CE/TTPS
O/o CE/TTPS
TTPS OPN MPM II ACP Reconditioning of cooling tower by renewing of louvers, wire meshes, spray header pipes, MS structural materials, Ladder at Service Building and painting the cooling tower of Service building and Switchyard I AC Plant
2026_EB_715809_1
CE/SE/O/TTPS/Spec.No.163/26-27
Open Tender
Miscellaneous Works
Item Rate
25 days
TTPS
Please refer Tender documents.
5 documents required · 5 mandatory
₹0
₹5,400
Yes
17 Oct 2026
17 Oct 2026
3 Nov 2026
17 Oct 2026
2 Nov 2026
17 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Charges for fabrication and erection of structural works by cutting and welding MS structure of channels, angles and MS Ladder after removing the existing damaged MS structure & MS Ladder at service building cooling tower, the rates including the shifting of materials, T&P hire charges, consumables etc., as per the direction of engineer incharge. | 0.53 | Ton | - | - |
| 1.1 | Material on Contractor scope
Ms Angle (65x65x6 mm) | 467 | Kg | - | - |
| 1.2 | Material on Contractor scope
MS Angle (50x50x6) | 67 | kg | - | - |
| 2 | Charges for fabrication and erection of louvers size (940 X340 )mm ; 52 Nos, by the G.I. Sheet 1mm thick after dismantling the existing damaged louvers of service building cooling tower. The rates including the materials like the bolt & nuts and other consumables.
louvers size (940 X 340 )mm | 52 | Nos | - | - |
| 2.1 | Charges for fabrication and erection of louvers size (890 X 340) mm;52 Nos by the G.I. Sheet 1mm thick after dismantling the existing damaged louvers of service building cooling tower. The rates including the materials like the bolt & nuts and other consumables.
louvers size (890 X 340 )mm | 52 | Nos | - | - |
| 2.2 | Material on Contractor scope
G.I sheet=2.5m X 1.25m | 319 | kgs | - | - |
| 3 | Charges for fabrication and erection of 3 Nos wire meshes at approximate size (1.8 X 1.8)mtr after cutting and dismantling the existing damaged wire meshes, fabricated with new M.S. flat (25 X 5 mm) and S.S. wire meshes the rates including the consumables, T&P hire charges M.S. Flat etc., | 3 | Nos | - | - |
| 3.1 | Material on Contractor scope
SS Wire meshes | 1 | No | - | - |
| 3.2 | Material on Contractor scope
MS Flat | 21.6 | kgs | - | - |
| 4 | Charges for fabrication and erection of spray header pipe (3 Nos) of size 40 mm M.S pipes providing holes in spray pipes after cutting and removing of the existing corroded pipes approximate total length 6m in service building cooling tower as per the direction of engineer in charge. | 1 | No | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.26 MB
BOQ_859837.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .