| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.7 CrAccepted-AOC SHALABH HOUSE 490 PURANI TEHSIL ROORKEE DISTT HARIDWAR | HARIDWAR | UTTARAKHAND | 247656 | ₹4.7 Cr Quoted ₹4.8 Cr | L1 | Accepted-AOC lowest bidder |
| 2 | L2₹5.1 Cr+₹31.4 L (6.56%)Rejected-Finance | ₹5.1 Cr+₹31.4 L (6.56%) | L2 | Rejected-Finance Other than L1 |
| 3 | L3₹5.4 Cr+₹59.3 L (12.4%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | ₹5.4 Cr+₹59.3 L (12.4%) | L3 | Rejected-Finance Other than L1 |
| 4 | Rejected-Technical | - | - | Rejected-Technical No slow progress shown in WLR and Scanned copy of DD towards cost of tender also not uploaded |
Tender Value
₹5.8 Cr
EMD Value
₹6.2 L
Closing Date
19 Apr 2022, 6:00 pmClosed
HQ CE Lucknow Zone Lucknow
HQ CE Lucknow Zone, 17, cariappa marg, Lucknow 226002
IMPROVEMENT / AUGMENTATION OF HT/LT ELECTRIC INCLUDING CONNECTED PANELS AND FEEDERS UNDER GE (EAST) AGRA.
2022_MES_501439_2
CELZ/AGR/T-39 OF 2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
GE (East) Agra
Refer tender documents
7 documents required · 7 mandatory
₹3,000
GE (East) Agra
₹6.2 L
Yes
23 May 2022
29 Mar 2022
23 Apr 2022
29 Mar 2022
19 Apr 2022
6 Apr 2022
Amount
Excavation in trenches in soft/loose type of soil n exc 1.5 metre in width and n. exc 1.5 metre in depth and getting out all as required for laying of cables, foundation filling of poles or stays complete all as specified and directed.
Excavation in trenches in hard/dense type of soil n exc 1.5 metre in width and n. exc 1.5 metre in depth and getting out all as required for laying of cables, foundation filling of poles or stays complete all as specified and directed.
Returning, filling in , including spreading ,leveling, watering and well ramming in layers not exc 25 cm each complete all as specified and directed.
Removing excavated material to a distance not exceeding 50 metre and depositing where directed at a level not exc 1.5 metre above the starting point complete all as specified and directed.
M&L for sand cushning to underground cable with clean dry river sand in layers of 23 cm thick (8 cm before laying the cable and 15 cm thick after laying the cable) in trenches including watering and consolidiation, complete all as specied and directed by Engineer in Charge. Note :- punned thickness only shall measured and paied
Supply and laying of sub class 'B' bricks locally available of best quality old size, laid flat (length of brick laid across the length of cable) in trenches for the protection of under ground cable, complete all as specied and directed by Engineer in Charge.
Supplying & Laying un-reinforced pre cast flat concrete cable protection cover of class HV, type I, size 300 mm x 180 mm x 40 mm, factory made, complete all as specified and directed .
M&L for cement concrete 1:4:8 type D2 ( using 40 mm graded stone aggregate) for foundation of pole / stay including form work etc complete all as specified and directed.
M&L for cement concrete 1:3:6 type C1 ( using 20 mm graded stone aggregate ) in coping of poles studs including form work etc complete all as specified and directed.
Material and labour for PPR polypropylene random copolymer 50 mm dia pipe SDR 7.4 PN16 UV stabilized and antimicrobial fusion welded having thermal stability for water supply all PP-R plain & brass threaded polypropylene random fittings laid for protection of cable under road crossing fixed to walls or pole complete all as specified and directed.(clamps for fixing pipe, nuts, bolts washers shall be measured separately )
Material and labour for PPR polypropylene random copolymer 75 mm dia pipe SDR 7.4 PN16 UV stabilized and antimicrobial fusion welded having thermal stability for water supply all PP-R plain & brass threaded polypropylene random fittings laid for protection of cable under road crossing fixed to walls or pole complete all as specified and directed.(clamps for fixing pipe, nuts, bolts washers shall be measured separately )
Material and labour for PPR polypropylene random copolymer 110 mm dia pipe SDR 7.4 PN16 UV stabilized and antimicrobial fusion welded having thermal stability for water supply all PP-R plain & brass threaded polypropylene random fittings laid for protection of cable under road crossing fixed to walls or pole complete all as specified and directed.(clamps for fixing pipe, nuts, bolts washers shall be measured separately )
Taking out of old unserviceable steel tubular pole 11/09 metre long complete any type complete all as specified and directed.
M&L for steel tubular swaged pole 11 mtr long with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP 55, including painting with anti corrosive paint internally complete and externally up to planting depth, alternative green & white strips of 30 cm width upto 1.5 mtr above ground level, balance lenght to be painted with two coats of aluminium paint externally all as required at site or directed by Engr-in-charge.
M&L for steel tubular swaged pole 09 mtr long with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP 31, including painting with anti corrosive paint internally complete and externally up to planting depth, alternative green & white strips of 30 cm width upto 1.5 mtr above ground level, balance lenght to be painted with two coats of aluminium paint externally all as required at site or directed by Engr-in-charge.
Supply and fix HT 11 KV out door type gang operated air-break switch with Drop out fuse suitable for horizontal or vertical mounting rotating type complete with 15 insulators of rating upto 200 Amps complete all as specified and as directed.
M&L for cross arms, bracings, supports, clamps and back plates fabricated from steel section including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of one coat primer , one under coat and one finishing coat of alumn paint complete all as specified and directed.
M&L for ACSR conductor of any size drawn straight horizontal on over head lines on poles including binding with insulators using aluminium binding wire, jointing jumpers etc including connections of incoming and out going cables complete all as specified and directed.
Supply and fixing disc type insulator, porcelain, vitreous 145 mm height and 255 mm dia ball and socket type white/brown or green two -in-series assembly for tension with tension clamps for conductors of working pressure 11000 volts for HT overhead lines complete all as specified and directed.
Supply and fix lightening arrester non liner resister type confirming to IS No 3070 part I complete with all fittings, discharge capacity 65 KA suitable for 11 KV including making connections with over head line with ACSR conductor complete on poles all as specified and directed.
Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to GI strip 25 x 4 mm thick as main earthing strip by means of galvanized bolts, nuts and washers with connected to earth test point & to main switch board etc. all as specified and testing on completion with and including necessary excavation and earth work in any type of soil, earth electrode, earthing lead from electrode to equipment/substation/panel etc, adequate quantity of charcoal dust and common salt, test point, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover reinforced with 8 mm dia TMT bars 3 Nos both way with 12mm dia TMT bar handle, GI light grade watering pipe 20 mm dia with funnel and wire mesh, and 40 mm dia GI light grade earth strip protection pipe, complete all as specified and directed. Note : Earth strip & GI protection pipe up to 7.5 m shall be deemed to be included in quoted rate
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, triple entruded electric power cables (heavy duty) with stranded aluminium conductor, ISI marked, IS : 7098 (Pt-II), 11000 (Earthed) volts grade, of size 3 core 95 sq mm.complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 95 sqmm complete all as specified and directed. Note for item No 22 to 25 :- Factory visit/inspection for HT cables at OEM premises will be carried out by rep of Accepting Officer and all necessary arrangements will be get done by the contractor & cost is deemed to be included in the quoted rates.
M&L for drilling suitable dia horizontal bore holes for insertion/ laying of 50 mm to 110 mm bore PP-R pipe of any description below/under existing road surfaces / floors at a level not less than 0.60 metre etc with using mechanical / or manual devices as required at site including making good the disturbed surfaces to match with the existing after laying pipes complete all as specified and directed by Engineer-in-Charge. Note : (i) Cost of equipment tools and plant material (horizontal boring rig machine) required for boring shall be arranged by contractor at no extra cost to the Govt.
Supply, installation , Testing and Commissiong outdoor cubicle panel board for three phases, 4 wire , design verified as per IS/IEC 61439- 1& 2 for 415 Volts , 50 Hz rated fault level 65 KA with internal arc containment with IP-56 protection rupturing capacity at 415 volts , factory made in an approved factory having seven tank treatment process for powder coating with thickness not less than 60 microns with paint shade RAL -7035 provided with suitable gasket to make it dust/vermin proof and provided multifunctional digital panel meter with LCD display flush mounting type of size 96 mm X 96 mm, accuracy class 1, suitable for CTs with secondary current 5A and mounted on PCC foundation of size as required or approved by manufacturers in PCC 1:3:6 Type C-2 , using 40 mm graded crushed stone aggregate as recommended by manufacturer or directed by the Engr -in - charge including earth work complete & general construction comprising of the following :- Note :- (i) The termination of LT cables in the panel will be through cable glands of appropriate size. (ii) The electrical connection of incoming switchgears & outgoing switchgears (ACB/MCCB’s) will be through copper strips bus bar of rating 1.5 times the current rating of respective switchgears. (iii) Factory visit/inspection for LT panels at OEM premises will be carried out by rep of Accepting Officer and all necessary arrangements will be get done by the contractor & quoted rates are deemed to be included for the same .
OUTER SHELL :- The outer shell shall be made out of 3.15 mm thick CRCA sheet steel and MS angle section 50 mm x 50 mm x 6 mm frame with front and back openable double door system lockable /openable by keys from both sides having flush pattern fancy locks with louvers and air vent gasket for natural flow of air `U' type gasket shall be used to make the outer shell completely vermin proof. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The dimension of the outer shell should be adequate to accommodate inner shell described below giving 75 to 100 mm space around & shall be fabricated in such a way that the complete inner shell alongwith its with its control gears & accessories could be taken outside without disturbing outer shell. Provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift the panel, safety shall be made with degree of protection of outer shell shall be IP-56, Computer out self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided.
INNER SHELL :- Inner shell made out of 2 mm thick CRCA sheet duly compartmentalised for each control gear,front & back openable single door system lockable /openable by key from both sides having chromium plated 19 mm dia fancy locks (02 Nos in each compartment) having louvers & air vent gasket fro natural flow of air, "U" type gasket shall be used to make the inner shell completely vermin proof & to accommodate incomer / outgoing MCCBs and electrical grade busbar with 65 KA short time current (rms) for 1 sec and 105 KA (Peak) rated dynamic short circuit with stand with heat shrinkable sleeves alonwith shrouds for joints & eath duly colour coded shall be mounted on suitable size "F" class insulator made of nonhygroscopic , noncumbustile , track resistance , high strength FRP/SMC/DMC material at an interval not less than 500 mm through out the length of the TPN busbar . The cubical incomer MCCB as wel las out going shall have copper TPN extension links of current carrying capacity not less than 1.5 times the rated capacity of individual feeder, the extension links shall not be less than 300 mm long supported on suitable size "F" class insulator made of non hygroscopic , noncumbustile, track resistance , high strength FRP/SMC/DMC material having provision for termination of incomer and outgoing cables. All inter connections between the main busbar as well as outgoing feeder shall be arried out with TPN copper busbar of rating not less than 1.5 times rated capacity of individual outgoing feeder and should be insulated with heat shrinkable PVC sleeves. All control wires shall be with 2.5 sqmm multistranded copper conductor and shall be properly bunched , tied, ferruled for proper identification and crimped with adequate size of copper lugs. The cubical shall have a bottom channel of size 75 x 40 mm duly coated with zinc metal coating having thickness not not less than 100 microns. A detachable predrilled gland plate of thickness 3.15 mm powder coated should be used at the bottom . The inner shell shall be of powder coated Siemens grey structtural RAL -7032 shade. An inspection lamp LED 5 watt with movable non ferrous chromium plated arm fitted on top side of inner shell shall be provided . The degree of protection for inner shell shall be IP-42 and carry the following controlls :-
METERING : Multifunctional digital panel meter with LCD display flush mounting type of size 96 mm X 96 mm, accuracy class 1, suitable for CTs with secondary current 5A.
INCOMING: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip with current capacity 400 A with 65 KA rated short time current (rms) for 1 sec & 105 KA (Peak) rated dynamic short circuit with heat shrinkable PVC sleeves alongwith shrouds for joints . (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty - 01 No OUTGOING :(a) MCCB 4 pole having current ratings 63 Amps, AC 415 Volts, with Ics = 16 KA, Ics = 100% of Icu, with thermal release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting complete with spreader links. Qty - 06 Nos, All accessories pre-wired with suitable size PVC insulated copper conductor cables for control wiring and PVC insulated copper strips of appropriate size for power circuits as per standard engineering practice and required at site and suitable foundation for panel as per manufacturer recommendation.
All as per item No 27,27.01 to 27.03 here-in-before but comprising of the following :- Incoming : (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip capacity 400 A capacity . (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. - Qty- 01 No Outgoing :(a) MCCB 4 pole having current ratings 63 Amps, AC 415 Volts, with Ics = 16 KA, Ics = 100% of Icu, with thermal release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting complete with spreader links.Qty- 06 No
All as per item No 27,27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Busbar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 1000 A,with heat shrinkable PVC sleeves. (b) MCCB, 4 pole having current ratings 630 Amps, AC 415 Volts, with Icu= 50 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links:- Qty - 06 No , : (b) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links - Qty - 01 No.
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 1200 A. (b) ACB 4 pole having current ratings 800 Amps,AC, 3 phase, 50 Hzs AC Horizontal drawout type motorized, front operated with microprocessor release for adjustable over current , short circuit and earth fault protection. The breaker shall have minimum breaking capacity of 50 KA (RMS) symmetrical . The ACB should have Ics=Icu=Icw for 1 sec.for short circuit breaking and over temperature protection feature with 4 NO/4NC auxiliary contacts. ACB shall also confirm to IEC 60947/ IS-13947/Part-II/19939 latest version. Protection release should be communicable & having battery backup. Breaker should have last tripping detail memory complete with spreader links. :- Qty - 01 No (c) On load change over 630 Amps - Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links :- Qty - 02 No (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links :- Qty - 02 No (b) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links, Qty - 01 No
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 A. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty -01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty- 3 Nos (b) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty -03 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 A. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 3 Nos (b) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 A. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 06 Nos (b) MCB 4 Pole, 32 Amp, 10 KA, C series-03 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 A. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 160 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 05 Nos (b) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 1 No : (c ) MCB 4 Pole, 32 Amp, 10 KA, C series-02 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 250 A. (b) MCCB, 4 pole having current ratings 160 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 06 Nos : (b) MCB 4 Pole, 32 Amp, 10 KA, C series-02 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Busbar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 A. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos :(b) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 2 Nos ( c) MCB 4 Pole, 32 Amp, 10 KA, C series-02 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amp. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty -07 Nos (b) MCB 4 Pole, 32 Amp, 10 KA, C series-02 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amp. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing : (a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty- 03 Nos (b) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-Qty - 2 Nos (c ) MCB 4 Pole, 32 Amp, 10 KA, C series-02 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 300 Amps. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links , Qty - 08 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 1000 Amp . (b) MCCB, 4 pole having current ratings 630 Amps, AC 415 Volts, with Icu= 50 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 03 Nos (b) MCCB, 4 pole having current ratings 160 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos (c) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, withthermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amp. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty -01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty -08 Nos (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty -1 No
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amp. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty 01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- 08 Nos (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 1 No :
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amps, with heat shrinkable PVC sleeves. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links - Qty- 01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 08 No (b) MCCB, 4 pole having current ratings 160 Amps, AC 415 Volts, with Icu= 25 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 1 No
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 250 Amp. (b) MCCB, 4 pole having current ratings 160 Amps, AC 415 Volts, with Icu= 25 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 08 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 1200 Amp . (b) ACB 4 pole having current ratings 800 Amps,AC, 3 phase, 50 Hzs AC Horizontal drawout type motorized, front operated with microprocessor release for adjustable over current , short circuit and earth fault protection. The breaker shall have minimum breaking capacity of 50 KA (RMS) symmetrical . The ACB should have Ics=Icu=Icw for 1 sec.for short circuit breaking and over temperature protection feature with 4 NO/4NC auxiliary contacts. ACB shall also confirm to IEC 60947/ IS-13947/Part-II/19939 latest version. Protection release should be communicable & having battery backup. Breaker should have last tripping detail memory complete with spreader links. Qty- 01 No Outgoing :(a) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 03 Nos (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 1000 Amps. (b) MCCB, 4 pole having current ratings 630 Amps, AC 415 Volts, with Icu= 50 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 07 Nos (b) MCCB, 4 pole having current ratings 630 Amps, AC 415 Volts, with Icu= 50 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amp. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-Qty - 07 Nos (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty- 01 No
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 500 Amp. (b) MCCB, 4 pole having current ratings 320 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qtyn - 07 Nos (b) MCCB, 4 pole having current ratings 160 Amps, AC 415 Volts, with Icu= 25 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 250 Amps . (b) MCCB, 4 pole having current ratings 160 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 07 Nos (b) MCCB, 4 pole having current ratings 160 Amps, AC 415 Volts, with Icu= 25 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amp. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No (c) On load change over switch 400 Amps 4 pole, 415 volts without sheet steel enclosure-Qty-01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos (b) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 500 Amp. (b) MCCB, 4 pole having current ratings 320 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos (b) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 1000 Amps . (b) MCCB, 4 pole having current ratings 630 Amps, AC 415 Volts, with Icu= 50 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links Qty - 02 Nos (c) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amp . (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amps. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos (b) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 04 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 500 Amps. (b) MCCB, 4 pole having current ratings 320 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty- 02 Nos (b) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 03 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amps. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos (b) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 1200 Amps. (b) ACB 4 pole having current ratings 800 Amps,AC, 3 phase, 50 Hzs AC Horizontal drawout type motorized, front operated with microprocessor release for adjustable over current , short circuit and earth fault protection. The breaker shall have minimum breaking capacity of 50 KA (RMS) symmetrical . The ACB should have Ics=Icu=Icw for 1 sec.for short circuit breaking and over temperature protection feature with 4 NO/4NC auxiliary contacts. ACB shall also confirm to IEC 60947/ IS-13947/Part-II/19939 latest version. Protection release should be communicable & having battery backup. Breaker should have last tripping detail memory complete with spreader links. Qty - 01 No (b) On load change over switch, 4 pole, 630 Amps without sheet steel enclosure-Qty-01 No Outgoing :(a) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 03 No (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 03 No
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 1000 Amps. (b) MCCB, 4 pole having current ratings 630 Amps, AC 415 Volts, with Icu= 50 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty- 01 No (b) On load change over switch 630 Amps 4 pole, 415 volts without sheet steel metal enclosure-Qty-01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty- 02 Nos (b) MCCB, 4 pole having current ratings 125 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 2 Nos . (c) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 2 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amps . (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 125 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 03 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amps. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 125 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 03 Nos (b) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-. Qty - 02 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 1200 Amps. b) ACB 4 pole having current ratings 800 Amps,AC, 3 phase, 50 Hzs AC Horizontal drawout type motorized, front operated with microprocessor release for adjustable over current , short circuit and earth fault protection. The breaker shall have minimum breaking capacity of 50 KA (RMS) symmetrical . The ACB should have Ics=Icu=Icw for 1 sec.for short circuit breaking and over temperature protection feature with 4 NO/4NC auxiliary contacts. ACB shall also confirm to IEC 60947/ IS-13947/Part-II/19939 latest version. Protection release should be communicable & having battery backup. Breaker should have last tripping detail memory complete with spreader links. Qty - 01 No (c) On load change over switch, 4 pole, 630 Amps without sheet steel enclosure-Qty-01 No Outgoing :(a) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty -- 01 No (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty .- 02 No (c ) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos (d) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 02 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amps. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty -- 01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-Qty - 04 Nos :(b) MCCB, 4 pole having current ratings 125 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 03 Nos.
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 1200 Amps ,with heat shrinkable PVC sleeves. (b) ACB 4 pole having current ratings 800 Amps,AC, 3 phase, 50 Hzs AC Horizontal drawout type motorized, front operated with microprocessor release for adjustable over current , short circuit and earth fault protection. The breaker shall have minimum breaking capacity of 50 KA (RMS) symmetrical . The ACB should have Ics=Icu=Icw for 1 sec.for short circuit breaking and over temperature protection feature with 4 NO/4NC auxiliary contacts. ACB shall also confirm to IEC 60947/ IS-13947/Part-II/19939 latest version. Protection release should be communicable & having battery backup. Breaker should have last tripping detail memory.complete with spreader links. Qty - 01 No (c) On load change over switch, 4 pole, 630 Amps without sheet steel enclosure-Qty-01 No Outgoing :(a) MCCB, 4 pole having current ratings 630 Amps, AC 415 Volts, with Icu= 50 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty .- 02 Nos (c ) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 03 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 500 Amps. (b) MCCB, 4 pole having current ratings 320 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No :(b) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 1 No (c) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 2 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 250 Amps, with heat shrinkable PVC sleeves. (b) MCCB, 4 pole having current ratings 160 Amps, AC 415 Volts, with Icu= 25 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 07 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amps. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 25 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No (b) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 03 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amps . (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No (c ) On load change over switch 4 pole 200 Amps without sheet steel enclosure Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 25 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty- 01 No (b) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 4 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 500 Amps, with heat shrinkable PVC sleeves. (b) MCCB, 4 pole having current ratings 320 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No (b) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-Qty - 6 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amps. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty -01 No Outgoing :(a) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magneticr release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty- 06 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amps. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 01 No (b) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty.- 01 No (c ) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-Qty- 06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amps . (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 02 No (b ) MCCB, 4 pole having current ratings 125 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No (c ) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amps ,with heat shrinkable PVC sleeves. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-. Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 09 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 200 Amps. (b) MCCB, 4 pole having current ratings 160 Amps, AC 415 Volts, with Icu= 25 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 500 Amps . (b) MCCB, 4 pole having current ratings 320 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty- 01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-. Qty - 01 No (b) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with themal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty.- 06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amps. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty - 01 No (b) MCCB having current ratings 40 Amps with rupturing cap 16 KA , AC 415 Volts 4 pole with thermal magnetic and adjustable over load setting (Min 70% to 100%) complete with spreader links. Qty- 06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 200 Amps. (b) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty- 01 No Outgoing :(a) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amps. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty .- 08 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amps ,with heat shrinkable PVC sleeves. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty- 01 No Outgoing :(a) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty- 01 No (b) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 06 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amps . (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty.- 01 No Outgoing :(a) MCCB, 4 pole having current ratings 200 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty.- 01 No : (b) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amps. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 125 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty.- 01 No (b) MCCB having current ratings 40 Amps with rupturing cap 16 KA , AC 415 Volts 4 pole with thermal release & adjustable over load setting (Min 70% to 100%) as per IEC 60947-1&2 complete with spreader links.Qty - 06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 250 Amps. (b) MCCB, 4 pole having current ratings 160 Amps, AC 415 Volts, with Icu= 25 KA , Ics = 100% of Icu, with thrmal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 125 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-Qty.- 01 No : (b) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amps. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty- 01 No Outgoing :(a) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty- 01 No : (b) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty -02 No (c) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-Qty.-06 No (d) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty.-06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 250 Amps,with heat shrinkable PVC sleeves. (b) MCCB, 4 pole having current ratings 160 Amps, AC 415 Volts, with Icu= 25 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 125 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 01 No (b) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-Qty- 06 Nos
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amps. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty- 01 No Outgoing :(a) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty- 01 No (b) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links- Qty.-06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amps. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 200 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links-.Qty - 01 No (b) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links Qty.-06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 250 Amps . (b) MCCB, 4 pole having current ratings 160 Amps, AC 415 Volts, with Icu= 25 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links.- Qty -01 No Outgoing :(a) MCCB, 4 pole having current ratings 125 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links.-Qty - 01 No (b) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links Qty -06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 1000 Amps. (b) MCCB, 4 pole having current ratings 630 Amps, AC 415 Volts, with Icu= 50 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. -Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 630 Amps, AC 415 Volts, with Icu= 50 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty- 01 No (b) MCCB, 4 pole having current ratings 100 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links -Qty- 02 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 1000 Amps. (b) MCCB, 4 pole having current ratings 630 Amps, AC 415 Volts, with Icu= 50 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. -Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 630 Amps, AC 415 Volts, with Icu= 50 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty - 01 No (b) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty -06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 1000 Amps. (b) MCCB, 4 pole having current ratings 630 Amps, AC 415 Volts, with Icu= 50 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links -Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty- 01 No (b) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty-06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 600 Amps. (b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links.- Qty -01 No Outgoing :(a) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty- 01 No (b) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty -06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amps. (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links - Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 200 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links.- Qty - 01 No (b) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty -06 Nos,
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming: (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 400 Amps . (b) MCCB, 4 pole having current ratings 250 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessor release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty - 01 No Outgoing :(a) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty - 01 No (b) MCCB, 4 pole having current ratings 40 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty -06 Nos.
All as per item No 27, 27.01 to 27.03 here-in-before but comprising of the following :- Incoming (a) Bus bar chamber comprising 4 Nos copper strip bus bars made of copper strip of capacity 200 Amps. (b) MCCB, 4 pole having current ratings 125 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty - 01 No Outgoing : (a) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) as per IEC -60947-1 and 60947-2 standard and fixed magnetic setting, complete with spreader links. Qty-02 Nos (b) MCB FP having current ratings 63 Amps with rupturing cap 10 KA , AC 230 Volts 'C' curve type. Qty- 01 No (c ) MCB DP having current ratings 40 Amps with rupturing cap 10 KA , AC 230 Volts , 'C' curve type.Qty- 02 Nos (d) Street light control switch comprising of (i) Time Switch Multifunctional digital for automatic switch ON/ OFF of street lights suitable for working on 110 to 240 Volts , Qty- 01 No (ii) Air break contactor AC 415 Volts, 50 Hz , 3 Pole 415 Volts, 63 Amps, AC-1 Rating with operating coil 220 Volts. 1 Nos (iii) MCB SP 2.5 Amps -Qty - 04 Nos . Note for item No 27, 27.01 to 27.03, 28 to 93 :- The structural and connection diagram of panel should be got approved before placing order to the panel manufacturer.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 Part-I of size 400 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 Part-I of size 240 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 Part-I of size 150 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 Part-I of size 95 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 Part-I of size 70 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 Part-I of size 16 sq mm 4 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 Part-I of size 16 sq mm 2 core complete all as specified and directed. Note for item No 94 to 100 :- Factory visit/inspection for LT cables at OEM premises will be carried out by rep of Accepting Officer and all necessary arrangements will be get done by the contractor & quoted rates are deemed to be included for the same .
S&F PVC Aluminium conductor cable 2.5 sqmm 2 core ISI marked confirming to IS 7098 Part-I complete all as specified and as directed.
S&F MS sheet metal enclosure Busbar Chamber of 200 Amps 4 way including electric connection ,etc with and including angle made out of 50 mm x 50 mm x 6 mm mounted on PCC foundation of size as required or approved by manufacturers in PCC 1:3:6 Type C-2 , using 40 mm graded crushed stone aggregate complete all as specified and directed.
S&F MS sheet metal enclosure Busbar Chamber of 400 Amps 4 way including electric connection ,etc with and including FI clamp made out of 50 mm x 3 mm mounted on PCC foundation of size as required or approved by manufacturers in PCC 1:3:6 Type C-2 , using 40 mm graded crushed stone aggregate complete all as specified and directed.
S&F on pole ,dust proof, vermin proof , out door type Polycarbonate box including MCB SPN 6 Amps,, SPN bus bar, insulator,GI nut, bolts and washers and aluminium lugs etc with and including FI clamp made out of 30 mm x 3 mm , nut and bolts complete all as specified and directed.
M&L for cable end termination kit in door/out door, heat shrinkable type suitable for XLPE/ PVC cables of size 16 Sqmm to 50 sqmm 3½ core with working voltage 1100 volts complete all as specified and directed.
M&L for cable end termination kit in door/out door, heat shrinkable type suitable for XLPE/ PVC cables of size 70 Sqmm to 150 sqmm 3½ core with working voltage 1100 volts complete all as specified and directed.
M&L for cable end termination kit in door/out door, heat shrinkable type suitable for XLPE/ PVC cables of size 185 Sqmm to 400 sqmm 3½ core with working voltage 1100 volts complete all as specified and directed.
Dismantling old unserviceable cross-arms of M.S channel or angle sections etc complete all as specified and directed.
Dismantling of old unserviceable ACSR complete any size and any type complete all as specified and directed.
Taking out old unserviceable LT Panels complete any type complete all as specified and directed.
M & L for Earth continuity GI Strip size 25 x4 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing complete all as specified and directed.
S & F GI tubing 40 mm dia "light grade" for protection of GI strip/cable including suitable size MS clamp complete all as specified and directed.
Provision of cable route indicator fabricated from 50 mm x 50 mm x 6 mm angle iron of minimum length 650 mm including 6 mm thick Cast iron disc of size 100 mm dia duly engraved (in casting ) HT/LT cable duly reveted with angle iron at one end and other end duly grouted in ground with PCC 1:3:6 type C1 using stone aggregate of minimum size 20 cm x 20 cm x 30 cm complete all as specified & directed.
M/s T. S. POWER CO.
R D Bansal
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .