
S&F MCB SPN, 40 Amp, 240 volts AC confirming to IS: 13947-3 and IEC-60898 'C' Curve type, breaking capacity 10 kA complete all as specified and directed.
S&F MCB SPN, 6 to 32 Amp, 240 volts AC confirming to IS: 13947-3 and IEC-60898 'C' Curve type, breaking capacity 10 kA complete all as specified and directed.
S&F MCB SP, 6 to 32 Amp, 240 volts AC confirming to IS: 13947-3 and IEC-60898 'B' Curve type, breaking capacity 10 kA complete all as specified and directed.
S&F MCB SP, 40 Amp, 240 volts AC confirming to IS: 13947-3 and IEC-60898 'B' Curve type, breaking capacity 10 kA complete all as specified and directed.
M&L for Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR-2009 Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by 15mm dia light grade GI pipe and watering pipe shall be 20mm bore light grade including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover with handle of 8 mm dia bar, charcoal/salt, funnel with wire mesh etc complete all as specified and directed. NOTE :- (i) The concrete pit (to be provided atleast 500mm away from earth pit) shall be PCC (1:3:6) type C-1, 40 mm thick pre cast cover slab of RCC (1:2:4) type B-1 using 20mm graded stone aggregate reinforced with 8mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I. (ii) The unit rate includes the cost of GI pipe light grade for protection of earth wire and 4mm dia earh lead wire upto 7.5 M.
S&F Telephone RJ 11 Socket, modular type, 1 module with & including MS/PVC concealled flush box complete all as specified and as directed.
S&F LAN RJ 45 Socket, modular type, 1 module with & including MS/PVC concealled flush box complete all as specified and as directed.
S&F LED lights fitting 1 x 20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.
S&F LED light fitting 1 x 9/10 watt tube light fitting, 2 feet length complete suitable for surface mounting on wall including connecting with PVC insulated multi-stranded opper flexible cable 0.5 sqmm nominal cross-sevtion area, 2 core, type of housing aluminium complete all as specified and as directed.
S&F round/square shape 15 watts 230 volts AC recessed/surface mounted with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with 2/3 core flexible copper conductor cable of suitable size and type of housing aluminium complete all as specified and as directed.
S&F round shape 6 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with 2/3 core flexible copper conductor cable of suitable size complete all as specified and as directed.
EXTERNAL WATER SUPPLY--
BLANK
Supplying, fixing and testing of DI pipe fittings (specials) heavy duty for any type (flanged/socketed) pipes such as bends (any type radius, and angle), tapers, any type straight bend, increasing,decreasing, or double socket etc) Tee pieces, ring branch, 'Y' junction double branch, Cross (all socket or socket and spigot), collors, caps and plugs, adopters etc of any size radius and lenght confirming to IS specifications with external bitumen coating and internal cement mortar lining and metalic zinc coating up to 150mm bore complete all as specified & directed.
M&L for cutting existing DI pipe line 250mm bore and with & including inserting new DI tee of size 250mm x 250mm x 80mm and all necessary fittings, mechanical & lead joints (as required at site), gaskets, nuts bolts, earth work, etc complete all as per site requriement and all as specified and directed. Note: The cost of earth work, cuting, new CI tee, CI fittings including lead joints, mechanical joints as required at site are deemed to be included in quoted unit rate.
M&L for construction of brick masonary valve pit chamber with 100mm thick PCC 1:4:8 type D2 lean concrete foundation using 40mm graded stone aggregate providing well burnt brick masonary wall of 23mm thick built in CM 1:6 rendering in cement 1:6 finished even smooth using extra cement internally and 20mm thick in CM 1:4 and finished fair and even supply and fix 3.15 mm thick MS sheet steel cover fixed on 40mm x 40mm x 6mm thick angle iron frame embbeded in PCC coping with locking arrangement and 1 Nos 50mm size 4 levers lock with key in duplicate Standard size and MS hold fast and handle made out of 25 x 6mm flat iron appplying two coats of synthetic enamel paint of approved shade over a coat of primer (Red Oxide) to all exposed surface making good all disturbed surface to match surrounding complete all as specified and directed. The valve pit chamber shall be following sizes:-
900 mm x 900 mm x 1000 mm size
600 mm x 600 mm x 900 mm size
HOT WATER SUPPLY--
EXTERNAL ELECTRIC SUPPLY
S&F LED street light fitting pressure dia cast aluminum housing IP-66 with all accessoreis of 70/71//72 Watt 240 Volt, 50 Hz complete with connection from junction box to fitting connecter with suitable multistranded copper conductor cable of 2.5 Sqmm, 3 core; with & including fixing on 32 mm bore (or next suitable size) light grade GI pipe bracket, 1.20 mtr long, bent to shape by cutting, welding and well finishing including MS clamps of flat iron of size 25 x 5 mm of suitable length - 2 nos complete for steel tubular poles with nuts, bolts and painting with two coats of aluminium paint over a coat of primer on MS clamp complete all as specified and directed.
S&F street light Engineering plastic one piece moulding control box (size- 350 x 250 x 150mm) with locking arrangment made out of HDPE and FI clamp 25 x 3 mm complete with & including 1 No - MCB, SP, 6 Amp, 240 Volts and 04 Nos aluminum busbar of rating 63 amps for phase and neutral on porcelain based insulators and fixing clamps to pole for street lights all as required complete all as specified and directed.
S&F post top lantern type external light fitting complete including junctin box with MCB, wiring from junction with and including LED 40 watts Copper dust finish cast aluminium spigot and spun aluminium canopy fixed with opal polycarbonate inclosure, etc including earthwork, GI Pipe light grade 50 mm bore 2.8 m long embedded 300mm in PCC bed block 1:2:4 type B1 using 20 mm graded stone aggregates (size of bed block 300 x 300 x 300mm) including all necessary earth work & foundation work complete all as specified and directed.
S&F construction of platform for installation of transformer of size not less than 2.0m x 2.0m x 2.5m with & including excavation in any type of soil 30 cm below ground level, PCC M-10 ( Nominal Mix ) in foundation, 100mm thick PCC M-15 (Nominal Mix) over 150 mm thick Hard Core of Broken stone boulder over rammed earth filling in floor, stone masonry work in cement mortar 1:4, 15 mm thick plaster using cement mortar 1:4 and applying two coats of colour wash over one coat of white wash complete all as specified and directed.
M&L for Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR-2009 Part-I connected to test point or main switch board or main control board all as specified and testing on completion including provision of earth strip protection by 40mm dia light grade GI pipe and watering pipe shall be 20mm bore light grade including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover with handle of 8 mm dia bar, charcoal/salt, funnel with wire mesh etc complete all as specified and directed. NOTE :- (QUANTITY- 12 NOS FOR EXT ELECT + 02 NOS FOR FIRE DETECTION & ALARM SYSTEM = 14 NOS) (i) The concrete pit (to be provided atleast 500mm away from earth pit) shall be PCC (1:3:6) type C-1, 40 mm thick pre cast cover slab of RCC (1:2:4) type B-1 using 20mm graded stone aggregate reinforced with 8mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I. (ii) The unit rate includes the cost of 40mm GI pipe light grade for protection of earth strip and 32 x 6 mm GI earth strip upto 7.5 M.
Design, supplying, installing, testing and commissioning LT outdoor type, double door, IP - 54, panel board, powder coated, factory fabricated, cubical type, weather vermin proof with locking arrangement and made out of MS CRCA sheet 3.0 mm thick with suitable size of channel for base fixed on frame made out of 50 x 50 x 6 mm thick angle iron complete with 600 Amps rated Aluminium bus bar inside sepreate chamber and compartmentalised cabinet for housing and mounting MCCBs, metering equipmentt prewired with suitble size of copper conductor duly marked the incoming & all outgoing controls and comprising of the following :-.
Supply, installation, testing & commissioning factory made CPRI approved, out door type, Automatic power factor corrector (APFC) panel with double door, fabricated out of 3.15 mm thick CRCA sheet and base frame and internal compartment 2 mm thick, panel shall be powder coated, mounting on angle iron legs suitable for operation of 415 Volts, 50 Hz, AC supply with switch gear and accessories, pad locking arrangement, earthing stud, labelling, inter connection, providing of danger plate, etc all as per specification and 10 % extra space for future expansion. The panel shall be placed on pedastal fixed on 1:3:6 PCC foundation extending 30 CM above the floor level with 1 Mtr x 1 Mtr wide plateform having 100 KVAR capacitor controle panel comprising of following :-.
M&L chain link fencing of mesh size 150mm x 100mm x 4mm dia wire of tranformer fencing (approx size 6m x 6m) with height 1.5 mtr including provision of angle iron gate of size 2 mtr consisting of double door 1.5 mtr height with angle iron posts of /_ 65 x 65 x 5mm @ 3 meter center to center,, excavation in any type of soil, PCC 1:2:4 type B-1 work, iron flat 65 x 5 mm for fixing of fencing with suitable nuts & bolts of size 10 mm dia and 25 mm length and around the transformer complete all as specified and directed.
S&F cast iron cable route indicator duly mounted on MS angle iron of size 40 x 3 mm for HT cable and duly grouted in PCC and painted with brown colour complete all as specified and directed.
CENTRAL AIR CONDITIONING
(a) Design, Supply, Installation, Testing & Commissioning of Central Air Conditioning plant including AHUs, Water pump sets, Cooling Towers, ducting and electrical connections suitable for 3 phase AC supply chilled water system of suitable capacity (tentaive capacity 60 TR with 50% stand by 30 TR i.e. total capacity 90 TR) including all provisions for earthing, floor mounted LT Panel board, all civil and electrical works as per IS specification and best practices for "OTM Accn for 21 CORPS Dental unit Bhopal" as per drawings complete all as specified and directed. Note : - (i) The capacity mentioned for AC Plant is tentive. Actual capacity should be work out by the contractor based on inside & outside enviroment condition. (ii) Compressor, Chiller & Pump, etc should be equally divided (e.g. 60 TR =2 x 30TR (W) + 30 TR (S) alongwith 50% stand by based on the total AC plant capacity as designed vetted from IIT/NIT and approved by GE.
BOQ Serial Item No.7.01 (Contd/-) (b) Design of energy efficient central air conditioning plant based on inside/outside conditions. Inside conditions to be obtained from GE on given data sheet attached as per format given in Appendix 'C', 'D' & 'E' of particular specifications. The design shall meet relevant code requirements and should be as per latest IS practices. It should include the followings:- (i) Data based heat load calculations for AHU as per site plan. (ii) Double line duct drawing showing different sizes of ducts air flow details. (iii) Chiller water piping drawing including condenser pipes and fitting with details of dia. (iv) Layout schematic line diagram of LT control panel suitable for the plant showing all the details such as main incoming, outgoing and their type, capacities, Qty, alongwith connected measuring instrument/meters, indication lamp, starters, MCB, MCCB isolator etc. (v) Specification/description of equipment and other materials/items with technical literature of various components of reputed makes. (vi) Recommendation of type of plant with detailed justifcation depending upon heat load to meet the desired condition specified in data sheet to be obtained from GE in consultation with user as per format attached as Appendix 'C', 'D' & 'E' of particular specifications. (vii) Line plan of plant AHU showing various eqpts/items with dimensions of various eqpts/items with specific working clearances between eqpts to eqpts and from walls, after due consideration existing doors and windows. (viii) Schedule of item/description of equipment of all items with accounting unit, Qty and particuar specification etc. (ix) Full description of item/eqpt of schedule with recommended brand/makes. (x) Inside design conditions are required to be maintained irrespective of minor variations in outside.
BOQ Serial Item No.7.01 (Contd/-) Notes :- (a) Contractor should submit 2 Nos CD showing detailed design with description/ specification complete alongwith heat load calculation (For summer, winter & monsoon) design, drawing bill of quantities and two Nos hard copies. (b) Outside design conditions can be obtained from concerned metrological authorities. (c) Contractor will develop the soft copy of all the drawings required for the work on the basis of Hard copy/line plan of the project. (d) The details given in Appendix 'C', 'D' & 'E' of particular specifications are tentative. Contractor has to obtain firm details from GE in consultantion with users. (e) Atmospheric/any other required data to be obtained from concerned metrological deptt/Govt institutions. (f) DPR should be vetted alongwith its drawing from IIT/NIT & finally approved by GE. (g) The work of Air Conditioning shall be carried out by specialist agency having past experience as approved by GE. (h) Noise level (sound pressure) should not exceed the permissible limits. (i) Testing includes phase- I, 24 Hrs continuous and Phase-II 24 Hrs continuous for all three seasons. (k) Any other connected works not mentioned above but considered necessary by the tenderer for successful installation, commissioning and operation and efficient performance of the plant shall be provided by the contractor and the rate for the same shall be deemed to be inclued in the quoted unit rates.
SUMMER APPLIANCES
Supply, install, connecting and testing of water cooler, fully stainless steel, non- corrosive electric driven (single phase) having approx storage capacity 80 Ltrs, self contained drinking water cooler with (Non - CFC refrigerent) energy efficient compressor and nominal cooling capacity of 40 Ltrs/Hrs including connecting of incoming and outgoing GI pipe medium grade and gate valve of suitable size with necessary PVC Nylone braided pipe, suitable PCC platform including draining water provision etc. complete all as specified and directed.
Supply & install refrigerator, electric driven (single phase) 230 Volts, single phase, 50 HZ ,BEE certified minimum 4 star rating capacity 165 Litres complete all as specified and directed.
Supply & install refrigerator, electric driven (single phase) 230 Volts, single phase, 50 HZ, BEE certified minimum 4 star rating, capacity 265 Litres, frost free complete all as specified and directed.
Supply, installation and testing of commercial evaporative type Air cooler (Desert Cooler), Plastic body, 230 Volts, single phase, having air throw capacity of 4000 cum/hr, Water storage capacity not less than 45 Ltrs, 15 mm dia float valve and suitable PVC connection, mosquito proofing net on all sides including fixing arrangements on windows complete all as specified and directed.
FIRE FIGHTING
S&F MS flanged pipe 200mm NB, heavy duty for multi-storied building duly painted with 2 coats of synthetic enamel paint over coat of zinc chrom primer complete all as specified and directed.
S&F MS flanged pipe 100mm NB, heavy duty for multi-storied building duly painted with 2 coats of synthetic enamel paint over coat of zinc chrom primer complete all as specified and directed.
S&F Cast Iron Foot Valve conforming to IS 4038, 200 mm NB complete all as specified and directed.
S&F Cast Iron Foot Valve conforming to IS 4038, 100 mm NB complete all as specified and directed.
S&F MS cabinet (approx size 750mm x 600mm x 450mm) to enclose fire brigade inlet connections fabricated from 16 gauge sheet with full front glass door and locking arrangement duly painted with 2 coats of synthetic enamel paint over coat of zinc chrom primer and mounted on masonry platform complete all as specified and directed.
S&F fire hydrant landing valve type-B (double head outlet) of 63mm dia conforiming to IS 5290 complete all as specified and directed.
S&F gun metal fire brigade inlet connection for connecting to external fire hydrant ring main consisting of two nos 63mm dia instantaneous type male coupling with built in check valves and 150mm dia, flanged outlet with all accessories complete all as specified and directed.
Supply, install and testing Star delta Starter fully automatic suitable for 415 V, 50HZ, with ML-6 contactor with suitable relay range 66-140 Amps with timer 9-30 sec SPP including incomming and outgoing electric connnection complete all as specified and as directed.
Supply, install and testing of DOL Starter fully automatic suitable for 415 V, AC, 50HZ suitable for 6-10 Amps rating including incoming and outgoing electric connection complete all as specified and as directed.
M&L for construction of brick masonry valve pit chamber of size 1050mm x 750mm x 1000mm (Internal dimension) with PCC 1:3:6 foundation 150mm thick, brick work 230 mm thick built in CM 1:6, PCC 1:3:6 coping 50 mm thick, plastering 15mm thick in CM 1:4 to all internal and exposed surfaces with & including excavation earth work in any type of soil, MS sheet cover 3.15mm thick fixed with angel iron frame 50x50x6mm with locking arrangement embedded in PCC and painting ot MS cover with two coats of synthetic enamel paint over one coat of red oxide primer etc complete all as specified and directed.
SEWAGE DISPOSAL NOTE:- For items of Dewage disposal notes given at the beginning of Sch ‘A’ Part-IX (SEWAGE DISPOSAL) shall also be applicable.
M&L for Brick masonry septic tank for 50 users designed to carry sewage and sludge water, excavation in any type of soil, PCC (1:4:8) below foundation, base slab, baffle walls and precast cover slab etc with vent shaft, inspection chamber etc all as specified and shown in drawing No. CEBZ/TD/76/2011 Sheet 1/2 & 2/2complete all as specified and directed.
ROAD/CULVERT
M&L 150mm thick (compacted thickness) WMM (Wet Mix Macadam) (layed in two layers of 75mm thickness each layer) prepared in continuous mixing plant, spreading should be done by mechanical paver and not be dumped in heaps, power roller should be used for rolling and consolidated to gradient and camber required and the final layer should be allowed to dry for 24 hrs including necessary lateral support and formwork if required using crushed stone coarse aggregate of maximum size 40mm of grading as specified and igneous type rock such as granite/trap/basalt, etc complete all as specifed and directed.
M&L for sand stone edging of roughly rectangular stone of size 50mm to 60mm thick not less than 300mm deep & 50 to 60 cm in length; dressed so that the maximum depression from a strainght edge held against the dressed surface shall not exceed 6mm from top and 20mm for the rest of surfaces jointed in CM (1:6) & joint struck flush including all necessary excavation & earth work in any type of soil complete all as specified & directed
SECURITY FENCING AND GATE
M&L Steel gate 6.00 metre wide in double leaf including RCC pillars in RCC M-25 design Mix using 20 mm graded stone aggregate, excavation and earth work form, reinforcement steel, painting to steel surfaces with two coats of synthetic enamel paint over a coat of red oxide primer, two coats of cement base paint to pillars, 10 mm thick cement mortar plaster on concrete surfaces in cm (1:4) etc all as specified and shown in drawing No. CEBZ/TD/104/2011 Sheet 1/3 to 3/3 complete all as specified and directed. NOTE:- Irrespective of whatever width shown on drawing the gate shall be 6.00 meter wide.
M&L Wicket gate of steel 1.5 m wide all as specified and shown in drawing No. CEBZ/TD/106/2011 Sheet 1/1 complete all as specified and directed.
FIRE DETECTION AND ALARM SYSTEM
Supply, fixing, testing and commissioning of Multi criteria heat and smoke detectors complying with any type certified to EN - 45 baddressable type heat & smoke detector photoelectric/optical with self build intelligence as per IS:11360, Detectors shall comply with and be type certified to UPCB Heat and smoke detectors. Dectector housing shall be moulded in pure white self-extinguishing polycarbonate, V-O rated to UL94. Detectors shall be ununobstrusive when installed complete all as specified and directed. NOTE: Detectors shall also be installed above false ceiling araes wherever required as per norms.
Supply, installation, testing and commissioning of Zonal indicators panel of upto 6 zones; having provision for audio & video indications for FIRE, FAULT, OPEN/SHORT EARTH CIRCUIT duly interfaced with main control panel. The panel shall be factory manufactured with 1.6mm thick CRCA powder coated enclosure and shall have self diagonistic features and test facilities complete all as specified and directed.
S&F ISI marked Fire extinguisher, ABC type, multi-purpose, 6 KG capacity with squeeze grip valve and pressure indicating meter complete all as specified and directed.
M/s Khialdas Constructions
Raja enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .