CWS(X) Talcher, Southbalanda, Talcher, Angul Odisha-759116. mobile no. 9438878244. email so-enm-cwst.mcl(at)coalindia.in
re-insulation and recoiling of the old and usable coils of one 1000KVA -11/0.440KV, a 1000KVA -11/3.3KV, and two 750KVA 3.3/0.440KV Transformers of CWS(X) Talcher MCL.
2025_MCL_327078_1
MCL/GM/CWST/EnM/TRNF/Coil /24-25/42 DTD 27.01.2025
Open Tender
Miscellaneous Works
Item Rate
20 days
at Bidder primises
As per NIT documents
4 documents required · 4 mandatory
₹5,000
23 Feb 2025
28 Jan 2025
15 Feb 2025
29 Jan 2025
14 Feb 2025
29 Jan 2025
29 Jan 2025 - 4 Feb 2025
Amount
Item Description/ Heading
Re-insulation and recoiling of 3Nos old and used primary coils of 1MVA 11/0.415 KV Distribution Transformer with proper grade of insulation. i. Covering should be TPC ii. Dimensions and other insulation should be exactly as per old coils. Primary coil data: Type-Disc coils 1. 99.9% Electrolytic Bright annealed copper strip with TPC. 2. No of Conductor: (i) For DISC coil = 1 3. size of conductor: Bare: 7.7X1.3MM , TPC: 8.1X1.7MM 4. No of DISC : 42 As per sample,TURN/DISC: 22(approx) 5. Coil Size: ID:287mm, OD:360mm and HT:480mm 6. Weight of each coil: 90 Kg (including insulation) 7. No. of coils: Three(03) 8. Tap Range : +10% to -10% ( In stpes of 2.5%) Detail scope of work 1. Scraping of the old insulation, acid washing and pre annealing for all bend straightening of the disc coils. Straightening of the bend portions through roller die, final annealing and covering with four layers of Kraft papers of specific sizes as required, with in clock and anti clock direction with overlapping and bringing the insulated conductor as per specification provided. 2. Formation of disc coils with all lock joint cut spaces as required, pre-compressed press-phan boards for separators and winding the coils with 14% Rupatan sticks if required. Finally placement of the coils in heat chamber and pressing the same till the desired specifcations are achieved. (total cost including materials, manpower, transport to and fro, packing and forwarding charges and other overheads)
Re-insulation, recovering and recoiling of 3nos old and used Secondary coils of 1MVA 11/0.415KV Power Transformer with proper grade of insulation. i. Covering should be TPC ii. Dimensions and other insulation should be exactly as per old coils Secondary coil data: Type-cylinderical 1. 99.9% Electrolytic Bright annealed copper strip with TPC. 2. No. of conductor - 12(2AX6R) 3. size of conductor: Bare: 11.0mm X 3.3mm TPC: 11.4mm X 3.7mm 4. No of TURN:20 5. Coil Size: ID:215mm, OD:262mm and HT:520mm 6. Weight of each coil: 60 Kg (including insulation) 7. No. of Coils: Three (03) Detail scope of work: 1. Scraping of the old insulation, acid washing and pre annealing for all bend straightening of the disc coils. Straightening of the bend portions through roller die, final annealing and covering with four layers of Kraft papers of specific sizes as required, with in clock and anti clock direction with overlapping and bringing the insulated conductor as per specification provided. 2. Formation of disc coils with all lock joint cut spaces as required, pre-compressed press-phan boards for separators and winding the coils with 14% Rupatan sticks if required. Finally placement of the coils in heat chamber and pressing the same till the desired specifcations are achieved. (total cost including materials, manpower, transport to and fro, packing and forwarding charges and other overheads)
Re-insulation and recoiling of 3 Nos old and used primary coils of 750KVA 3.3/0.440 KV Transformers with proper grade of insulation. i. Covering should be TPC ii. Dimensions and other insulation should be exactly as per old coils. Primary coil data: Type-Disc coils 1. 99.9% Electrolytic Bright annealed copper strip with TPC. 2. No of Conductor: (i) For DISC coil = 1 3. size of conductor: Bare: 11.7X2.5MM TPC:12.2X3.0MM 4. No of Discs : 28, TURN/DISC:12(APPROX.) As per Sample / Old Coil 5. Coil Size: ID:290mm, OD:360mm and HT:515mm 6. Weight of each coil: 96KG (including insulation) 7. No. of coils: Three(03) 8. Tap Range : +7.5% to -7.5% ( In stpes of 2.5%) Detail scope of work: 1. Scraping of the old insulation, acid washing and pre annealing for all bend straightening of the disc coils. Straightening of the bend portions through roller die, final annealing and covering with four layers of Kraft papers of specific sizes as required, with in clock and anti clock direction with overlapping and bringing the insulated conductor as per specification provided. 2. Formation of disc coils with all lock joint cut spaces as required, pre-compressed press-phan boards for separators and winding the coils with 14% Rupatan sticks if required. Finally placement of the coils in heat chamber and pressing the same till the desired specifcations are achieved. (total cost including materials, manpower, transport to and fro, packing and forwarding charges and other overheads)
Re-insulation and recoiling of 3Nos old and used primary coils of 1MVA 11/3.3 KV Power Transformer with proper grade of insulation. i. Covering should be TPC ii. Dimensions and other insulation should be exactly as per old coils. Primary coil data: Type-Disc coils 1. 99.9% Electrolytic Bright annealed copper strip with TPC. 2. No of Conductor: (i) For DISC coil = 1 3. size of conductor: Bare: 6mm X 2mm TPC: 6.4mm X 2.4mm 4. No of Discs : 52 ,TURN/DISC: 18(APPROX) As per Sample / Old Coil 5. Coil Size: ID: 340mm, OD:430mm and HT:545mm 6. Weight of each coil: 116 Kg (including insulation) 7. No. of coils: Three(03) 8. Tap Range : +10% to -10% ( In stpes of 2.5%) Detail scope of work: 1. Scraping of the old insulation, acid washing and pre annealing for all bend straightening of the disc coils. Straightening of the bend portions through roller die, final annealing and covering with four layers of Kraft papers of specific sizes as required, with in clock and anti clock direction with overlapping and bringing the insulated conductor as per specification provided. 2. Formation of disc coils with all lock joint cut spaces as required, pre-compressed press-phan boards for separators and winding the coils with 14% Rupatan sticks if required. Finally placement of the coils in heat chamber and pressing the same till the desired specifcations are achieved. (total cost including materials, manpower, transport to and fro, packing and forwarding charges and other overheads)
Re-insulation, recovering and recoiling of 3nos old and used Secondary coils of 1MVA 11/3.3KV Power Transformer with proper grade of insulation. i. Covering should be TPC ii. Dimensions and other insulation should be exactly as per old coils Secondary coil data: Type-DISC TYPE 1. 99.9% Electrolytic Bright annealed copper strip with TPC. 2. No. of conductor : FOR DISC COIL: 2(TWO) 3. size of conductor: Bare: 8.6mm X 3.5mm TPC: 9.0mm X 4.0mm 4. No of DISC: 36 , TURN/DISC: 4 As Per Sample /Old Coil 5. Coil Size: ID:245 mm, OD:320 mm and HT:540 mm 6. Weight of each coil: 76 Kg (including insulation) 7. No. of Coils: Three (03) Detail scope of work: 1. Scraping of the old insulation, acid washing and pre annealing for all bend straightening of the disc coils. Straightening of the bend portions through roller die, final annealing and covering with four layers of Kraft papers of specific sizes as required, with in clock and anti clock direction with overlapping and bringing the insulated conductor as per specification provided. 2. Formation of disc coils with all lock joint cut spaces as required, pre-compressed press-phan boards for separators and winding the coils with 14% Rupatan sticks if required. Finally placement of the coils in heat chamber and pressing the same till the desired specifcations are achieved. (total cost including materials, manpower, transport to and fro, packing and forwarding charges and other overheads)
Total impact of GST plus Labour Cess [@ 1 % (BOCW Cess to be deducted from the RA bill as per the value of the work progress)] for the purpose of CTC
R.Traders (BID ID -1127369)
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_339025.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .