Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.1 LAccepted-AOC 2099 6A GALI NO 15 PREM NAGAR NEW DELHI 08 | NEW DELHI | DELHI | 110001 | ₹1.1 L | L1 | Accepted-AOC As per NIT |
Tender Value
₹1.2 L
EMD Value
₹2,500
Closing Date
23 Apr 2026, 3:00 pmClosed
Sh. Sudhir Kumar
Old Zonal MCD Office, Vishal Enclave, Rajouri Garden, West Zone, Delhi -110027.
Improvement/Upgradation of Electrical Installation in various Municipal Public Toilets in Ward No. 113, 115 and 116 in AC -32 Uttam Nagar under West Zone.
2026_MCD_274914_1
E.E(Elect.)/WZ/2026-27/NIT No.03
Open Tender
Electrical Works
Percentage
90 days
EE/Electrical-III Division West Zone.
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
₹2,500
4 May 2026
16 Apr 2026
23 Apr 2026
16 Apr 2026
23 Apr 2026
16 Apr 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.001 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*6 sqmm | 70 | meter | 95 | ₹6,650 |
| 1.002 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV
with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing complete in
all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures
as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
18-22 Watt | 22 | each | 787 | ₹17,314 |
| 1.003 | Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%,
Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per
IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protectionEMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum
50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as
approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction
temperature shall not rise above 90°C).50 watt | 7 | each | 2,089 | ₹14,623 |
| 1.004 | P/F Hot press sheet moulded compound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof pole box of inner dimension 200x160x98mm (NS) complete with suitable arrangement for fixing of 2 nos of 6 to 32 amp single pole MCB & 63 Amp. Double pole isolator (MCB/Isolator excluded) with neutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plate of suitable size with danger monogram property printed on the cover etc as reqd. as reqd. | 7 | each | 742 | ₹5,194 |
| 1.005 | Supply of 12" (300 mm) sweep 1400 rpm exhaust fan heavy duty complete with shutter blades etc. as required. | 6 | each | 2,567 | ₹15,402 |
| 1.006 | Supply of 250 mm ( 10inch) sweep 1250 rpm exhaust fan fresh air type complete with shutter blades etc. as required. | 4 | each | 1,955 | ₹7,820 |
| 1.007 | Installation of Exhuast fan in the existing opening including making good the damage,connection,testing,commissioning etc. as required
upto 450 mm sweep | 10 | each | 556 | ₹5,560 |
| 1.008 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar,
interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6 way , Double door | 2 | Each | 2,390 | ₹4,780 |
| 1.009 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. single pole and neutral | 8 | each | 643 | ₹5,144 |
| 1.01 | Double pole | 6 | each | 696 | ₹4,176 |
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.09 MB
0301ConditionsandCircular.pdf
Tender Documents • 10.99 MB
0301GCC.pdf
Tender Documents • 1.74 MB
0301DNIT.pdf
Tender Documents • 1.64 MB
0301Schedule.pdf
Tender Documents • 4.55 MB
BOQ_321102.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .