Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹2.3 CrAccepted-Finance | ₹2.3 Cr | 1 | Accepted-Finance ok |
| 2 | 2₹2.4 Cr+₹14.2 L (6.25%)Accepted-Finance | ₹2.4 Cr+₹14.2 L (6.25%) | 2 | Accepted-Finance ok |
| 3 | 3₹2.4 Cr+₹14.4 L (6.36%)Accepted-Finance | ₹2.4 Cr+₹14.4 L (6.36%) | 3 | Accepted-Finance ok |
| 4 | 4₹2.5 Cr+₹27.5 L (12.1%)Accepted-Finance | ₹2.5 Cr+₹27.5 L (12.1%) | 4 | Accepted-Finance ok |
| 5 | 5₹2.6 Cr+₹35.3 L (15.6%)Accepted-Finance | ₹2.6 Cr+₹35.3 L (15.6%) | 5 | Accepted-Finance ok |
Tender Value
₹3.0 Cr
EMD Value
₹6.0 L
Closing Date
15 Feb 2024, 3:00 pmClosed
Executive Engineer Ed Anantnag
Office of the Executive Engineer ED Anantnag
Construction of distribution network at Wantrag viz creation of 4x400 and 2x 250 kVA DT Sub-stations alongwith HT/LT Network and High mast lights On SITC basis sub division Anantnag Division ED Anantnag (excluding LT Part)
2024_PDD_243472_1
eNIT No 286/EDA of Electric Divn Anantnag KPDCL
Open Tender
Electrical Works
Turn-key
120 days
TRANSIT CAMP AT WANTRAG ANANTNAG
Please refer Tender documents.
8 documents required · 8 mandatory
₹4,000
Executive Engineer ED Anantnag
₹6.0 L
1 Jul 2024
24 Jan 2024
17 Feb 2024
24 Jan 2024
15 Feb 2024
10 Feb 2024
25 Jan 2024 - 9 Feb 2024
Amount
Supply, Installation, Testing, Commissioning, Carriage, Loading and unloading at site of ( 04 No. 400 KVA DT sub-Stations)
400kVA,11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Copper wound ), redesignated as level 1, and with LV Cable Box having detachable Aluminium Gland plate.Transformer should have arrangement for vertical take off of cable ( 400kVA with OCTC (Off Ckt Tap Changer)
11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
630 mm² Single Phase Cable, 1.1K V Grade, XLPE Insulated Stranded Conductor FRLS type
9 Mtr. Long Pole ( ST-410 SP33)
G.I Pipe of 150 mm dia 2 mtr long for Pole Butts (6")
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
GI Channel/Angle/Flat of sizes including clamps for L.A Set/G.O Set/Horn Gap
Galvinized Nuts and Bolts.
Earthing of Substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
Transformer Pad/G.I Channel Bedding (300Kg)
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
LT Distribution Box for 400 kVA DTR with 630 Amp MCCB 3P (36 KA) adjustable 1 No. for incomer & 150 Amp 3 P (16 KA) 5 No.s (4 + 1 spare) fixed for Outgoing Circuits as per drawings
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 )mm, nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Wedge Connectors / PG Clamps
Danger Plates with Clamps
GI Barbed Wire for Anti Climbing with clamps.
Cement bottoming 1:2:4 mix as per Standards 0.48cum /pole
Red Oxide(one coat) and Almunium paint(2 or more coats so as to obtain smooth finish)
Supply of Bamboo Ladders (14-16 ft long)
Sundry items like Aluminium lugs, Jumpers, binding Tape etc
Supply,installation,Testing,Commissioning,Carriage,Loading and unloading at site ( 02 No.250 KVA DT sub-Stations)
250 kVA,11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2,(Cu wound) , ( redesignated as Level 1 ) and with LV Cable Box having detachable Al. Gland plate with LV Bimetallic terminal connection suitable for vertical take off of cable..
11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
400 mm² single core Cable,1.1kV Grade, XLPE Insulated Stranded Conductor FRLS type (44mtr for 1 Ckt)
9 Mtr. Long Pole,(ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
LT Distribution Box for 250 kVA DTR with 400 Amp MCCB 3P (36 kA ) for incomer and 160 Amp MCCB 3P (16 kA) 3 No.s for Outgoing Circuits as per drawings
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6) mm, nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Wedge Connectors / PG Clamps
Danger Plates with Clamps
GI Barbed Wire for Anti Climbing with clamps.
Cement bottoming 1:2:4 mix as per Standards 0.48 cum/pole
Red Oxide(one coat) and Almunium paint(2 or more coats so as to obtain smooth finish)
Sundry items like Aluminium lugs, Jumpers, Binding Tape etc
Supply,installation,Testing,Commissioning,Carriage,Loading and unloading at site ( 01 No.25 KVA DT sub-Station)
25kVA,11/0.433kV 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, redesignated as level 1, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate with LV Bimetallic terminal connection suitable for vertical take off of cable.
11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
95 mm² Single-Core Cable,1.1kV Grade XLPE Insulated Stranded Conductor FRLS type
9 Mtr. Long Pole( ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT Distribution Box for 25 kVA DTR with 40 Amp MCCB 3P (16 kA) 1 No. for incomer & 25 Amp MCCB 3P (16 kA/10 kA) 2 No for Outgoing Circuits as per drawings
Cement bottoming 1:2:4 mix as per Standards 0.48cum /pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
3 Phase LT prodigy Meter
Red Oxide(one coat) and Almunium paint(2 or more coats so as to obtain smooth finish)
Danger Plates with Clamps
Supply,installation,Testing,Commissioning,Carriage,Loading and unloading at site ( 11KV Line (H-Frame/Single Circuit/Double Circuit )
13 Mtr. Long Pole(ST-410 SP69)
9 Mtr. Long Pole( ST-410 SP33)
11 Mtr. Long Pole( ST-410 SP56)
GI V cross-arm with top Bracket including clamp
100 mm² ACSR Conductor
50 mm² ACSR Conductor
PG Clamps for 100 mm² ACSR Conductor
PG Clamps for 50 mm² ACSR Conductor
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm 3mtr long through GI Strip 25x3 mm
Red Oxide(one coat) and Almunium paint(2 or more coats so as to obtain smooth finish)
Cement bottoming 1:2:4 mix as per Standards 0.7 cum / pole
Cement bottoming 1:2:4 mix as per Standards 0.66 cum / pole
Cement bottoming 1:2:4 mix as per Standards 0.48 cum /pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 )mm, nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Guard netting (Appx 40m Span)
120 mm² AB (HT) Cable (3x120 + 1x95 insulated) mm² XLPE(11 kV, 3C + Earth)
Heat Shrinkable Outdoor Cable Termination Kit
Suspension/Tension Clamp with eye hook
11 kV Isolator, Double Break,3-pole, 630 Amp, horizontal mounting Type, with Earth Switch on supply side of the feeder
Dismantling of the Existing structure
Dismantling by way of uprooting of Existing ST Poles(11/9/8 mtr) and stacking of the same in Divisional stores including transportation loading and unloading etc.
Dismantling by way of Cutting of Existing ST Poles(11/9/8 mtr) and stacking of the same in Divisional stores including transportation loading and unloading etc
Dismantling by way of Cutting of Existing wooden Poles and stacking of the same in Divisional stores including transportation loading and unloading
Rubble of PCC Pole to be dumped at the site as identified by the site engineer to the lead upto 200 mtrs
Dismantling of ACSR (50/30 sqmm) and stacking of the same in Divisional stores including transportation loading and unloading
Branch Cutting /Pruning of trees
Supply,installation,Testing,Commissioning,Carriage,Loading and unloading at site ( Street Lights)
9.0 mtr Long GI (65 micron DFT single dip) Octogonal poles uniformally tappered with thickness of 3mm with bottom/top Dia of 175 mm x 70mm & base plate of 275x275x16mm/pcd 250 mm provided with proper door opened gear box for connections on the bottom side with G.I. Foundation Bolts (J Type) M24x750 mm long (Set of 4 no.’s per pole)
Laying of RCC foundation for 9.0 mtr. Long Octagonal poles including proper curing. 0.6mX0.6mX1.5 m (RCC with concrete ratio (1 : 1.5 : 3 ) with minimum 8 Nos. of 12 mm dia longitudinal MS reinforcement rods with rings of 8 mm dia not more than 200 mm C.C for fixing the pole).
Earthing of Octagonal Pole Complete by GI Pipe 40 mm or GI Rod 20mm 3 mtr long through GI Strip (25x3)mm
Pre fabricated galvanized single way top bracket (1000 mm long with 48.3 OD GI Pipe) to be fitted on top of Octogonal pole for holding lighting
DK thermoplastic cable Junction/ Termination T boxes 8"x10"of class IP55/IP65 fitted with two 2-5 Amp MCB strip,4-way terminal block / connectors Incl. copper lugs, Clamps ,nut & bolts washers etc (Hansel or equivalent make) or poles with two way type bracket to be fitted properly inside the door opened gear box provided on the bottom side of the pole.
120 Watt LED Luminaries of IP 67 protection, LED efficacy - > 120 lumen / watt, Lamp life not less than 50,000 burning hours, Reverse EMI protection provided / over voltage protection upto 300V / surge protection upto 6kV
Surge Protector for the 120 watt LED type lighting fixture complete.
3X1.5 mm² PVC insulated multistrand flexible copper wire for service connections from connection plate to the LED luminary individual circuit including loop & earthings laid properly.
HDPE pipe 50 mm O/D and inner Dia 38 mm including trench excavation in hard soil (0.3x0.45x1000m) for laying of 25/16 sq mm Almunium armored cable . The job further inludes refilling back the same and removal of surplus excavted material to an appropriate place.
LT 25 mm² 4 core Aluminium XLPE Armoured cable to be carried through conduit/pipe U/G or A/G only in case of site constrains excluding cost of pipe & trench excavation. The cable shall include end termination lugs with its crimping /taping.
LT 16 mm² 2 core Aluminium XLPE Armoured cable to be carried through conduit/pipe U/G or A/G only in case of site constrains excluding cost of pipe & trench excavation. The cable shall include end termination lugs with its crimping /taping.
Dust/rain/snow-proof canopy type mini-outdoor LT feeder panel of size 450X300mm with front door opening duly powdered colour coated with inbuilt 2No TPN 16-32 Amp MCCB,TPN busbars of same capacity installed on cement concrete block with 4 angle iron legs grouted in the cement concrete of termination of main 25sqmm cable and outgoing 25/16 sqmm cable circuits.
Supply,installation,Testing,Commissioning,Carriage,Loading and unloading at site ( All in One Solar Street Lights)
6 Mtr long GI pole of (3 inch Dia) Standard Make
GI Bracket suitable for for fixing of solar street light including clamps nuts and Bolts
35W ALL-IN-ONE Solar Street Light integrated with PV Panel(Lumens not less than 120 lumins per watt) , Life span greater than 50000 hours, Solar panel Poly solar Cell,Battery LiFePO4 lithium battery,Battery rating Min 3-rainy days backup,Life span greater than 2000 charging cycles , operation mode (Dawn to desk ) with aoutomatic and manual switching, working temprature -20 Deg C to + 60 Deg C,Water proof , CRI greater than 85% ( Standard make to be finalized by the contract committee)
Earthing Complete by GI Rod 20mm 2.5 mtr long through GI Strip.
Cement bottoming 1:2:4 as per REC standars 0.2cum/pole
MIR ELECTRICALS
Marib Constructions
N S ENTERPRISES
M/s M. S. CONSTRUCTIONS
M/S Haji Construction Company
AZEEM CONSTRUCTIONS
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .