Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | Single par₹25.6 LRejected-Finance 1ST FLOOR KRISHNA TOWERS OPP TO THRIKKAKARA TEMPLE THRIKKAKARA P O COCHIN 682 021 | ERNAKULAM | KERALA | 682021 | Single par | Rejected-Finance Rates are unreasonable and unacceptable | |
| 2 | Rejected-Technical | - | Rejected-Technical see attached file | |
| 3 | Rejected-Technical BENUGRAM PO CHANDIPUR PS KHANDAGHOSH BURDWAN WEST BENGAL | BURDWAN | BURDWAN | WEST BENGAL | - | Rejected-Technical see attached file |
Tender Value
₹21.4 L
EMD Value
₹42,790
Closing Date
8 Aug 2022, 6:00 pmClosed
Director, CSIR-NML
CSIR-NML, Jamshedpur
Comprehensive Annual Maintenance Contract and Operation of Creep Central Package A.C plant (2 X 125TR) of CSIR-NML for the year 2022-23-24
2022_CSIR_123217_1
NML/ENG/WSM/eNIT/07(09)/22-23
Open Tender
Miscellaneous Works
Item Rate
365 days
CSIR-NML, Jamshedpur
As per eNIT
8 documents required · 8 mandatory
₹0
₹42,790
6 Sept 2022
27 Jul 2022
10 Aug 2022
28 Jul 2022
8 Aug 2022
28 Jul 2022
Amount
CAMC of Water Cooled Screw Chiller, as complete. (including all consumables, all genuine electrical / mechanical spares, accessories & panel etc., as required. See scope of work) Model: 30XW0532P ; Make: Carrier ; Refrigerant: HFC-134A
CAMC of Airside Equipment, as complete. (including all consumables, all genuine electrical / mechanical spares, accessories & panel etc., as required. See scope of work) (i) "Creep Bay (2Nos AHUs): 13,000 CFM/50mm W.G. Static Presure/ Filter & Coil Area 28 squre ft/ 4-Row Cooling Coil + 2 Row Reheat Coil for RH Control, 5.5 KW Motor AHU Model: ETU-120 H/ Make : Edgetech Air System AHU Motor Model : 2H13S4K3, Make Bharat Bijlee" (ii) "Mezzanine Office (1No. AHU): 1,600 CFM/ 50mm W.G. Static Presure/ Filter Area 16 sq ft Coil Area 4 sq ft / 4-Row Cooling Coil/ Bypass Damper on Remaining Area, 1.1 KW Motor AHU Model: ETU-015 H/ Make : Edgetech Air System AHU Motor Model : 2H080453, Make Bharat Bijlee" (iii) "Director Floor (1No. AHU): 3,000 CFM/ 50mm W.G. Static Presure/ Filter Area 9 sq ft Coil Area 9 sq ft / 6-Row Cooling Coil/ 1.5 KW Motor AHU Model: ETU-030 H/ Make : Edgetech Air System AHU Motor Model : 2H080NL473, Make Bharat Bijlee" (iv) "Auditorium (1No. AHU): 16,000 CFM/ 60mm W.G. Static Presure/ Filter Area & Coil Area 32 sq ft / 6-Row Cooling Coil/ 7.5 KW Motor AHU Model: ETU-150 H/ Make : Edgetech Air System/ SN: 17-18 FM 06172 AHU Motor Model : 2H13M4T3, Make Bharat Bijlee
CAMC of Cooling Tower, as complete. (including all consumables, all genuine electrical / mechanical spares, accessories & panel etc., as required. See scope of work) (i) "Hot Water Flow = 500 usgpm Model: 3870 ; Make: Paharpur" (ii) "Motor = 5.5 KW Model: TH132S-4 ; Make: Motovario"
CAMC of PUMPS, as complete. (including all consumables, all genuine electrical / mechanical spares, accessories, VFD & panel etc., as required. See scope of work) (i) "Primary CHW Pump (2Nos.)(PCHWP) 320 GPM/50 ft Model: KI132S ; Make: Kirloskar" (ii) "Secondary CHW Pump (2Nos.)(PCHWP) 320 GPM/55 ft Model: KI132S ; Make: Kirloskar" (iii) "Condenser Water Pump (2Nos.)( CNDWP) 500 GPM/60 ft Model: KI160M ; Make: Kirloskar" (iv) "Vertical Inline Hot Water (HW) Pumps (2Nos.)Model: KI100L ; Make: Kirloskar" (v) "Condensate Water Pumps(10Nos.) (75W)Model: Max high Flow: FP3349 ; Make: ASPEN"
CAMC of Fan Coil Unit, as complete. (including all consumables, all genuine electrical / mechanical spares, accessories & panel etc., as required. See scope of work) (i) Cassette type fan coil unit:- (a) "1.5 TR (19Nos.)(Director Floor 14 Nos + Mezz. Floor 5 Nos) Model: MKA 600 ; Make: Media" (b) "2 TR (17Nos.)(Director Floor 11 Nos + Mezz. Floor 6 Nos)Model: MKA 750 ; Make: Media" (ii) Concealed type Fan Coil Unit:- (a) "2 TR (2Nos.)Model: ETU-012 C ; Make: Edgetech Air System"
CAMC of 2-Way Flow Control Valve for AHUs with modulating Actuator and Programmable Temperature & Humidity Controller & Actuator Motor (240 Volts), as complete. (including all consumables, all genuine electrical / mechanical spares, accessories & panel etc., as required. See scope of work) (i) "100 mm dia (Auditorium)(1No.) Model: CN7220A2007 ; Make: Honeywell" (ii) "80 mm dia (Creep AHU)(2Nos.)Model: CN7220A2007 ; Make: Honeywell" (iii) "50 mm dia (Mezz & Director Floors)(2Nos.)- ON-OFF Type Actuator Model: Manual system" (Temperature & Humidity sensors & controller used):- (i) "Humidity" Model: H6000 (2Nos.); Make Honeywell Model: 600" (ii) "Temperature" (3Nos.) (Make: Honeywell (2Nos.) & Belimo (1No.)
Operation of Creep Central Package A.C plant (2 X 125TR) (See scope of work) (i) Operator-cum-technician (Gr II)- 1 No. in each of 3 shifts (i.e. A, B & C) for 7 days a week for 365 days (ii) Helper/Khallasi- 1 No. in each of 2 shifts (i.e.General & C) for 7 days a week for 365 days (N.B.: A shift:06:00-14:00; B shift:14:00-22:00; C shift:22:00-06:00; General shift: 09:15-17:45)
Supply, installation & commissioning of 1HP Single phase tullu pump make: Crompton, Kirloskar, Havells etc alongwith 5mtr of adequate size ISI marked suction pipe & 10mtr of adequate size ISI marked drain pipe; as required & complete
Supply, installation & commissioning IR Thermometer range -18oC to 275oC Make: Fluke Model: Fluke-59mini or equivalent
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .