Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.6 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹12.9 L+₹71,640 (5.86%)Rejected-Finance | L2 | Rejected-Finance Not Being lowest | |
| 3 | L3₹16.6 L+₹4.4 L (35.8%)Rejected-Finance | L3 | Rejected-Finance Not Being lowest | |
| 4 | L4₹17.8 L+₹5.5 L (45.3%)Rejected-Finance | L4 | Rejected-Finance Not Being lowest | |
| 5 | L5₹18.5 L+₹6.3 L (51.2%)Rejected-Finance | L5 | Rejected-Finance Not Being lowest |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
21 Mar 2022, 6:00 pmClosed
GE Chandimandir
Garrison Engineer Chandimandir panchkula Haryana 134107
GE/CHM-94/2021-2022 REPAIR / REPLACEMENT OF WIRING ALONGWITH ITS ACCESSORIES IN MD ACCN IN SECTOR D AND F AT CHANDIMANDIR
2022_MES_509571_1
GE/CHM-94/2021-2022
Open Tender
Civil Works
Item Rate
180 days
Chandimandir
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
Garrison Engineer
₹60,000
Yes
7 Apr 2022
21 Feb 2022
28 Mar 2022
21 Feb 2022
21 Mar 2022
7 Mar 2022
Amount
Taking down carefully aluminum/copper point wiring on & including hard wood battens, surface conduit and board/blocks etc or through conduits for light , socket or power point ,fan point complete incl fitting such as switches ,sockets, ceiling rose , holder socket, light fitting, regulators and making good disturbed surfaces of wall, floor , ceiling etc and removing materials (other than those for which credit has been given by the contractor) to the MES stores yard for keeping in safe custody complete all as specified and directed.
Material and labour for point wiring with approved colour code multi stranded copper conductor, PVC insulated and unsheathed FRLSH cable of size 1.5 Sqmm ,1100 volts grade, two run of single core cable for phase & neutral and one run of single core multi stranded copper conductor, PVC insulated and unsheathed FRLSH cable of size 1.5 Sqmm ,1100 volts grade for earth continuity conductor to common earth and connected to earth dolly in and including new concealed PVC conduit terminated on and including new steel sunken boxes 1.2mm thickness covered with provision of 3mm thick plastic laminated sheet, comprising of One light /bell/buzzer point controlled by one switch or one fan point controlled by one switch &fan regulator, complete all as specified and directed. Note :Unit rate is inclusive of cutting chases in wall /foor/PCC and making good the disturbed surfaces to match the original finishes surface and nothing extra shall be paid on this account.
All as per serial item 2 herein before but for socket outlet 3 pin 5 Amps on same board complete all as specified and directed
All as per serial item 2 herein before but for socket outlet 3 pin 6 Amps on independent board complete all as specified and directed
All as per serial item 2 herein before but One socket outlet three pin ,6/16 Amp, independent board, with 2.5 Sqmm (nominal area ) FRLSH cable & 2.5 Sqmm (nominal area ) cable as earth continuity conductor
Material and labour for point wiring with approved colour code multi stranded copper conductor, PVC insulated and unsheathed FRLSH cable of size 1.5 Sqmm ,1100 volts grade, two run of single core cable for phase & neutral and one run of single core multi stranded copper conductor, PVC insulated and unsheathed FRLSH cable of size 1.5 Sqmm ,1100 volts grade for earth continuity conductor to common earth and connected to earth dolly in existing conduit terminated on and including new steel sunken boxes 1.2mm thickness covered with provision of 3mm thick plastic laminated sheet, comprising of One light /bell/buzzer point controlled by one switch or one fan point controlled by one switch &fan regulator, complete all as specified and directed. Note : Unit rate is inclusive of making good the disturbed surfaces to match the original and nothing extra shall be paid on this account. Note :Unit rate is inclusive of cutting chases in wall /foor/PCC and making good the disturbed surfaces to match the original and nothing extra shall be paid on this account.
All as per serial item 6 herein before but for socket outlet 3 pin 5 Amps on same board complete all as specified and directed
All as per serial item 6 herein before but for socket outlet 3 pin 6 Amps on independent board complete all as specified and directed
All as per serial item 6 herein before but One socket outlet three pin ,6/16 Amp, independent board, with 2.5 Sqmm (nominal area ) FRLSH cable & 2.5 Sqmm (nominal area ) cable as earth continuity conductor
Supply & Fixing for switch piano, flush type, 5 amps, 230 volts, single pole, one way (ISI marked) complete all as directed by Engineer-in-charge
Supply & Fixing for switch piano, flush type, 15 amps, 230 volts, single pole, one way (ISI marked) complete all as directed by Engineer-in-charge
Supply & Fixing for sockets outlet multipurpose 2 in 1 pin, 5 and 15 Amps flush type ISI marked all as specified and directed by Engineer-in-charge
Supply & Fixing for sockets outlet multipurpose 2 in 1 pin, 5 and 15 Amps flush type ISI marked all as specified and directed by Engineer-in-charge
Supply & Fixing for stepped type electronic fan regulator flush type complete all as specfied and directed.
Supply and fixing for electric Bell, AC, 230 volts, single pole all as specified and directed by Engineer-in-charge.
Supply & Fixing for bell push, flush type, 5 amps, 230 volts, single pole, complete all as directed by Engineer-in-charge
Supply & Fixing for ceiling rose, PVC or polycarbonate of size 65mmx50mm three terminals (ISI marked) all as specified and directed by Engineer-in-charge.
Supply and fixing for Lamp holder, PVC/Polycarbonate type with back plate angular type fixed on wall suitable for batten fitting including supply and fixing of 7 watts LED lamp complete all as specified and directed.
Supply and fixing for bulk head fitting in engineering plastic housing with clear prismatic diffuser 6 watt capacity complete all as specified and directed.
Supply and fixing indoor decorative extruded aluminium anodized housing /CRCA sheet steel coated housing (suitably coated to improve resistance against corrosion) LED batten type luminaries' (LED batten shall be prewired box type, retrofit solution with and including replaceable retrofit cool day white LED tube rod with well designed aluminium heat sink /aluminium housing for excellent heat dissipation; 4 feet (appx) size, high efficiency electronic driver, system wattage not more than 20 watt (lumen output not less than 2000 lumen), UV radiation light fitting with wall mounting arrangement and making connections with PVC insulated copper conductor 3 core cable of 0.5 sq mm" complete all as specified and directed.
Supply and fixing indoor decorative extruded aluminium anodized housing /CRCA sheet steel coated housing (suitably coated to improve resistance against corrosion) LED batten type luminaries' (LED batten shall be prewired box type, retrofit solution with and including replaceable retrofit cool day white LED tube rod with well designed aluminium heat sink /aluminium housing for excellent heat dissipation; 2 feet (appx) size, high efficiency electronic driver, system wattage not more than 10 watt (lumen output not less than 1000 lumen), no UV radiation light fitting with wall mounting arrangement and making connections with PVC insulated copper conductor 3 core cable of 0.5 sq mm" complete all as specified and directed.
Taking down carefully old copper or aluminium sub main wiring of any Nos of wiring and size with earth wire on wooden batten/ surface conduit/ casing- capping complete with its all accessories and making good disturbed surfaces of wall , floors etc complete all as specified & directed by Engineer-in-charge.
Supply and fixing sub main wiring with two single core FRLSH PVC insulated and unsheathed cable with copper conductor of size 6 Sqmm (nominal area), 1100 Volt grade(with approved colour coding as per IS) with and including continuous earth wire of size 6 Sqmm PVC insulated and unsheathed FRLSH multi stranded copper conductor 1100 volts grade , and connected to main board drawing through PVC concealed conduit 25mm size(minimum size), cutting chases in walls for PVC concealed conduit and making good the disturbed surfaces after taking out old unserviceable sub main wiring complete by provding by wall putty/POP after mason work and finshing to match the original surfaces and nothing extra shall be paid on this account all as specified and directed. Note : (i) For the purpose of measurement, 2 single core of 06 sqmm and one single core of 06 sqmm cable along with PVC conduit shall be considered as 1 running metre. (ii) cutting chases and PVC conduit will be measured and paid separately
Disconnecting the power supply and taking down carefully by unscrewing from boards fittings and fixtures such as DBs, Junction Box, Panels of any size complete with all MCCB's ,MCB's etc and removing from site, all as specified and directed by Engr-in charge.
Supply and fixing MCCB, 100 to 125 Amps, four pole,3 phase ,36KA, 415 volt with adjustable thermal and maganetic release complete all as specified and directed
Supply and fixing for vertical TPN distribution board double door flush mounting with provisions for MCCBs incomer upto 100 to 125Amps & outgoing 4 way having IP 54 protection complete all as directed
Supply and fix MCB DB, with provision for incoming 2 pole (MCB / Isolator ) and single phase outgoing, suitable for surface and flush mounting, IP 43 protection, double door of metal 8 way complete all as specified and directed
Supply & Fixing for MCB ,SP , 240 volt, 6Amps to 32Amps, 10 KA , 'C' series including connection with suitable size aluminium / copper lugs complete all as specified and directed
Supply & Fixing for MCB ,SP , 240 volt, 63Amps, 10 KA , 'C' series including connection with suitable size aluminium / copper lugs complete all as specified and directed
Supply & Fixing for MCB ,SPN, 240 volt, 40Amps, 10 KA , 'C' series including connection with suitable size aluminium / copper lugs complete all as specified and directed
Supply & fixing of 25 to 32 mm dia, rigid non metallic PVC concealed conduit, 'ISI marked', inclusive of all fittings (such as junction boxes, bends, elbows, tees, reducers, bell mouth tube ends) and all fixing accessories such as couplers lock nuts, saddless, pipe hooks etc for wiring, complete all as specified
Cutting chases in brick walls, pinning in, making good to facings where required and pointing in cement mortar (1:3) to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc and cutting chases for concealed water tubing or concealed conduit wiring etc and making good, cutting not exceeding 10cm girth complete all as specified & directed by Engineer-in-charge.
Material & labour, earthing complete with galvanized steel earth plate electrode 60cmx60cmx6.00mm thick, burried directly in ground vertically to a depth not less than 2.25m below normal ground level, with top edge of the plate not less than 1.5m below normal ground level, earth plate surrounded by 15cm thick and packed alternate layers of charcoal dust and common salt, connected with and including earth lead of GI wire 4mm dia (8 SWG) by means of bolts, nuts, check nuts and washers of galvanized iron or thimbles and other end of the earth wire connected to main switch board and protected by galvanized iron pipe light grade 15mm dia bore including watering pipe 20mm dia bore GI light grade (ISI marked) with funnel and wire mesh, including all necessary excavation and earth work, PCC chamber in plain cement concrete (1:3:6) type C-1 and pit cover of presast RCC with MS frame etc and all as shown in electrical plate No 3 of MES Sch Part-I (2009), complete all as specified and directed. Note(s) :- (i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with XPM not less than 4Kg/Sqm. (ii) PCC chamber shall be constructed 500 mm away from the edge of earth pit. (iii) Rate shall include earth lead and protection pipe of length 7.5m, excess beyond 7.5m length required at site shall be measured and paid separately. (iv) Earth resistance should be less than 3Ohm. In case the test results are not found below 3Ohm, complete earthing will be redone without any extra cost to Govt.
Supply and fix in repair multipurpose PVC box with 05 Amps multipin socket and 05 Amps switch with necessary connection including taking down oldunserviceable/rusted box complete and making good the surface as per existing complete all as specified and directed
Supply and fix in repair with 15 Amps multipin socket and 15 Amps switch with necessary connection including taking down old rusted box complete and making good the surface as per existing complete all as specified and directed
Supply and fixing in repair for PVC junction cover circular type with suitable size screws and washers complete all as specified and directed by Engr-in Charge
Taking down old rusted sunken box any type/capacity including cutting/chases and making good to disturb surface all as specified and directed by Engr-in Charge
Supply and fix sunken box 2 mm thick 4"x4" including cutting/chasis flush to wall and making good to disturbed surface complete all as specified and directed
Supply and fix sunken box 2 mm thick 6"x4" including cutting/chasis flush to wall and making good to disturbed surface complete all as specified and directed
Supply and fix sunken box 2 mm thick 6"x 6" including cutting/chasis flush to wall and making good to disturbed surface complete all as specified and directed
Supply and fix sunken box 2 mm thick 6"x 8" including cutting/chasis flush to wall and making good to disturbed surface complete all as specified and directed
Supply and fix sunken box 2 mm thick 8"x 8" including cutting/chasis flush to wall and making good to disturbed surface complete all as specified and directed
Supply and fix sunken box 2 mm thick 10"x 8" including cutting/chasis flush to wall and making good to disturbed surface complete all as specified and directed
Supply and fix in replacement of hylum sheet 3mm thick with machine screw and washers including cutting for switch/socket suitable for 4"x4" sunken box complete all as specified and directed by Engr-in Charge
Supply and fix in replacement of hylum sheet 3mm thick with machine screw and washers including cutting for switch/socket suitable for 6"x4" sunken box complete all as specified and directed
Supply and fix in replacement of hylum sheet 3mm thick with machine screw and washers including cutting for switch/socket suitable for 6"x 6" sunken box complete all as specified and directed
Supply and fix in replacement of hylum sheet 3mm thick with machine screw and washers including cutting for switch/socket suitable for 6"x 8" sunken box complete all as specified and directed
Supply and fix in replacement of hylum sheet 3mm thick with machine screw and washers including cutting for switch/socket suitable for 8"x 8" sunken box complete all as specified and directed
Supply and fix in replacement of hylum sheet 3mm thick with machine screw and washers including cutting for switch/socket suitable for 10"x 8" sunken box complete all as specified and directed
Supply and fix in repair decorative wall light fixture made up polycarbonate, suitable for 15 W B-22 base . Make- Havells CITY 3 Cat Part LHDL06160099or equivalent make in Apppx 'C'
Supply and fix sheet metal enclosure of size of 915mm x 610mm x 200mmwith locking arrangement flush to wall suitable for fixing of 04 Nos energy meter including taking down carefully energy meter including connection complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3.5 corecomplete all as specified and directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation etc or for shaft, wells, cesspits, manholes, pier holes etc not exceeding 10 sqm on plan and getting out in soft and loose soil all as specified & directed by Engineer-in-Charge.
Returning filling in including spreading, levelling, watering and well ramming in layers not exc.25cm thick each layer of soil all as specified.
Removal excavated soil to a distance exc 250 but n.exc 500m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified & directed by Engineer-in-Charge.
Supply and fix 40mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS 14930 Part-II with anti rodent and non flame propogating properties of approved colour with fittings for cable protection from approval make complete , all as specified and directed Make : Finolex / Duraline /Rex
CHADHA ENGINEERS
KIRTI ELECTRICALS
Vasudeva Trading Co.
Sabhyata Electrical and Mechanicals
M/s Krishan Aggarwal
Horizon Construction Company
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .