Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.1 LAccepted-AOC | L1 | Accepted-AOC Due to being Lowest | |
| 2 | L2₹13.6 L+₹23,285 (1.74%)Rejected-Finance | L2 | Rejected-Finance Rejected due to L2 | |
| 3 | L3₹14.1 L+₹74,220 (5.56%)Rejected-Finance | L3 | Rejected-Finance Rejected due to L3 | |
| 4 | L4₹14.4 L+₹1.1 L (7.98%)Rejected-Finance | L4 | Rejected-Finance Rejected due to L4 | |
| 5 | L5₹14.9 L+₹1.6 L (11.9%)Rejected-Finance 6 O YASHODA NAGAR KANPUR UP 208011 | KANPUR | KANPUR NAGAR | UTTAR PRADESH | 208011 | L5 | Rejected-Finance Rejected due to L5 |
Tender Value
Refer Docs
EMD Value
₹41,700
Closing Date
25 Feb 2021, 6:00 pmClosed
GE
GE (I) (P) FY KANPUR
REPAIR/REPLACEMENT OF OLD UNSERVICEABLE LT PANEL BOARD AND OTHER ELECTRICAL ASSOCIATED WORK AND REPAIR/REPLACEMENT OF 15A POWER SOCKETS AND LED PANEL AND PROVISION OF 04 NOS. AIR CONDITIONERS AT NAI(KANPUR) FOR NCN PROJECT UNDER GE(I) (P) FY KANPUR.
2021_MES_417318_1
8860/KAN/T-29/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (I) (P) FY KANPUR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE (I) (P) FY KANPUR
₹41,700
Yes
20 Mar 2021
29 Jan 2021
27 Feb 2021
29 Jan 2021
25 Feb 2021
12 Feb 2021
Amount
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting fans etc.removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls floors etc
Material and labour for point wiring with 2.5 sqmm single core PVC insulated unsheathed cable 1100 volt FRLS grade ISI marked with multistranded copper conductor drawn through and including rigid PVC conduit/ Casing caping on wall/ceiling with and including provision of MS box of suitable size with 3mm thick laminated hylam sheet cover for housing switch, socket, etc incl provision of 2.5 sqmm single core cable green in colour PVC insulated copper conductor as earth continuity conductor connected to earth dolly for following:- (Make of wire shall be : Finolex/Havells/Gloster and PVC conduit/casing shall be of make : Finolex/Avonplast/Garware/AKG/Asian i)one socket outlet 2 in 1, 15 Amps power point
All as per item No 2 here in before but for one socket out let 2 in 1, 5 and 15 Amps or AC point with 4 Sqmm PVC copper conductor and provn of 4.0 sqmm PVC insulated single core copper cable green in colour as earth continuity conductor.
Material and labour for point wiring with 1.5 sqmm single core PVC insulated unsheathed cable 1100 volt FRLS grade ISI marked with multistranded copper conductor drawn through and including rigid PVC conduit/ Casing caping on wall/ceiling with and including provision of MS box of suitable size with 3mm thick laminated hylam sheet cover for housing switch, socket, etc incl provision of 1.5 sqmm single core cable green in colour PVC insulated copper conductor as earth continuity conductor connected to earth dolly for following:- (Make of wire shall be : Finolex/Havells/Gloster and PVC conduit/casing shall be of make : Finolex/AKG/Asian i)One light point controlled by one 05 Amps switch.
S&F modular switch flush type 6 Amp single pole one way, one module
S & F ceiling rose 2 to 3 terminal backelite
S & F Modular white cover plate with frame 4 module
S & F Modular white cover plate with frame 8module
S & F modular metal flush box 4 module
S & F modular metal flush box 8 module, Note : for item No. 9 to 32 Make shall be Anchor/Cona/Leader
S & F socket 2 in one, 5 and 15 Amps flush type
S & F Switch 15 Amps flush type
Supply and fix in replcement MCB DB double door type single phase with common eath and neutral bus and 200 amps copper bus bars complet , 240 volts ,08 way Make : ABB/Legrand/Siemens/L&T
All as per item No.13 above but 12 way Make : Make : ABB/Legrand/Siemens/L&T
All as per item No. 13 above but of 4 way Make : ABB/Legrand/Siemens/L&T
S & F MCB SP 6-32 Amps, 10 KA, 'C' series. Make : ABB/Legrand/Siemens/L&T
S & F MCB SP 63 Amps, 10 KA, 'C' Series Make : ABB/Legrand/Siemens/L&T
S & F MCB SPN 63 Amps, 10 KA, 'C' Series Make : ABB/Legrand/Siemens/L&T
S & F MCB SP 40 Amps, , 10 KA, 'C' Series Make : ABB/Legrand/Siemens/L&T
S & F MCB SPN 40 Amps, , 10 KA, 'C' Series Make : ABB/Legrand/Siemens/L&T
Taking down old unserviceable aluminium sub main wiring and S & F sub main wiring for circuit of size 10 sq mm 2 core alongwith earth wire of 10 sq mm single core of FRLS PVC insulated unsheathed cable (FR), 1100 volts grade with multistranded copper conductor, conforming to IS-649, 1100 V grade and drawn through and including PVC non metalic rigid conduit/casing of suitable size and conduit/casing accessories run on surface of wall/ceiling etc and connecting terminal ends of suitable size complete all as specified and directed by Engr-in-Charge. Make : Finolex/Havells/Gloster
All as per item No. 23 above but with wire 6 sq mm 2 core with 6 sq mm single core as earth continuity Make : Finolex/Havells/Gloster
Taking down old unserviceable aluminium sub main wiring, material and labour for sub main wiring complete with 4 runs of 16 sqmm PVC insulated and unsheathed cable with multi stranded copper conductor, conforming to IS-649, 1100 V (FR) grade and drawn through and including PVC non metalic rigid conduit of suitable size and conduit accessories run on surface of wall/ceiling etc and connecting terminal ends including 2 run of 16 sqmm PVC insulated un-sheathed copper conductor cable green colour as contineous earth continuity conductor and connecting to earth dolly complete all as directed. Make : Finolex/Havells/Gloster
M&L for earthing complete withGI plate electrodes 600x600x6mm thick buried directly in ground earth pit not less than 2.25m deep below normal ground level with top edge of earth plate not less than 1.5m below ground level connected to G I strip 32X6 mm as earthing lead fixed by means of nut bolt washer of brass as shown in electrical plate No.3 of SSR Pt-I 2009 including necessary excavation and earth work in any strata, GI pipe 40mm dia light grade for watering , and 15 mm light grade as protrection to earth wire upto 7.5 mtr ,charcoal & salt etc and PCC chamber in PCC 1:3:6 type C1 covered with 40mm thick RCC 1:2:4 type B1 using 20mm graded stone aggregate reinforced with 8mm dia MS bar @ 75mm C/C both ways cover, funnel & wire mesh including making of test point all as specified testing on complete.
All as per item No. 26 Above but with earth wire 4 mm dia and 15 mm dia GI pipe light grade for protection upto 7.5 mtrs
Supply and fixing in repair LED 33 watts suitable for armstrong/Grid ceiling of size (600 x 600) mm complete connecting to existing ceiling rose with three core flexible wire 0.5 sq mm complete all as specified and directed. Cat No. CRC010R033HP57UGR of make Wipro or its equivalent in Havells/ C&S.
M & L earth continuity conductor or main earthing lead fixed to wall or battens or recess or chases or buried in ground in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc as required of 4 mm dia size GI wire
Supply and fix MCCB with enclosure in extg panel with addition / alteration to the extg panel , 415 V, 4 pole 400 amps capacity, 36 KA with adjustable thermal and magnetic settings
Supply and lay and testing XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 Sq mm 3.5 core layed in trenches, passing through floor/walls, passing through GI pipe under road cutting etc complete all as specified and directed by Engr-in-charge. (Main Panel cable)
All as per item No. 30 but of size 70 sq mm 3.5 core (Distribution Panel )
All as per item No. 30 but of size 50 sq mm 3.5 core (Proposed TPN DB)
All as per item No. 30 but of size 35 sq mm 4 core (Extg. TPN DB)
All as per item No. 30 but of size 10 sqmm 2 core
All as per item No. 30 but of size 6 sq mm 2 core. Note : Make for Item Ser No. 2 to 7 shall be Havells/Grandlay/Polycab
S & F PVC insulated & sheathed multistranded copper conductor, 1100 volts grade, cross sectional area 25 sq mm four runs (FRLS) for phase and neutral and 25 sq mm 2 runs (FRLS) as earth wire duly clamped with suitable size of saddles on wall or passing through existing cable tray without disturbing the existing cable tray or passing through PVC conduit of suitable size complete all as specified and directed. Make Shall be : Havells/Grandlay/Polycab
S & F sub main wiring for circuit of size 10 sq mm 2 runs (FRLS) alongwith earth wire of 10 sq mm single runs of FRLS PVC insulated unsheathed cable, 1100 volts grade with multistranded copper conductor including PVC conduit of suitable size complete all as specified and directed by Engr-in-Charge. (for SPN DB 12 way) . Make Shall be : Havells/Grandlay/Polycab
All as per item No. 37 above but of wire 6 sq mm two runs and 6 sq mm single run as earth wire. (for SPN DB 8 way) Make Shall be : Havells/Grandlay/Polycab
All as per item No. 37 above but of wire 4 sq mm two runs and 4.0 sq mm single run as earth wire. (for SPN 4 way) Make Shall be : Havells/Grandlay/Polycab
M & L cutting chases, pinning in,making good to facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps cills, sun shadows, sheves lintels etc and cutting chases for concealed water tubing or concealed wiring etc and making good cutting n . exc 10 cm girth
All as per item No. 40 above but exc 10 cm but not exc 20 cms girth
Demolition of cement concrete of any description for laying of pipes/cables and making good to the disturbed surfaces to match with existing complete all as specified and directed. Note : Providing PCC work will be measured and paid separately under relevant items.
Material and labour for cement concrete in foundations, filling and mass concrete Type D2 1:4:8 (40 mm graded aggregate) incl form work
Material and labour for cement concrete in foundations, filling and mass concrete Type B2 1:2:4 (40 mm graded aggregate) incl form work (for redressing road surface)
M & L for Horizontal drilling hole at a depth upto 1 mtr below the normal ground level of suitable size to insert pipe upto 40-80 mm dia across the road across the horizontal position at different location complete all as specified and as directed.
M & L for GI tubing (light grade) for 50mm dia bore with all necessary fitting laid in trenches/under road crossing, or fixed on poles/walls/under floor etc complete all as specified and as directed
All as per item No 47 above but for 80 mm dia.
Excavation in trenches in soft/ loose soil not exc. 1.5 metre wide and n'exc. 1.50m deep for pipes and getting out complete all as specified and directed.
Returning filling including spreading leveling watering and well ramming in layers not exc 25Cm in soft/ loose soil, complete all as specified and directed.
Removing excavated material in soft/ loose soil n'exc 50M and depositing where directed at a level n'exc1.5M above the starting point, complete all as specified and directed.
M&L for sand cushning to U/G cable in layers of 23cm thick( 8 Cm before laying the cable and 15Cm thick after laying the cable) in trenches including watering and consolidation, complete all as specified and directed.
Supply and lay well burnt brick class B as protection to cable in cable trenches all as specified and directed
Supply and fixing in repair TPN DB's 4 way vertical type 415 V, double door suitable for housing of 125 Amps MCCB as main incoming. Make Shall be : Indo Asian/ABB/Havells
Supply and fixing in repair MCCB 100 Amps, 4 Pole, 25 KA, suitable to be fixed in 6 way TPN DB complete all as specified and directed. Make Shall be : Indo Asian/ABB/Havells
S & F MCB SPN 40 Amps Make Shall be : Indo Asian/ABB/Havells
M & L Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop as required of size 32x6mm galvanised iron strip as earth continuty lead
Material and labour for providing cable path indicators made out of CI plate 150 mm dia, inscribing ''1.1 KV LT cable" fixed on MS angle iron with minimum two numbers of nut and bolts or rivets. The nuts shall be tack welded with bolts after full tightning. The size of MS angle iron shall be 30 Cm X 30 Cm X 4 mm thick and length of angle iron should be 900 mm above adequate to be ensure minimum planting depth of 600 mm below ground and 300 mm above GL .Bottom end of angle iron should be anchored type to provide better grip and should be mbedded in PCC 1:3:6 with 20mm aggregate block size 200 X 200 X 300 mm MS angle iron shall be painted with one coat of red oxide primer through out length and there after it will be painted with two coat of bluecolour enamel paint and bituminous paint in the portion above ground and below ground respectively complete.
Supply and fix air cooled split unit air conditioner electric driven single phase of capacity of 2.0 TR, BEE 5 Star rated, invertor AC, Dehumidifier & air purifier feature with remote control mode, model No- RMOG524HCEA of make Hitachi or equivalent in Daiken or Blue star
Supply and fix air cooled split unit air conditioner electric driven single phase of capacity of 1.5 TR, BEE 5 Star rated, invertor AC, Dust filter, dehumidifier, model No- RSOG518HDEA of make Hitachi or equivalent in Voltas or Blue star
Supply and fix single pole and neutral enclosure with two pin and earth plug and socket complete with one single pole MCB 20 Amps complete all as specified and directed.
Supply and fix voltage stabilizer for automatic operation, single phase naturally air cooled indoor type and designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of (+/-) 2.5% and of capacity 5.0 KVA
S& F sub main wiring for circuit of size 4.0 sq mm 2 core (FRLS) alongwith earth wire 4.0 sq mm single core FRLS PVC insulated unsheathed cable, 1100 volts grade with multistranded copper conductor including PVC conduit of suitable size complete all as specified and directed by Engr-in-charge.
Manoj Electricals
S B ENTERPRISES
IMPEX TRADERS
N.P.BUILDERS
Sagar Electricals
classic contriction co.
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .