| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.0 LAccepted-AOC 1389 RADHETENAMENT SOCIETY SARDAR ROAD SURENDRANAGAR SURENDRA NAGAR GUJARAT 363001 | SURENDRANAGAR | GUJARAT | 363001 | L1 | Accepted-AOC Accepted being L1 | |
| 2 | L2₹20.8 L+₹78,360.10 (3.91%)Rejected-Finance 16 BAITHAKKHANA ROAD 16 BAITHAKKHANA ROAD SEALDAH BAITHAKKHANA ROAD SEALDAH BAITHAKKHANA ROAD SEALDAH KOLKATA | L2 | Rejected-Finance Rejected being L2 | |
| 3 | L3₹21.0 L+₹99,260.20 (4.95%)Rejected-Finance C O SREE SUMANGAL A T ROAD TINSUKIA ASSAM 786125 | TINSUKIA | DIBRUGARH | ASSAM | 786125 | L3 | Rejected-Finance Rejected being L3 | |
| 4 | L4₹21.1 L+₹1.1 L (5.38%)Rejected-Finance AT ROAD MES TINALI PO CHABUA DISTT DIBRUGARH ASSAM 84 | CHABUA | DIBRUGARH | ASSAM | 786102 | L4 | Rejected-Finance Rejected being L4 | |
| 5 | L5₹21.9 L+₹1.9 L (9.33%)Rejected-Finance COLLEGE ROAD CHABUA PO CHABUA DIST DIBRUGARH ASSAM 786184 | DIBRUGARH | ASSAM | 786184 | L5 | Rejected-Finance Rejected being L5 |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
21 Aug 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE(AF) CHABUA
GE(AF) CHABUA, POST-CHABUA AIR FIELD, DIST-DIBRUGARH, ASSAM-786102
REPAIR/MAINTENANCE OF EXTERNAL ELECTRIC SUPPLY AT BALIJAN STN UNDER GE(AF) CHABUA
2021_MES_464181_1
328/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE(AF) CHABUA
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Yes
GE(AF) CHABUA
₹40,000
Yes
15 Sept 2021
31 Jul 2021
23 Aug 2021
31 Jul 2021
21 Aug 2021
14 Aug 2021
31 Jul 2021 - 7 Aug 2021
60 days
Amount
Supply, laying in trenches through pipes under road, floor/on wall/on pole or any other indicated place & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade, of size 3 core 95 sqmm including taking down of old unserviceable cable complete all as specified and as directed.
Supply laying & testing of XLPE insulated, armoured, heavy duty electric under ground cable with stranded aluminum conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminum lugs complete of size 25 Sqmm nominal cross section x3.5 core including taking down of old unserviceable cable complete all as specified and as directed.
All as per item 2 above but Size 35 Sqmm X 3.5 core complete all as specified and as directed.
All as per item 2 above but Size 50 Sqmm X 3.5 core complete all as specified and as directed.
All as per item 2 above but Size 70 Sqmm X 3.5 core complete all as specified and as directed.
All as per item 2 above but Size 95 Sqmm X 3.5 core complete all as specified and as directed.
All as per item 2 above but Size 120 Sqmm X 3.5 core complete all as specified and as directed.
Supply and fixing in repairs steel tubes, galvanized, light grade, ISI marked 80mm bore for protection of cable under floor, road and on wall complete all as specified and as directed.
Excavating in trenches n exc 1.5m wide and n exc 1.5m deep and getting out in soft/loose soil complete all as specified and directed.
All as per item No. 9 here-in-before but in hard/dense soil complete all as specified and directed.
Excavation in trenches in hard/dense soil n.exc 1.5m wide and exc 1.50m but n.exc 3.0 m in depth for foundation or shafts, wells cesspit, manholes, pier holes, cable laying, sewage/water lines etc complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers n exc 25cm complete all as specified and directed.
Removing excavated material n exc 50m and depositing where directed at a level n exc 1.5m above the starting point complete all as specified and directed.
Material and labour for sand cushioning with dry river sand in trenches for cushioning of underground cable line including spreading, leveling, well ramming completed all as specified and directed.
S&F Sub-Class B Brick, well burnt, laid breadth-wise along the length of Cable laid in Trenches over Sand Cushion laid for UG Cable Protection, complete all as specified and as directed.
M&L for cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE aromoured aluminum conductor cable of size 50 sq mm to 95 sq mm complete all as specified and as directed.
M&L for cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE aromoured aluminum conductor cable of size 50 sq mm to 95 sq mm complete all as specified and as directed.
Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminum conductor cable of size 50 sqmm to 95 sqmm complete all as specified and as directed.
M & L for rewinding of 433 Volts LV coils of transformer, removing unserviceable material, reinsulation with new insulated materials three layer complete and re-winding as per existing size of core of transformer including heating, varnishing etc complete all as specified and directed.
M & L for rewinding of 11/0.433 KV HT coils of transformer, removing unserviceable material, reinsulation with new insulated materials three layer complete and re-winding as per existing size of core of transformer including heating, varnishing etc complete all as specified and directed.
M & L for rewinding 433 Volts LV coils of transformer of using proper size new copper wire suitable for working voltage 11 KV complete all as specified and directed.
M & L for rewinding 11/0.433 KV HV coils of transformer of using proper size new copper wire suitable for working voltage 11 KV complete all as specified and directed. NOTE for item No 21 and 22:- (i) Oil filtration, supply of new oil will be measured separately. (ii) All petty parts including nut, bolts, gasket minor weldings are deemed to be included the rate quoted. (iii) The rate for transport and lifting of transformer by crane should be deemed to include in the rate quoted.
Dehydration of HV/EHV grade transformer oil (On line/off line), minimum three cycles to achieve dielectric strength upto 60KV for EHV grade and upto 40 KV for HV grade, complete all as specified and directed. Note - Centrifuging Machine with all T&P & testing eqpt required for dehydration to be arranged by contractor.
Supply and filling, transformer oil EHV grade as per IS-335 of 1993 Part-II, complete all as specified and directed.
Supply and stringing in repair ACSR conductor of any size for LT over head line as directed including fixing to insulators with proper size of binding wire complete all as specified and as directed.
All as per item No. 25 but GI wire 4 mm dia complete all as specified and as directed.
Supply and fixing in repairs mild steel galvanized stay assembly set complete comprising of 14mm dia, 400mm long stay bow, 1800 mm long stay rod 20mm dia, 300mm x 300mm x 6mm stay plate, thimble, GI stay wire of 7/8 SWG upto required length including loop type insulator of vitreous porcelain, small size with overall dimensions 90x140mm, clearance of hole 25.5mm, all as shown in electrical plate No.1 of MES Schedule part-I 1991 complete all as specified and as directed.
M & L in repairs for Cross arms, bracing, supports, clamps and back plate, fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of aluminum paint over a coat of red oxide primer, complete all as directed.
Supply and fixing steel tubular pole, swaged, complete with cast iron base plate, finial taper plug, bolts, nuts, washer and screws including painting with two coats of of aluminum paints over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to portion embedded in PCC including numbering of poles with two coats of synthetic enamel paints, type 410-SP-22 (8.5 meter long) including taking down old unserviceable one complete all as specified and directed. Note:- Earthwork and PCC shall be measured and paid separately under respective items.
M & L for cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregate in foundation, filling and mass complete all as specified and directed.
M & L for cement concrete 1:3:6 type C-2 using 40 mm graded stone aggregate in foundation, filling and mass complete all as specified and directed.
M & L for providing cement concrete 1:2:4 type B-1 using 20 mm graded stone aggregate in copings to poles & the like etc including weathering, slightly rounded or chamfered angles and throating as complete all as specified and directed.
M&L in repair for Air break Switch triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 200 amps suitable for 11000 volts complete all as specified and directed.
M&L for drop out expulsion fuse single pole suitable for 11000 volts grade upto 50 amps complete all as specified and directed.
S & F in repairs Pin type, porcelain, vitreous, white, brown or green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 50 mm height,65mm dia for 550 volts grade complete all as specified and as directed.
M&L for replacement of pin type insulator porcelain, vitreous, white, brown or green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 150 mm height, 150 mm dia for working pressure 11000 volts grade complete all as specified and directed.
M&L for replacement of disc type insulator, porcelain, vitreous 145 mm high and 255 mm dia ball and socket type white, brown or green single disc assy for tension with tension clamps for conductors, working pressure 11000 volts complete all as specified and directed.
Re-stringing Over Head Line ACSR Conductor and earth wire of any size and type on LT poles including disconnection on Existing Lines by un-binding at Each Pin/Shackle Type Insulator, re-fixing the same after stretching Conductor, removing excess Sag, maintaining proper distance between Conductors adjusting line dividers etc and cutting trimming of tree branches up to 2 mtr clear distance from wire, complete all as directed by Engr-in-Charge.
Supply and fixing in replacement rubber mat of 1 meter x 2 meter x 10 mm complete all as specified and as directed.
Disconnect and taking out the Numeric/ Microprocessor based relay of any type of any Make from 11 KV HT panel, cleaning the contacts, calibrating the relay by conducting secondary injection tests, checking of current transformer, rectification of defects in control wiring for proper tripping of circuit breakers through CTs and relay and tripping coils, adjustment/setting to plug and time multiplier settings of the relay to achieve the discrimination in tripping, tune/synchronise upstream breaker relay settings, re-installation of relay, testing & commissioning etc complete all as specified and as directed.
S&F in repair Master Trip Relay suitable for 11 KV HT panel for protection system complete all as specified and as directed.
S&F in repair 110V DC closing coil for 11 KV HT panel for protection system complete all as specified and as directed.
S&F in repair 110V DC tripping coil for 11 KV HT panel for protection system complete all as specified and as directed.
Taking down HT switch gear (Vacuum circuit breaker ) of capacity 11 KV 250/350 MVA comprising of following repairs, overhauling, servicing and refixing the same after repairs/ overhauling complete all as specified and as directed. Notes:- (a) Tripping off the breaker, lowering the breaker with raising/lowering handle and pulling out the breaker complete from the panel along with the trolley for servicing/inspection/overhauling (b) Servicing/Inspecting/checking of automatic safety shutter operation for serviceability and replacement of spares if required. (b) Servicing/Inspecting/checking of circuit spout and circuit spout connections for RYB phases and replacement of spares if required. (c) Dismantling and checking of cross bar assembly, fixed contacts and current carrying parts of the breaker, trolley, insulated assembly and checking lamination with clamps, epoxy spout, isolator assembly etc. (d) Setting, reassembling, cleaning, adjustment of fixed contacts, main contact, arcing contacts and chamber baffle pot assembly, moving contact for proper setting of auxiliary contacts operating mechanism. (e) Servicing/Inspecting/checking of secondary sockets/bus bar earthing plugs/earthing sockets and replacement of spares if required. (f) Checking, setting and adjustment of lowering and raising operation of the breaker trolley. (g) Lubrication and greasing of all moving parts of the trolley, stopper bolt for proper operating and closing of shutter gear, isolation resistance of trolley of with vacuum interrupter assembly.
h) The inspection of HT switch gear shall involve:- (i) Inspection of truck & hoist assembly. (ii) Inspection of tank assembly & barriers. (iii) Inspection of assembly & components of solenoid assembly. (iv) Inspection of assembly & components of dependent mechanism. (v) Inspection of assembly & components of spring box mechanism. (vi) Inspection of motor mechanism spring charge assembly (vii) Inspection of assembly of trip unit & related components (j) The rate quoted shall be deemed to include for necessary T&P, nuts, bolts, washers, gasket, insulation tape, compound, painting of VCB panels with approved colour all as per existing etc. to put in to the VCBs and panels in serviceable condition, testing and commissioning all as specified and as directed by the Engineer-in-Charge. (k) Major spares like Breaker bushings, vacuum interrupter assly, bus bar spout, bus bar spout connections, circuit spout/circuit spout connections/buffer fixed contacts, moving contacts, tank assly/barriers, solenoid spares, dependent/spring mechanism/ motor mechanism, trip unit etc will be measured and paid separately under relevant items of Schedule 'A'. However the rate quoted shall be deemed to include for any other minor spares require replacement. (l) the servicing shall be carried out by Authorized service centre as approved by GE.
Supply and fix in repairs of LED Indication Lamps for VCB panel complete all as specified and directed.
S & F in repairs of single unit resin cast type current Transformer of rating 11 KV, ratio 50-25/5-5A, burden 5P10 for protection an 10VA for metering complete all as specified and directed.
S & F in repairs of single unit resin cast type potential Transformer of rating 11 KV, ratio 11KV/ √3/110V/√3 burden 100VA, pistol type complete all as specified and directed.
M&L for dismantling the cable connections of four pole/ three pole Air circuit breaker of capacity 800 to 1250 Amps, 415 V 50 HZ, strip opening the Air circuit breaker, inspecting the parts for serviceability/overhauling complete and carrying out the following repairs/maintenance :- a) Cleaning the insulation parts including bushings with CTC solution. b) Checking the alignment and condition of movable and stationary contacts and adjust them all as per manufacturer's instructional manual c) Check the bolts, nuts, washers, cotter pins and all terminal connections are in place and tights. Replace the worn-out parts. d) Check arching contact for damage . e) Clean and lubricate the operating mechanism with a light machine oil for pins and bearings and with a non-hardening grease for the wearing surfaces. Adjust breaker operating mechanism all as per manufacturer's instructional manual. f) Checking / inspecting shunt trip coil for serviceability and replacing the same if required. g) Checking control device free for operation. h) Check after servicing the circuit breaker to verify the contacts move to the fully opened and fully closed positions, that there is an absence of friction and that the electrical operation is functional. Note:- The rate quoted deemed to be inclusive of T&P and minor spares like lubricants, nuts/bolts/washers/ pins etc. Major spares like Shunt release & trip coil etc will be measured & paid separately under relevant schedule items.
Supply only fixed arching contact suitable for air circuit breakers of rating 800 Amps to 1250 Amps complete all as specified and directed.
Supply only moving arching contact suitable for air circuit breakers of rating 800 Amps to 1250 Amps complete all as specified and directed.
Supply only shunt release (110 /220 V DC or 240 V/415 V AC) suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing of Make complete all as specified and directed.
Supply only under voltage release 240V AC for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing of Make complete all as specified and directed.
Supply only trip coil suitable for air circuit breakers of rating 800 Amps to 1250 Amps complete all as specified and directed.
Supply only draw out breaker suitable for air circuit breakers of rating 800 Amps to 1250 Amps complete all as specified and directed.
Supply and fix in repair motor 240 V AC for air circuit breakers of rating 800 Amps to 1250 Amps complete all as specified and directed.
Supply and fix in replacement Tap changer assy of 11/0.433 KV transformer 500 to 750 KVA including replacing worn out connection sleeves, insulated plates, nut, bolts & washers and testing after replacement complete all as specified and directed.
S&F in repairs bushing with insulator, packing, nut, washers etc on HT side suitable for 500 KVA to 750 KVA 11000/433V complete all as specified and directed.
S&F in repairs bushing with insulator, packing ,nut, washers etc on LT side suitable for 500 KVA to 750 KVA 11000/433V complete all as specified and directed.
Supply and fixing in replacement of heavy duty breather assembly of capacity 0.5 kg with silica gel crystal complete all as specified.
Balancing of load on three phases and neutral of transformer by applying necessary engineering efforts like interchanging of jumpers, interchanging of service connections on over head conductors, in LT feeder pillar boxes or any other such efforts to make a balanced distributions of electrical load on transformer all as directed and required as per site conditions including submission of corrected readings of meters. Note:- The unit rate quoted will include the cost of necessary tools, safety devices and plants required for the purpose.
Supply and fixing in repairs gun metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed for 25 mm bore pipe complete all as specified and as directed.
Supply and fixing in repairs gun metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed for 50 mm bore pipe complete all as specified and as directed.
Supply and fix, in repairs, LED 25 to 40 watts post top lantern with aluminum die-cast housing cum heat sink in IP-65 protection including all fixing arrangements, complete all as specified and directed.
Supply and fix in repairs, garden light fitting, 8 to 12 watts LED bollard with soft 360 degree light IP-65 protection, resistant to corrosion better optics for uniform distribution including all fixing arrangements, complete all as specified and directed.
Dismantling and taking down old Aluminum strip 25 x 3.15 mm (lightning conductor) with saddles and air termination from roof/wall and making good the surface of wall/roof and white/colour washing to match with the existing surface complete all as specified and as directed.
Supply and fix in repairs Air termination, single pointed aluminum rod 12mm dia and 300mm long all as specified and directed.
Supply and fix in repairs Aluminum strip 25 x 3.15 mm with PVC/porcelain insulators, nut bolts, fixing screws etc for roof conductors and down conductors on wall/roof all as specified and directed.
Schedule of Credit
M/s HALDER ENTERPRISE
M/S D P BERLIA
M/S R G Construction
M/s PRABIR ENTERPRISE
FREEZCON
STANDARD ELECTRIC WINDERS
MAA COMMUNICATION
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .