Executive Engineer MHD Srinagar
office of Executive Engineer MHD Srinagar
Replacement of existing defunct Split Air conditioning units at CT Scan Section of Govt. GB Panth Hospital, Srinagar.
2026_PWDJK_311984_1
MHDS/TS/2026-27/21/e-tendering dt 09.06.2026
Open Tender
Machineries/ Mechanical Engg Items
Percentage
10 days
gb panth hospital
as per nit details
3 documents required · 3 mandatory
₹100
EXECUTIVE ENGINEER MHD SRINAGAR
₹10,115
20 Jun 2026
9 Jun 2026
19 Jun 2026
9 Jun 2026
19 Jun 2026
9 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Dismantling of defunct Air conditioning unit in CT Scan Section, along with replacement by way of Supply, Installation, testing, and commissioning of 2.0 TR (Min. 7.0 kW Rated Capacity), Hot and Cold, Inverter Type Split AC Unit comprising of indoor and outdoor units with R-32 Refrigerant (Green Gas) having rotary compressor, indoor Motor, Outdoor Motor, Expansion Valve and a remote-control unit with allied accessories. AC should be suitable for operation on 50 Hz single Phase AC Supply. Both the indoor and outdoor units shall be installed on wall and wall/floor brackets respectively as per requirement to hold the units and should be complete with all default accessories as per OEM like Hooking arrangements, Fixtures, frames for holding indoor and for resting outdoor units, Drainage Piping etc .The AC should have ISEER Rating ≥ 4.3. Ambient Temperature operationability in Heating shall be - 10° C or lower. The AC should have Min. 10 Years Warranty on Compressor, and, Min. 5 Years Warranty on PCB. The cost is exclusive of cabling, copper tubing and nitrile foam insulation. | - | Job | - | - |
| 3 | Providing, Fitting, Testing and commissioning of below SizedCopper tubing along with jointing, bending etcfor liquid flare and gas flare and duly insulated by Elastomeric nitrile rubber along with fixtures, saddles, ties etc | - | - | - | - |
| 4 | Minimum 6.35 mm Dia/AS RECOMMENDED BY OEM. | - | mtr | - | - |
| 5 | Minimum 12.7 mm Dia/AS RECOMMENDED BY OEM. | - | mtr | - | - |
| 6 | SITC of 5kvaCopper wound automatic voltage stabilizer single phase with high cut and low cut & allied safety/protections, wall mounted designed at input voltage range of 150-220 volts and output voltage range of 220-240 volt along with the wall mounting brackets and necessary fittings. The job encompasses carrying out repairs to the walls wherever the same are cut. the stabilizer shall have digital meter showing input, output voltage and load of the AC. the item shall confirm to IS 8448 (1989). | - | Job | - | - |
| 9 | providing and laying of 20 mm PVC conduit/channel with flexible Conduit wherever required along with fixtures,bends,junction box union, saddle wherever applicable. | - | Mtr | - | - |
| 10 | Providing, laying and fitting ofFRLS(flame retardant low smoke)4sqmm 1core , insulated unarmored sheathed copper cable. The item shall confirm to IEC 60502 and IS-694:2010 | - | mtr | - | - |
| 11 | Providing and fitting of 2 pole 32-amp c-curve type MCBwith Circuit Breaking Capacity, Icn=10kAinside Powder Coated MS Enclosures to be fitted for each for AC unit. The item shall confirm to is/IEC 60898 and IEC 60947-2. | - | Job | - | - |
| 12 | Providing and fitting of 32 Amp ISI marked 3 2 pole mcb with circuit breaking capacity Icn=10 ka ,inside powder coated steel enclosure to be fitted for each ac unit he item shall confirm to is/IEC 60898 and IEC 60947-2. | - | Job | - | - |
| 13 | Providing, laying and fitting ofFRLS (flame retardant low smoke) 2.5 sqmm 4 core with insulated unarmored sheathed copper cable. The item shall confirm to IEC 60502 and IS-694:2010 | - | Mtr | - | - |
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.61 MB
Tendernotice_2.pdf
PDF • 1.07 MB
BOQ_1009925.xls
BOQ • 0.30 MB
21.rar
PDF • 0.50 MB
cor.pdf
PDF • 0.44 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .