GE NAMS
GE NAMS KHASA CANTT AMRITSAR
MANNING AND OPERATION OF 66 KV SUB STATION INCLUDING CONNECTING ITEMS AT NAMS
2020_MES_360128_1
GE NAMS - 54 / 20 - 21
Open Tender
Electrical and Maintenance Works
Item Rate
334 days
NAMS CANTT
Class D
Category d (v)
8 documents required · 8 mandatory
₹500
Yes
GE NAMS
₹90,000
Yes
15 Mar 2021
10 Jul 2020
31 Jul 2020
10 Jul 2020
30 Jul 2020
23 Jul 2020
Amount
Manning and operation and routine maintenance of 66 KV Grid Sub Stn, in three shifts comprising of the following assests :-
A) 66 KV Assests and connected accessories
Transformer 66 KV/11 KV 8 MVA-02 Nos complete with protection control cable and connected accessories.
Stand by Transformer 66/11 KV 4 MVA-01 No complete with protections control cable and connected accessories.
72.5KV,31.5 KA, 1600 A, SF-06 type circuit breaker - 04 Nos
Control and relay panel for 66/11 KV Transformers 8MVA/4MVA-03 Nos.
OLTC panel-03 Nos.
72.5 KV/110 Volt PT Set - 09 Nos.
72.5 KV, 31.5 KA CT's of ration 400-200/1-1-1A - 12 Nos
Bus bar of 66 KV Grid - 01 Set
Earthing pit- 04 Set
Protection control cable - 01 Set
60KV ZnO surge Arresters (Gapless) - 04 Set (Each of 03 Set)
11KV, VCB Panel- 15 Nos
ACDB & DCDB Panel- 02 Nos
Transformer 11 KV/0.433 KVA 63 KVA – 01 Nos.
Bty bank consisting of 110 Nos battery of 02 Volt 100 AH- 01 Set
Bty charging panel - 01 Set
Gen Set 25 KVA with AMF panel -01 Nos
72.5 KV, 31.5 KA, 1250 Amp isolator without earth switch- 06 Nos
Do but without earth switch- 01 Nos
Capacitor bank of capacity 1.6 MVAR, 11KV & 1.2 MVAR- 03 Nos
Outdoor feeder pillar for lighting - 01 No
Operating staff to be deployed :-
Sub Station Attendant (Electrician) - One persons per shift (Total three shifts per day) having diploma/ITI in electrical engineering with three year experience in the relevant trade.
Helper - One person per shift (total three shift) who is physically fit and having minimum qualification of Matric.
Note :- Period of one shift - 8 Hours.
No of shifts to be deployed per day - 03.
Nature of Duties of operation staff
Sub Station attendant / Electrician have to operate and maintain all the assets listed under item No. 1(A) here in before.
Maintaining and recording of the records of all the Instruments all as directed by Engineer-in-Charge and register/log sheet will be provided by contractors.
Monitoring of periodical functioning of the instruments listed in Sub Station standing order/particular splecifications as per laid down periodically.
Recording daily break down /shut down in the log sheet other than reading such as trip record, breakdown its duration, preparing permit slip etc.
Carrying out necessary periodical test of earthing of complete Grid quarterly and recording it on test sheet.
Testing of DC batteries healthiness, checking of gravity of batteries, functioning of battery bank replacement of worn-out fuses, weekly and making the test/record sheet.
Testing, cleaning, checking of bty terminal, Ammeter, voltmeter periodically and maintain log book for running of Gen Set of capacity 25 KVA.
Maintaining and monitoring capacitor bank and power factor.
HELPER - To assist the sub station attendant / electrician for taking out trolleys of switch gears etc, recording the reading of instruments, watch and ward for complete assets installed with in the premises of the installation and daily cleaning of the installed machinery of installation and area of Sub Station.
PROTECTIVE CLOTHING/UNIFORM/TOOLS :- The duty SBA and helper shall wear uniform as approved by the GE/ Engineer-in-Charge. The tools kit consisting of Insulating plier, screw drivers, DE Spanner set shall always be in possission of the duty SBA. The uniform and tool kit shall be arranged by the contractor. SBA /Helper will not be attand to enter the sub stn without protective clothings.
Duty Roster. Necessary duty roster shall be prepared by the contractor every months and approved by JE/Engineer-in-Charge monthly.
One mobile set to be provided at 66 KV Sub Stn permanently for communication by contractor without extra cost.
Payment of wages : The Garrison Engineer is the principal employer as such payment to staff deployed shall be made not less than minimun wages as govt policy. Payment to staff deployed to made through bank cheque & evidence to be produced as directed.
Penalty Charges. The panelty charges are under:-
Absent of duty attandent recovery @ Rs. 500/- per day per shift for Electrician.
Absent of helper recovery @ Rs. 300 / per day per shift for helpar.
Not carring out the periodical test as per periodicity, recovery @ Rs. 500/- for each test.
Contractor is responsible for cleaning within the boundary wall of the sub stn remains foliage free/grass free at all time. Existing foliage / grass will be uprooted by machinery / maually as per the requirement and safety of cables.Removing rubbish upto distance of 50 mtr out the periphery of area under cleaness including internal cleaning complete all as specified and directed. Penal Charges:- Non cleaning of the area recovery @ Rs. 5000/-per month.
In case any attendant / helper not found in uniform a penalty of Rs 100/- be imposed per person per day.
Maintaining of power factor above 0.95. The panel charges charged by PSPCL shall be paid by contractor.
All safety precaution will be taken by the Electrician/Helper incase of any lapse contractor will be responsible for the same.
Routine testing of 66 KV assets by Power Grid Corporation of India/PSEB to be tested are as under: -
Transformer 66 KV 6.3/8 MVA - 01
Tests to be carried out
IR value test of both transformer and bushings.
PI value test for 20 seconds and 120 seconds.
No load current test.
Magnetic balance test.
Short circuit test.
Testing of tap changer.
Tan/delta test of transformer.
Dielectric strength of transformer Oil
Dissolved gas analysis test
66 KV SF-06 Breaker (02 Nos) - Tests to be carried out by the power Grid Corporation of PSEB Protectiion team. Following test shall be carried out :-
IR value both in open and close position.
Continuity of breaker in closed position.
Tripping and closing of breaker.
Functioning of all the tripping system/relays displayed on the control relay panel-such as differential o/c, earth fault, metering circuits and all other protection emanating from transformer - oil temp trip, OLTC trip, winding temp gauge trip, bucholz relay, inter trip etc, calibration of all the relays and complete Panel for time observed with respect to time setprimary injection of all the CTs, complete all as specified and directed.
Greasing/oiling of all the moving parts.
Operation/working of charging motor and limit switch.
Testing of 11KV, VCB breaker- 14 Nos through Power Grid Corporation of India PSEB. The equipments to be tested through Protection team PSEB are as under:-
Following tests to be carried out on each breaker ( Nos of Breaker - 12 Nos) ;-
IR Value for open/close circuit- fault relay, over load earth fault relay etc
Tripping and closing time in M/S.
Operation - both manual and through motor.
Functioning of indicators.
Continuity.
CT ration through primary injection.
Polarity test.
Testing of all the protection relay - i.e. o/c, earth fault, instantaneous, trip suspension, auxiliary relay etc.
Operation/working of charging motor and limit switch.
Calibration of all relay, male, female contracts of VCB.
Notes : (i) Any part/spare found defective during testing shall be repaired/replaced for which payment shall be made separately against respective items here in after. (ii) Test sheet shall be prepared as specified under PS clause and shall be produced.
Routine testing of 66 KV assets by Power Grid Corporation of India/PSEB to be tested areas under ;-
Transformer 66 KV 6.3/8 MVA - 01
Tests to be carried out
IR value test of both transformer and bushings.
PI value test for 20 seconds and 120 seconds.
No load current test.
Magnetic balance test.
Short circuit test.
Testing of tap changer.
Tan/delta test of transformer.
Dielectric strength of transformer Oil
Dissolved gas analysis test
66 KV SF-06 Breaker (01 Nos) - Tests to be carried out by the power Grid Corporation of PSEB Protectiion team. Following test shall be carried out :-
IR value both in open and close position.
Continuity of breaker in closed position.
Tripping and closing of breaker.
Functioning of all the tripping system/relays displayed on the control relay panel-such as differential o/c, earth fault, metering circuits and all other protection emanating from transformer - oil temp trip, OLTC trip, winding temp gauge trip, bucholz relay, inter trip etc, calibration of all the relays and complete Panel for time observed with respect to time setprimary injection of all the CTs, complete all as specified and directed.
Greasing/oiling of all the moving parts.
Operation/working of charging motor and limit switch.
Notes : (i) Any part/spare found defective during testing shall be repaired/replaced for which payment shall be made separately against respective items here in after. (ii) Test sheet shall be prepared as specified under PS clause and shall be produced. (ii) Test sheet shall be prepared as specified under PS clause and shall be produced.
Routine testing of 66 KV assets by Power Grid Corporation of India/PSEB to be tested areas under ;-
Transformer 66 KV 4 MVA - 01
Tests to be carried out
IR value test of both transformer and bushings.
PI value test for 20 seconds and 120 seconds.
No load current test.
Magnetic balance test.
Short circuit test.
Testing of tap changer.
Tan/delta test of transformer.
Dielectric strength of transformer Oil
Dissolved gas analysis test
66 KV SF-06 Breaker (01 Nos) - Tests to be carried out by the power Grid Corporation of PSEB Protectiion team. Following test shall be carried out :-
IR value both in open and close position.
Continuity of breaker in closed position.
Tripping and closing of breaker.
Functioning of all the tripping system/relays displayed on the control relay panel-such as differential o/c, earth fault, metering circuits and all other protection emanating from transformer - oil temp trip, OLTC trip, winding temp gauge trip, bucholz relay, inter trip etc, calibration of all the relays and complete Panel for time observed with respect to time setprimary injection of all the CTs, complete all as specified and directed.
Greasing/oiling of all the moving parts.
Operation/working of charging motor and limit switch.
Notes : (i) Any part/spare found defective during testing shall be repaired/replaced for which payment shall be made separately against respective items here in after. (ii) Test sheet shall be prepared as specified under PS clause and shall be produced. (ii) Test sheet shall be prepared as specified under PS clause and shall be produced.
Testing of 11KV breaker through Power Grid Corporation of India , through PSEB Protection team are as under:- (TOP-I )
Following tests to be carried out on each breaker ( Nos of Breaker - Seven in TOP I )
IR Value for open
Tripping and closing time in M/S.
Operation - both manual and through motor.
Functioning of indicators.
Continuity.
CT ration through primary injection.
Polarity test.
Testing of all the protection relay - i.e. o/c, earth fault, instantaneous, trip suspension, auxiliary relay etc.
Operation/working of charging motor and limit switch.
Calibration of all relay, male, female contracts of VCB.
Note: - Any part/spare found defective during testing shall be repaired/replaced for which payment shall be made separately against respective items here in after except for minor parts such as packing, nuts bolts, cotton waste etc for which cost shall be deemed to be included in the unit rate quoted for this item. (ii) Test sheet shall be prepared and produced to Engr-In-Charge.
Testing of 11KV breaker through Power Grid Corporation of India , through PSEB Protection team are as under:- (TOP-II)
Following tests to be carried out on each breaker ( Nos of Breaker - Nine in TOP II)
IR Value for open
Tripping and closing time in M/S.
Operation - both manual and through motor.
Functioning of indicators.
Continuity.
CT ration through primary injection.
Polarity test.
Testing of all the protection relay - i.e. o/c, earth fault, instantaneous, trip suspension, auxiliary relay etc.
Operation/working of charging motor and limit switch.
Calibration of all relay, male, female contracts of VCB.
Note: - (i) Any part/spare found defective during testing shall be repaired/replaced for which payment shall be made separately against respective items here in after except for minor parts such as packing, nuts bolts, cotton waste etc for which cost shall be deemed to be included in the unit rate quoted for this item. (ii) Test sheet shall be prepared and produced to Engr-In-Charge.
Servicing of HT VCB 11KV,630A of Kirloskar make alongwith tripping system and testing of vaccum circuit breaker 11KV, 630A, 25KA including taking out Breaker/trolley and carried out the fwg repair/tests made for smooth operation
Cleaning and greasing of mechanism- 01 Job
Tightning testing of mechanism parts- 01 Job.
Alignment testing and adjustment of mechanism- 01 Job.
Operation, testing of trip and close electrical and manual mode- 01 Job.
Spring charging testing electrical and manual mode- 01 Job.
Cleaning of panel insulater CT &PT unit- 01 Job.
Cleaning and tightning of control/wiring CT &PT unit- 01 Job.
Cleaning and testing of relay with current injection method- 01 Job.
Testing of auxillary relay - 01 Job.
Allingment of trolley, checking/greasing of shutter /lock of breaker
Note :- (a) Service will be carried out through any reputed Manfacturer authorised (ie L&T, Schenieder,CG,Kirloskar & ABB) Service Engineer only. (b) The cost of minor spare parts i.e nut and bolts, springs, grommets, dust cover, ring of isolator contacts, clips, pin for release prop, 'Y' Phase shround, over ride stop pin etc. unless or otherwise mentioned here-in-after but essentially required to make the panel serviceable shall be deemed to be included in the quoted rate.
Note: - (i) Any part/spare found defective during testing shall be repaired/replaced for which payment shall be made separately against respective items here in after except for minor parts such as packing, nuts bolts, cotton waste etc for which cost shall be deemed to be included in the unit rate quoted for this item. (ii) Test sheet shall be prepared and produced to Engr-In-Charge.
All as per items No 8 here in before but Areava / schenider make HT VCB Breaker including taking out and carried out repair/tests as per item no 8.01 to 8.12.
All as per items No 8 here in before but Crompton Make HT VCB Breaker including taking out and carried out repair/tests as per item no 8.01 to 8.12
Material and labour in replacement instant relay having tripping control of over current earth fault Cat No MC61A of LT make or Cat No IR 13010 of C&S make.
Supply and fixing in replacement automatic voltage regulator relay model AVR-102 (PE System Pvt Ltd Bangalore) complete all as specified.
Supply and fixing in replacement CT unit 100/50/5A, 15 VA 50Hz suitable for 11KV VCB Make Areva/Kirloskar/CG
Supply and fixing in replacement push button complete all as specified.
Supply and fixing in replacement Earth fault relay with IDMT complete all as specified.
Supply and fixing in replacement of sensor for HV/LV sefty element Model 2220 R2 complete all as specified.
Supply and fixing in replacement of HV/LV temp transformers model 2200 R2 complete all as specified.
Supply and fixing in replacement of silca gel for Transformers complete all as specified.
Dehydration of old transformer oil by heating and maintaing breaking capacity upto 55KV complete all as specified and directed by EIC.
Supply and fixing 66KV lightening surge arrestor 10 KA class -II metal oxide gapless type as per existing technical specification and size complete all specified.
Supply and fix spring charging electric motor suitable for kriloskar VCB of cap 630 Amp with complete accessories as per existing.
All as per item no 20 but areva/ schenider make VCB
All as per item no 20 but crompton make VCB
Supply and fixing in replacement of DC electric wiring kit complete suitable for Kriloskar/Areva/CG/ schenider made VCB 630 Amp and with male and female scoket 52 Pin type as per existing complete all as specified..
Material & labour for providing 20mm broken stone aggregate including spreading and levelling complete all as specified and directed.
Supply and fixing in replacement of energy saving environmental friendly, long life exclusive innvative die- cast aluminium IP65 flood light with high power LED's as light source, suitable high lighting architectural features of capacity 150W LED 6000K complete all as specified and directed by Engr-In-charge.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5 m in depth and getting out in soft / loose soil complete all as specified and directed.
All as per item no 27 here in before but depth exe 1.5 mtr but not exe 3.0 mtr In soft /loose soil
Returning, filling in, including spreading, leveling watering and well ramming in layers not exceeding 25cm soil / hard dense soil.
Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point.
M & L for sand cushioning to underground cable in trench complete all as specified and directed.
Supply and lay in repair in trenches/ road cross / floor etc , tube galvanised iron light grade with all fittings for protection of cable of size 100 mm dia bore all as specified & directed by Engr - In - Charge.
M & L for in repair XLPE insulated,screened, PVC bedded, galvanised steel strip earthed armoured electric power cable (heavy duty) with Aluminium conductor, 11000 volts ,grade cross sectional area 185 sq. mm 3 core complete all as specified and directed.
Supply only best quality wooden Bamboo ladder min height 9.5 mtr suitable for LT Pole step to step standared height complete.
Supply only best quality wooden Bamboo ladder min height 11 mtr suitable for HT Pole step to step standared height complete.
M& L for one layer of un-reinforced precast concrete cable cover class HV Type I,flat,size 300 x 180 x 40 mm laid flat in trenches over the cable with length of cover perpendicular to the direction of cable adjacent/abutting each other complete all as specified and as directed.
Supply, jointing, testing in repair end termination jointing kit heat shrinkable out door type, suitable for HT 11000 volts grade cable of size 185 sqmm 3 core complete all as specified and directed.
Supply in replacement of digital tap position indicator complete all as specified.
Supply and fixing in replacement of remote HV winding temparature indicator O-150 Degree Centigrade Model No 2220-R2 complete all as specified.
Supply and fixing in replacement of remote LV winding temparature indicator O-150 Degree Centigrade Model No 2220- R2 complete all as specified.
Supply and fixing in replacement remote winding temparature indicator complete all as specified.
Supply and fixing in replacement reomote oil tempatature indicator complete all as specified.
M & L for in repair XLPE insulated ,screened, PVC bedded, galvanised steel strip armoured electric power cable (heavy duty) with Aluminium conductor, 11000 volts ,grade cross sectional area 300 sq. mm 3 core complete all as specified..
Supply and fixing in replacement fault alarm complete all as specified.
Supply and fixing in replacement tap change in progress alarm complete all as specified.
Supply and fixing in replacement emergency stop complete all as specified.
Supply and fixing in replacement RYB indicator complete all as specified.
Supply and fixing in replacement of Amp meter DM 3 252 complete all as specified.
Supply and fixing in replacement of volt meter DM 3 251 complete all as specified.
Supply and fixing in replacement Earth fault relay instant under voltage relay/over voltage relay complete all as specified.
Supply and fixing in replacement of auxalary switch 8 NO + 8NC complete all as specified.
Supply and fixing in replacement trip coil assembly 24V DC complete all as specified.
Servicing and repair/maint of 66/11KV (HV) Power transformers safety controls at transformers end including Cleaning and greasing of mechanism (Replacement of parts will be measured under Item No 38 to 45 and 47 to 56) complete all as specified.
Supply and fixing in replacement of contactor coil 220 Volt DC complete all as per existing complete all as specified.
Supply and fixing in replacement of PLA relay of 220 volts DC , 04 MO, 04 NC complete all as specified.
M & L for in repair XLPE insulated, screened, PVC bedded, galvanised steel strip armoured electric power cable (heavy duty) with Aluminium conductor, 11000 volts ,grade cross sectional area 120 sq. mm 3 core complete all as specified.
Supply only heavy duty (Suitable for HT ) aluminium thimble of size 95 to 120 sqmm complete all as specified.
Supply and fixing in replacement three phase over current + earth fault digital relay with high set MC 61 ANX, 4000, Volts 24 - 240 AC /DC type MC 61 ANX 4 NO, Make L&T or equivalent complete with wiring all as specified..
Supply and fixing in replacement of muster trip relay voltage 220 volt DC VAZ type of model No VAZ 413YF67B, Make - Areva or equivalent.
Supply and fixing in replacement of Breaker control switch of 11KV VCB Make:- Kirloskar/Areva/Crompton for charging/discharging complete all as specified .
Supply and fixing in replacement of space heater 80Watt suitable for 11 KV VCB complete all as specified.
Supply and fixing in replacement of muster trip relay voltage 24 volt DC VAJ B type Make - Areva or equivalent complete all as specified.
Supply and fixing in replacement of remote indicator for WTI, HV winding temparature indicator + PPU unit + temparature 0 to 150 degree centigrate make :- Presimeasure controls limited for RTCC Panel
Supply and fixing in replacement of limit switch for 11 KV VCB of KEC Make all as specified and directed by Engr-In-charge.
Supply only heavy duty (Suitable for HT ) aluminium thimble of size 185 to 240 sqmm
Supply only heavy duty (Suitable for HT )aluminium thimble of size 300 to 400 sqmm
Supply and installed in replacement of 2 KVA invertor with battery backup upto 5 hrs including maint free batteries of cap 250Ah x 2 Nos including necessary wiring all as specified and directed.
Supply and fixing in replacment of openor latch for 11 KV VCB of KEC Make Model No C500 all as specified and directed by Engr-In-charge.
Supply and fixing of RYB LED type indicator operating with 220 volt DC supply all as specified and directed by Engr-In-charge.
Supply and fixing in replacement of Distribution chart For 11Kv Sub Stn (Khterpal & Red colny Power House) consisting of all the Distribution Sub stn and not less than 2mtr x 2mtr made of Flex in aluminium composit panels all as specified and directed by Engr-In-charge.
Supply and fixing in replacment of HRC Fuse cap 4 Amp suitable for 11 KV VCB DC Circuit all as specified and directed by Engr-In-charge.
Supply and fixing in replacment of HRC Fuse cap 10 Amp suitable for 11 KV VCB DC Circuit all as specified and directed by Engr-In-charge.
Servicing and repair/maint of HV SF6 Breaker 66 KV alongwith tripping system and carried out the fwg repair/tests made for smooth operation. (a) Cleaning and greasing of mechanism, Operation, testing of trip and close electrical and manual mode, Spring charging testing electrical and manual mode, Cleaning of panel insulater CT &PT unit, (a) Service will be carried out through any reputed manufacturer authorised (i.e. L&T, schenider, CG, kirloskar & ABB) Service Engineer only. (b) The cost of minor spare parts i.e nut and bolts, springs, grommets, clips, pin etc essentially required to make the breaker serviceable & additional qty of gas if require during servicing shall be charge by the contractor cost shall be deemed to be included in the quoted rate.
Supply and fixing in replacement of 11KV support insulator suitable for 11KV VCB (VCB make Areva, Kirloskar & CG, schenider), dismantling and mantling of VCB Panel labour charge,high quality 11KV VCB busbar Insulation Material and Nutbolts included in quoted rates complete all as specified
Supply and fixing, in replacement, air breather with silica gel as per existing suitable for 6/8 MVA Transformers main oil tank complete all as specified and directed.
Supply and fixing, in replacement, air breather with silica gel as per existing suitable for 6/8 MVA Transformers oil conservator tank complete all as specified and directed.
Supply and fixing, in replacement, air breather with silica gel as per existing suitable for 4 MVA Transformers main oil tank complete all as specified and directed.
Supply and fixing, in replacement, air breather with silica gel as per existing suitable for 4 MVA Transformers oil conservator tank complete all as specified and directed.
Supply only LT fire resistant PVC self adhesive electrical insulaion tape high quality size minimum 18 mtr long x 1.8 CM width complete.
Supply only HT Insulation tape High quality size minimum 20 mtr long x 1.8 CM width complete.
Material and Labour straight through joint/End termination kit of heats shrinkable suitable for 300 sqmm HT 3 core 11000 volts XPLE cable out door type complete all as specified and directed.
Supply,laying & fixing double wall corrugated (DWC) pipes made of high density polythyline (HDPE) with all accessories i.e. all type of joints,Sockets,Elbows,bends and End caps etc.. all as specified and directed by Engr in Charge of sizes size 120mm outer dia and 103mm inner dia for HT/LT UG cables. Make;-Telerex/Tirupati or E-in-C approved Make
Taking out carefully manually by excavation of existing cable with loops and relaying with DWC pipe the same after repair of cutting the damages / burnt parts of cable and reconnecting its into original positions complete with cable joints all as specified and directed by Engineer-in-Charge.Note:-(i) HT/LT Cable Joint & DWC Pipe will be measured and paid sepearetly. (ii) Unit rate shall be included in excavation and returning filling.
Excavates and relaying cables loops near the poles / transformers, cutting the damages/burnt parts of cable and reconnecting its into positions complete with thimbles, nut bolts, sleaves all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement of male and female contacts of gang operative switch made out of brass and rated capacity 200 amps ,make matching with the existing switch complete all as specified and directed .
Supply and fixing in replacement of copper ribbon suitable for 200 amps rated capacity gang operative switch, 45 CM long complete all as specified and directed .
Supply and laying or fixing in relacement 1100 Volts grade heavy duty cable with PVC insulated aluminium standard conductor served with an inner sheathing of PVC tape and over all PVC Sheathed in service connections , one twin core 16 Sqmm cable standard conductor cable flat or circular all as specified and directed by Engineer- in- Charge.
Supply & fixing in replacement Pin/Disc type type porcelain vitreous white, brown or green insulator including one galvanised mild steel straps, washers and nut for 11000 volts grade, including removal of existing insulators complete all as specified and directed.
Material & labour for cleaning away all grass vegetation, scapling shrubs bushes under grouth roots and trees not exceding 30 cm grith and removing rubbish upto distance of 50 mtr out the periphery of area under cleaness complete all as specified and directed.
Supply and spraying anti vegetation chemical liquid of 1ltrs bottle mixed with water as per direction of Engr in charge .
S&F in replacement HT Jumpers wire from top disc insulator to GOD and disc to disc in any lenth with complete nuts & thimbles all as required at site.
Supply, jointing, testing in repair straight through jointing kit heat shrinkable out door type, suitable for HT 11000 volts grade cable of size 185 sqmm 3 core complete all as specified.
M&L for testing of faulty HT cable by using HT high voltage fault locating machine and finding the fault and to be repaired the same including all T&P as required on site complete all as directed. Note :- (a) Each job includes finding out the location of each fault in HT feeder. (b) Necessary excavation,returning filling and removal deemed included in this job.(c) HT straight /end Joint and additional HT cable if required it will be measured and paid separetly under respective item.
Taking out existing gravels/hardcore material from the bottom of sub stn/equipment completely for cleaning and spraying of anti grass chemical and screnning the hardcore material and refill the same at places complete all as specified and directed by Engr in charge. Note:- Anti Grass chemical and loose filling of aggregate for topping up will be measured and paid separetly respective item.
Intrernational Engineers
Bharat Builder
Raman Electric Trading Co
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .