Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.5 CrAccepted-Finance | ₹1.5 Cr | L1 | Accepted-Finance as per boq |
| 2 | L2₹1.5 Cr+₹3.7 L (2.53%)Accepted-Finance | ₹1.5 Cr+₹3.7 L (2.53%) | L2 | Accepted-Finance as per boq |
| 3 | L3₹1.6 Cr+₹8.9 L (6.11%)Accepted-Finance | ₹1.6 Cr+₹8.9 L (6.11%) | L3 | Accepted-Finance as per boq |
| 4 | L4₹1.6 Cr+₹10.4 L (7.10%)Accepted-Finance | ₹1.6 Cr+₹10.4 L (7.10%) | L4 | Accepted-Finance as per boq |
| 5 | L5₹1.7 Cr+₹24.7 L (16.9%)Accepted-Finance BU 02 SFS FLATS OUTER RING ROAD PITAMPURA NORTH WEST DELHI DELHI 110034 | NORTH WEST DELHI | DELHI | 110034 | ₹1.7 Cr+₹24.7 L (16.9%) | L5 | Accepted-Finance as per boq |
Tender Value
₹1.8 Cr
EMD Value
₹3.6 L
Closing Date
24 Feb 2022, 6:00 pmClosed
Executive Engineer
JKPHC JAMMU
VRV based Air Conditioning System ( HVAC) at Crime Headquarters Channi Rama Jammu. (Contract No. 206)
2022_DGPJK_159704_1
Fresh 206 of PHC JAMMU DIV/2021-22 Dt 07-02-2022
Open Tender
Machineries/ Mechanical Engg Items
Item Wise
210 days
CHANNI RAMA JAMMU
REFER PQ TERMS AND CONDITIONS
3 documents required · 3 mandatory
₹5,000
Executive Engineer JKPHC Jammu
₹3.6 L
Office of the Executive Engineer, JKPHC Jammu
4 Mar 2022
7 Feb 2022
25 Feb 2022
7 Feb 2022
24 Feb 2022
14 Feb 2022
7 Feb 2022 - 11 Feb 2022
12 Feb 2022
Amount
OUTDOOR UNITS (HEAT PUMP TYPE)
Supply, installing, testing and commissioning of air cooled variable refrigerant flow modular type top discharge air conditioning system with R410a refrigerant suitable for 415±10%, 50 cycles. The unit shall consist of indoor and outdoor units with individual controller as per detail given in specifications and having following items
Modular type outdoor units equipped with highly efficient 100 % inverter type BLDC Scroll Compressors with special precoated heat exchanger, low noise condenser fan housed in compact housing duly powder coated and Outdoor unit having COP at 100% conditions shall not be less than 3.1 and IEER not less than 6.5
The outdoor unit should include all loading, unloading, transportation, power cabling/wiring from near the indoor and outdoor units respectively.
22 HP Outdoor unit for : ZONE - I
8 HP Outdoor unit for : ZONE - II
46 HP Outdoor unit for : ZONE - III
52 HP Outdoor unit for : ZONE - IV
50 HP Outdoor unit for : ZONE - V
44 HP Outdoor unit for : ZONE - VI
38 HP Outdoor unit for : ZONE - VII
INDOOR UNITS
Supply, installation, testing and commissioning of following Wall Mounted /Cassette type units with panel and inbuilt drain pump/slim Ceiling Mounted duct type/Ceiling Mounted Built in type/Ceiling Mounted Ductable type units VRV Air Conditioners with corded remote controller. Fully Factory assembled, wired and tested Indoor Units as per specifications as required to make the system complete.
Ceiling Mounted Cassette Type
Ceiling Mounted cassette Type – 1.5TR
Ceiling Mounted cassette Type - 2.0 TR
Ceiling Mounted cassette Type – 2.5 TR
Ceiling Mounted cassette Type – 3.0TR
Ceiling Mounted cassette Type – 4.0TR
Wall Mounted Split Type
Wall Mounted split Type - 1.0 TR
Wall Mounted split Type 1.5 TR
Wall Mounted split Type 2.0 TR
Duct able type concealed units
Ceiling Mounted Duct able Type - 2.0 TR
Ceiling Mounted Duct able Type - 2.5TR
Ceiling Mounted Duct able Type - 3.0TR
Ceiling Mounted Duct able Type – 4 HP
Ceiling Mounted Duct able Type – 5 HP
REMOTE CONTROLLERS
Supply, installation, testing and commissioning of Imported Remote controllers (Corded) for operation of ductable indoor units and AHU's.
Y-Joints
Supply, installation, testing and commissioning of Imported fittings Y-joints insulated, distributer and headers for all Indoor units at both the ends floors layout as per layout drawings
REFRIGERANT PIPING
Supply, installation, testing and commissioning of Inter connecting refrigerant pipe work with (13/19mmthick) closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with hangers and all external piping with UV coatings hall run in cable tray. (Note: Ref. Piping Length may be review as per site routing
06.35 mm with 13 mm thick nitrile rubber insulation
09.52 mm with 13 mm thick nitrile rubber insulation
12.70 mm with 13 mm thick nitrile rubber insulation
15.88 mm with 13 mm thick nitrile rubber insulation
19.05 mm with 13 mm thick nitrile rubber insulation
22.22 mm with 19 mm thick nitrile rubber insulation
25.54 mm with 19 mm thick nitrile rubber insulation
28.58 mm with 19 mm thick nitrile rubber insulation
31.81 mm with 19 mm thick nitrile rubber insulation
34.92 mm with 19 mm thick nitrile rubber insulation
38.92 mm with 19 mm thick nitrile rubber insulation
41.30 mm with 19 mm thick nitrile rubber insulation
TRANSMISSION, CONTROL & MAIN CABLING
Providing & fixing control cum transmission wiring in medium duty PVC Conduit between indoor and outdoor units.
2C X 1.5 Sqmm copper cable for control between indoor and outdoor
2C X 1.0 Sqmm copper cable from indoor to dedicated point for remote
3C X 2.5 Sqmm copper cable from each indoor to sub panel
4C X 06 Sqmm copper cable from each outdoor to main panel
4C X 10 Sqmm copper cable from each outdoor to main panel
3.5C x 300 sqmm Alumunium Armoured cable from main panel/Servo to out door machines including thimbles
3.5C x 400 sqmm Alumunium Armoured cable from Main Scource to the main panel/Servo including thimbles
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling /concrete flooring with G.I. suspenders/brackets including G.I. bolts & nuts, etc. as required.
Cable Tray 40x 150x40 mm 1.6 mm Thick
Cable Tray 40x 300x40 mm 1.6 mm Thick
Refrigerant-410a
Supply, charging & Leakage testing of refrigerant -410a of entire VRV System and commissioning.
DRAIN PIPING
Providing & fixing rigid PVC piping complete with fittings, supports as per specifications and pre insulated with 6mm thick closed cell elastomeric nitrile rubber tubular insulation including repairimg /plastering & making the same & disposal of chiseled mulba from site.
25 mm dia
32 mm dia
40 mm dia
50 mm dia
CANVASS CONNECTION
Supply, Installation, Testing and commissioning of double layer canvas connection with fire rating.
AIR DISTRIBUTION SYSTEM
Site Fabricated Duct - GI Sheet Metal duct
Supplying, fabricating, installing and testing of sheet metal ducts of following thicknesses including necessary supports, flexible hangers with isolators, flexible connections, nut bolts, fastener, gasket, splitter dampers and vanes, volume control dampers
0.63mm (24 gauge) GSS
0.8 mm (22 gauge) GSS
1.0mm (20 gauge) GSS
1.25mm (18 gauge) GSS
Supplying, installing, testing and balancing of aluminium supply/return air grills of various sizes. Each grill shall be with fixed horizontal front bar at Zero/15 Deg deflection through the collar and register.
Supply air grills /Diffuser with Dampers.
Return air grill /Diffuser without Dampers.
INSULATION WORKS
THERMAL INSULATION
SITC of Thermal insulation material for Duct insulation shall be closed cell cross linked polyethylene foam. Thermal conductivity of the insulation material shall not exceed 0.032 W/m°K at an average temperature of 25°C. Density of the material shall be 25-30 Kg/m3.The product shall have temperature range of –40°C to 105oC. The insulation material shall be fire rated for Class 1 as per BS 476 Part 6: 1989 for fire propagation test and as per BS 476 Part 7, 1987 for surface spread of flame test. Water vapour permeability as per DIN 52615 shall not exceed 0.15ng/Pa.Sec.m.
13 mm thick insulation (Return Air Ducts)
9 mm thick insulation (Supply Air Duct)
ACOUSTIC LINING IN THE SUPPLY/RETURN DUCTS
SITC of Insulation material for Duct Acoustic Lining shall be resin bounded fiberglass wool with one side factory laminated either Black Glass Oven Cloth or Black Glass Tissue. The Thermal conductivity of the fiberglass for air- conditioning application shall not exceed 0.034 W/m°K at 25°C mean temperature and average Noise Reduction Coefficient (NRC=1, frequency range from100 Hz to 8000Hz ) .The density of insulation material shall be either 32 Kg/m3 and thickness of insulation material shall not less 25 mm.
25 mm thick acoustic lining
13 mm thick acoustic lining
MAIN ELECTRIC PANNEL
Fabrication, supplying, installation testing and commissioning of following panel CPRI approved made out of 2mm thick M.S. sheet, floor/wall mounted, vermin and dust proof, indoor type with suitable size of angle iron legs for grouting in the ground, with lockable type hinged doors, duly p0wder coated with provision for fixing of 1 no incomer MCCB, outgoing MCB's, , required number of sets of Aluminium Bus Bar, providing & fixing . Strips for housing MCB's and other allied accessories etc. as required. Main and Sub main Panel = 54Cft.(APPROX)
Providing and fixing of following protection equipments and other allied accessories including connections, inter connections, with suitable size of PVC insulated copper conductor cable including earthing etc. as required.
MCCB FP 800 Amp. 50 KA Microprocessor type (main incomer) complete with spreader links. All MCCB's shall have rotary handle and ICU=ICS=100%.
40 amps TPN
32 amps TPN
ELCB 25-80 amp with 30 (Millie amp)
800 Amp Aluminium Bus Bar with required no of thimbles
800 Amp 4 pole Change Over Switch
CT Set of suitable rating 200/5 A 1.15 VA burden
Indicating Lamp(Led Type)
Voltmeter (0-500) Volts Digital type
Ammeter (0-500) Amps. Digital type
MCB Strip for 90 Nos. MCB's
Supply ,instalation,fabrication Testing and commissioning of Low voltage Sub Main Panel on 415 volts 3 phase 50 htzs of 2mm thick CRCA / Sheet of powder size 4 X 6 X 2 cft . b) Providing and fixing of 400 amp Bus bar with required nos of thimbles etc (1 no) e)400 amp 4P MCCB 36KA f)VSS meter/switch g) ASS meter/ switch
SUB ELECTRIC DB BOX, including Cheseling, repairing & making the same
16 Way DB Box with Double shutter
12 Way DB Box with Double shutter
08 Way DB Box with Double shutter
MCB/SPN 32 AMP
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.5.4
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.5.15
Cutting of Floor/ Floor Tiles/Granite for out let of Air Condition water & makig the same (Covered with Stainless steel almunium strip)
Supply, Installation, Testing and commissioning of 600 kVA Automatic Servo Voltage Stabilizer oil cooled, outdoor type, suitable for operation on 3 phase 50Hz, 415V system with input voltage correction range of 260V to 460V(phase to phase), output 415V +/-1%, unbalanced input, unbalanced load, first filling of oil, overvoltage, under voltage, over current, short circuit, protections and complete with bypass system.
COOLWAYS CONDITIONING PVT LTD
Yatha Consultants and Engineers
precision systems
PNEUMATIC ENGINEERS PVT LTD.
Superior Aircon Pvt. Ltd.
Modern cooling solution
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .