Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹53,400
Closing Date
10 Nov 2020, 6:00 pmClosed
CWE Mhow
HQ CWE Mhow Cantt Mhow 453441
SPECIAL REPAIR TO REPLACEMENT OF BER TRANSFORMERS UNDER GE AWC MHOW
2019_MES_303031_4
CA No CWE/Mhow/25(T) OF 2019-2020
Open Tender
Civil Works
Item Rate
180 days
HQ CWE Mhow
Please refer tender documents
8 documents required · 8 mandatory
₹500
Yes
GE AWC Mhow
₹53,400
Yes
20 Nov 2020
1 Oct 2020
12 Nov 2020
1 Oct 2020
10 Nov 2020
16 Oct 2020
Amount
Excavation in trenches in any type of soil not exceeding 1.5 m wide and not exceeding 1.5 m in deep and getting out for laying of cable/ pipes etc including forming bottom surfaces to the required level/slope complete all as specified and directed
Returning , filling in includiing spreading levelling, watering and well ramming in layers not exceeding 25 cm thick in any type of soil complete all as specified and directed
Removing surplus excavated to a distance not exc 50 m and depositing where directed at level not exc 1.5 m above the starting point complete all as specified and directed.
Material and labour for available local sand cushioning for under ground cable in trenches 8 cm before laying and 15cm after laying of cable and punned thickness of sand shall be measured and paid for 18 cm only after punned /consolidated thickness complete all as specified and directed
M & L for unreinforced PCC Cable protection cover , Class LV ,Type1 flat ,size 250mm X150mm x 40mm as cable protection laid flat width wise complete all as specified and directed.
Supply and laying galvanised iron pipe 'light Grade' 80mm in trenches , under floors, roads, along poles for protection of cables with all necessary fittings, including sealing ends complete all as specified and directed . (Make Jindal/Prakash Surya/Tata)
Supplying, laying and testing in replacement of LT UG cable XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured electric power cables ( heavy duty) 1100 Volts grade with stranded aluminium conductor of 185 Sqmm 3.5 Core complete all as specified and directed. (Make: Polycab,Havells,universal cable, Gloster) .
Supply & laying, testing in replacement of HT UG cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable heavy duty with stranded aluminium conductor, 11000 Volt Grade of size 95 Sqmm 3 core including jointing and testing complete all as specified and directed .
Supply and laying reinforced precast concrete cable cover, class HVP, type-1, flat, size 300mm x 180mm x 40mm complete all as specified and directed (Make Mahtabn tiles/ Alankar Tiles)
Supply and laying galvanised iron pipe 'light Grade' 100mm in trenches , under floors, roads, along poles for protection of cables with all necessary fittings, including sealing ends complete all as specified and directed . Make Jindal/Prakash Surya/Tata
Supply and fixing cable jointing kit 11 KV grade cable for out door termination heat shrinkable type joint complete with jointing material & accessories suitable for 3 core XLPE armoured cable alumininum conductor 95 sqmm complete all as specified and directed. Make- M Seal/ Densons/ Raychem.
Supply and fixing cable jointing kit 11 KV grade cable for In door termination heat shrinkable type joint complete with jointing material & accessories suitable for 3 core XLPE armoured cable alumininum conductor 95 sqmm complete all as specified and directed. Make- M Seal/ Densons/ Raychem.
Disconnecting the power supply of existing 250 KVA out door type step down transformer, removing all electrical connections and shifting the same to MES store yard complete all as directed.
Supply installing, testing and commissioning AC 3 phase 50Hz,315 KVA capacity transformer copper wound step down transformer Indoor type 11000/433 Volts (at no load) double wound oil immersed naturally cooled with external cooling tubes, core type delta connected on primary side (HV) and star connected on secondary side (LV) and have in tapping at +/- 2.5 % +/- 5.0% and +/- 7.5% to be changed by means of hand operated off load tap changing gear the maximum temperature rise should not exceed 45 degree centigrade in oil and 55 degree centigrade in HV/LV winding when measured by resistance method after continuous full load run in ambient temp of 40 degree centigrade and the transformer bushing on HT side and LT side all as per efficiency level -3 of IS 1180 /latest IS, standard losses of transformer is 955 watts at 50% load and 2750 watts at 100% load with percent impedance is 4.5 complete all as specified and shall be Comprising following accessories and the transformer shall be comprised with the follwing standared fittings:- (a) Three Nos porcelain Bushings HT 11 KV with copper bushing rods nuts and washers inside cable and including end box. (b) One cable box LV side consisting of four Nos porcelain bushing with copper rode complete with nuts and washer including box HV side.
(c) Oil conservator with filter type drain valve and oil level gauge. (d) Dehydrating breather with first fill dehydrating agent (Silica Jal) (e) Explosive vent (f) Thermometer pocket on tank cover having maximum temperature indication with resisting device for transformer. (g) Rating plate and terminal marking plate (h) The earthing terminal two Nos to facilitate fixing of earth strip. . (i) Oil filling hole with cap/plug with connection plate complete. (j) Air relief valve plug. (k) Initial filling to transformer oil. (Note : Testing of transformer to be carried out by officer detailed by Accepting officer before despatch from factory site)
Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6.0 mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to GI strip 32mm X 6mm main earthing lead by means of galvanized bolts, nuts and washers all as shown in electrical plate No. 5 of MES Schedule Part-I (1991) with connected to earth test point & to main switch board etc with & including adequate quantity of charcoal dust and common salt alround earth plate, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover reinforced with 6mm dia bars 3 Nos both way with 12mm dia round bar handle, GI light grade watering pipe 20 mm dia with funnel and wire mesh and 40 mm dia GI light grade earth lead protection pipe complete all as specified and directed.
Material and labour for danger notice plate of 1.6 mm thick mild steel vitreous enameled white of size 25cm x 20cm with letter fifures and conventional skull & bones in single red colour and fixed with mild steel clamps, nute, bolts, and washer clamps made out of GI 25mm x 3mm for HT poles/transformers etc complete all as specified & directed.
Material and labour for high Voltage insulating Mats as per with IS: 5424: 1969,(Old Ltd) as per Govt. of India, Gazzette Notification, No:- So-2086, dt 17 July 2007, thickness of insulating Mats 2.5 mm , (ISI Mark : 15652) complete all as specified & directed. Make :- Jyoti Electrosafe/Vardhman/RMG Poly vinyl.
Supply and fixing cable path indicator made out of 300mm x300mm x 1.6mm thick mild sheet duly rivetteed and welded to 600mm long mild steeel angle iron of 30mmx30mmx5mm and embedded in PCC 1:3:6 type C-2 block of size 300mmx300mmx300mm including necessary excavation and earth work and painting exposed surface of steel work two coats of synthemertic enamelled paint over a coat of red oxide primer and marking the size of cable and voltage complete all as specified & directed.
JAZZCON ENGINEERS PVT LTD
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .