Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹29.5 LAccepted-AOC 42 43A VIDYA SAGAR SARANI PALLY BARISHA KOLKATA 700 008 | KOLKATA | WEST BENGAL | 700008 | L1 | Accepted-AOC Being lowest bidder | |
| 2 | L2₹34.9 L+₹4.4 L (14.6%)Rejected-Finance | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹35.4 L+₹4.9 L (16.2%)Rejected-Finance | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹39.6 L+₹9.1 L (29.9%)Rejected-Finance 38 BAGUIATI ROAD KOLKATA 700059 | 24 PARAGANAS NORTH | WEST BENGAL | 700059 | L4 | Rejected-Finance Other than lowest | |
| 5 | Rejected-Technical ROOM NO B 111 PART III GANESH MURTINAGAR CAPT PRAKASH PETHE MARG CUFFEPRADE CALABA MUMBAI 400 005 | MUMBAI | MAHARASHTRA | 400005 | - | Rejected-Technical Due to contractor is not enlisted for eligible category. |
Tender Value
₹34.5 L
EMD Value
₹69,000
Closing Date
31 Jan 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE(FW) Kolkata
D9 Commissariat Road Hastings Kolkata 700022
REPAIR/MAINT OF EXTERNAL ELECTRIC SUPPLY AT OTM AND MD ACCN INSIDE FORT WILLIAM AND ALLIED WORKS UNDER GE (FW) KOLKATA
2022_MES_556324_2
8905/FW/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE(FW) Kolkata
Ref tender documents
7 documents required · 7 mandatory
₹500
GE(FW) Kolkata
₹69,000
30 Mar 2023
14 Jan 2023
1 Feb 2023
14 Jan 2023
31 Jan 2023
14 Jan 2023
Amount
Taking down unserviceable LT cable for repair/ replacement etc (from cable duct/underground trench / pole), stacking properly (cable, pipe and bricks) complete all as directed by the Engr-in-Charge of the following cross - sections :- (Note :- Earth work to be measured and paid separately.
10 Sqmm to 16 Sqmm, 2/3.5/4 core
25 Sqmm to 50 Sqmm, 3.5 core
70 Sqmm to 120 Sqmm, 3.5 core
150 Sqmm to 185 Sqmm, 3.5 core
240 Sqmm 4 core to 400 Sqmm, 4 Core
Excavation in trenches not exc 1.5 metre width and not exceeding 1.5 metre in depth in soft/loose soil and getting complete all as specified and as directed.
Excavation of trench in road/hardstanding etc, not exc 1.50 m wide and not exc 1.50 m deep and getting out complete all as specified and directed.
Returning, filling in including spreading levelling watering and well ramming in layers n.exc 25 thick for soft/loose soil complete all as specified and as directed.
Removal of excavated material to a distance n.exc 50 metre and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and as directed.
Supply and laying double wall corrugated HDPE pipe, 120 mm outer dia, confirming to IS-16205 (Part 24) with couplers, end caps & bends as required, laid in trenches for cable protection complete all as specified and directed. (Note :- Earth work to be measured and paid separately.
Supply and laying double wall corrugated HDPE pipe, 90 mm outer dia, confirming to IS-16205 (Part 24) with couplers, end caps & bends as required, laid in trenches for cable protection complete all as specified and directed. (Note :- Earth work to be measured and paid separately.
Relaying of XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cable 1100 Volts grade with stranded aluminium conductor cable, laid in trench or fixed to wall / passing through pipe/ pole. (retrieved against item No 1 above) complete all as directed by the Engr-in-Charge of the following sizes :- (Note :- Necessary earth work to be measured and paid separately.
10 sqmm to 16 Sqmm, 2/3.5/4 Core
25 Sqmm to 50 Sqmm, 3.5 core
70 Sqmm to 120 Sqmm, 3.5 core
150 Sqmm to 185 Sqmm, 3.5 core
240 Sqmm to 400 Sqmm, 3.5 core
Supply, Laying and testing XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cable 1100 Volts grade with stranded aluminium conductor cable, laid in trench or fixed to wall/passing through pipe/pole complete of the following sizes and cross sectional area :- (Note :- Necessary earth work to be measured and paid separately.
50 Sqmm, 3.5 core
120 Sqmm, 3.5 core
185 Sqmm, 3.5 core
240 Sqmm, 3.5 core
S&F heat shrinkable straight through Joints using suitable jointing Kit suitable for 1100 volts grade XLPE insulated stranded aluminium conductor cable including testing on completion complete all as specified and directed by the Engr-in-Charge for the following size of cables :-
25 sqmm to 50 sqmm, 3.5/4 core
70 sqmm to 150 sqmm, 3.5 core
185 sqmm to 240 sqmm, 3.5 core
S&F in repair MCCB, 4 pole, 50 kA, with microprocessor based release, 630 Amps, Ics=100% of Icu, 415 Volts AC with all accessories & copper spreader complete all as specified and directed. (Make: L&T, Cat No: CM93008OOOOX1 / LEGRAND, Cat No: 6699 19 /HAGER, Cat No: HMW631JR /SCHNEIDER, Cat No: LV432894 / C&S Cat No.CS630NFMU*4P or equivalent model in ABB/SIEMENS)
S&F in repair MCCB, 4 pole, 36 kA, with microprocessor based release, 400 Amps, Ics=100% of Icu, 415 Volts AC with all accessories & copper spreader complete all as specified and directed. (Make: L&T, Cat No: M93003OOOOX1 / LEGRAND, Cat No: 6699 07 /HAGER, Cat No:HNW401JR /SCHNEIDER, Cat No: LV432677 / C&S Cat No. CSE3N400ATM4P-* or equivalent model in ABB/SIEMENS)
S&F in repair MCCB, 4 pole, 36 kA, with thermal magnetic release, 200 Amps, Ics=100% of Icu, 415 Volts AC with all accessories & copper spreader complete all as specified and directed. (Make: L&T, Cat No: CM92109OON1OG / LEGRAND, Cat No: 6690 71 /HAGER, Cat No:HNT201DR /SCHNEIDER, Cat No: LV431641 / ABB, Cat No: 1SDA116345R1 / C&S Cat No.CSE2SX250ATM4P-* or equivalent model in SIEMENS)
S&F in repair MCCB, 4 pole, 36 kA, with thermal magnetic release, 160 Amps, Ics=100% of Icu, 415 Volts AC with all accessories & copper spreader complete all as specified and directed. (Make: L&T, Cat No: CM92108OOM1OG / LEGRAND, Cat No:6690 70 /HAGER, Cat No:HNS161DR /SCHNEIDER, Cat No: LV426319 / ABB, Cat No: 1SDA116274R1 / C&S Cat No. CSE2NN250ATM4P-* or equivalent model in SIEMENS)
S&F in repair MCCB, 4 pole, 25 kA, with thermal magnetic release, 100 Amps, Ics=100% of Icu, 415 Volts AC with all accessories & copper spreader complete all as specified and directed. (Make: L&T, Cat No: CM91712OOKOOG / LEGRAND, Cat No:6697 18 /HAGER, Cat No:HHS101DR /SCHNEIDER, Cat No: LV426217/ ABB, Cat No: 1SDA116246R1 / C&S Cat No. CSE1M125ATM4P-* or equivalent model in SIEMENS)
S&F in repair MCCB, 4 pole, 25 kA, with thermal magnetic release, 63 Amps, Ics=100% of Icu, 415 Volts AC with all accessories & copper spreader complete all as specified and directed. (Make: L&T, Cat No: CM91712OOHOOG / LEGRAND, Cat No:6697 16 /HAGER, Cat No: HHS064DR /SCHNEIDER, Cat No: LV426215 / ABB, Cat No: 1SDA116244R1 / C&S Cat No. CSE1M125ATM4P-* or equivalent model in SIEMENS)
S&F in repair motorised change over switch, 415V, 3 phase 4 pole 200 Amps, open execution type, alongwith AST controller with wire harness, fixed on existing panel, incl all accessories complete all as specified and directed. (MAKE: L&T, Cat No: CK90163BOOO + CK90192OOOO / HAGER, Cat No: HIB425I + HZI811I / ABB, Cat No: 1SYN022846R1590 + 1SCA122946R1001 or equivalent model in LEGRAND / SCHNEIDER / SIEMENS)
S&F in repair motorised change over switch, 415V, 3 phase 4 pole 400 Amps, open execution type, alongwith AST controller with wire harness, fixed on existing panel, incl all accessories complete all as specified and directed. (MAKE: L&T, Cat No: CK90166BOOO + CK90192OOOO / HAGER, Cat No: HIB440I + HZI811I / ABB, Cat No: 1SYN022847R3250 + 1SCA122946R1001 or equivalent model in LEGRAND / SCHNEIDER / SIEMENS)
S&F in repair motorised change over switch, 415V, 3 phase 4 pole 630 Amps, open execution type, alongwith AST controller with wire harness, fixed on existing panel, incl all accessories complete all as specified and directed. (MAKE: L&T, Cat No: CK90167BOOO + CK90192OOOO / HAGER, Cat No: HIB463I + HZI811I / ABB, Cat No: 1SYN022873R1990 + 1SCA122946R1001 or equivalent model in LEGRAND / SCHNEIDER / SIEMENS)
S&F in repair surge protection device, 3 phase, 4 module, protection against direct and indirect lightning surge type, 1+2 type, maximum discharge current 50 kA, fixed at LT panel including complete wiring with suitable size copper cable complete all as specified and directed. (MAKE: L&T, Cat No: AUSP123PN50 or equivalent model in HAGER / ABB/ LEGRAND / SCHNEIDER / SIEMENS)
S&F cable route indicator (blue in colour) for LT UG cable of 1100 volts, with embossed letters, min 80 mm dia, made from 5 mm thick cast iron plate 80 mm dia, bolted with 40 x 40 x 6 m angle iron of height 0.60 mtr above GL, embedded in PCC (1:3:6) type C2 (using 40 mm graded aggregate) of size 200 x 200 x 200 mm block, including taking down old unserviceable one, complete all as specified and directed. (NOTE: Cost of PCC is deemed to be included in quoted rate)
M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground vertically to a depth not less than 2.25 meter deep below ground level with top edge earth plate at a depth not less than 1.5M below normal ground level connected to galvanized iron strip 25 x 4 mm (upto 7.5 metres) by means of bolts, nuts check nuts and washers of galvanized steel and connected to main switch board or main control board as directed and including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 45 cm x 45 cm x 5 cm reinforced with 8 mm dia. TMT bars @ 150 mm centre to centre both ways, with one handle for lifting made out of 8 mm dia MS bar, provision of funnel, wire mesh, 20 mm bore galvanized steel tubing (Medium grade) for watering, charcoal or coke and salt in alternate layers, 40 mm bore galvanized steel tubing medium grade for protection of earth lead connection, necessary excavation and earth work in any type of soil and including necessary testing and dismantling of existing unsv earthing complete all as shown in Figure 15A of IS 3043 :1987, complete all as specified and directed.
Taking out unserviceable LT panel board/Feeder Pillar (of any size) and Supply, install, commissioning and testing of outdoor type LT panel board, cubical type, sloping canopy top roof, dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1500 mm x 1500 mm x 600 mm, fabricated in CPRI approved factory with front and back openable door (with locking arrangement) and making compartment for each ACB/MCCB/change over switch separately, duly powder coated over coat of red oxide zinc chrome primer inclusive of four numbers aluminium bus bar of 1000 Amps capacity (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and two numbers Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 0.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with MS angle iron 50x50x6 mm legs not more than 450mm long including grouting with PCC 1:2:4 type B1 complete all as directed by the Engr-in-Charge including S&F of the following accessories :-
On Load Change Over Switch 630 Amps, 4 Pole, Manual Type, open execution, 415V, 3 phase - 01 No (Make: L&T, Cat No: CO46300OOOO / HAGER, Cat No: HI4581 / ABB, Cat No: 1SYN022785R6050 / C&S Cat No. CSCS315DM4CO or equivalent item in LEGRAND / SCHNEIDER)
Surge protection device, 3 phase, 4 module, 3P+N, type 1+2, for protection against direct and indirect lightning surge, maximum discahreg current 50 kA -01 No (MAKE: L&T, Cat No: AUS0123PN50 OR equivalent model in ABB / HAGER / SCHNEIDER / LEGRAND/SIEMENS)
MCCB, 4 pole, 50 KA, thermal magnetic release, 630 Amps, Ics=100% of Icu, 415 Volts AC - 02 Nos (Make: L&T, Cat No: CM94104OOT1OG / HAGER, Cat No: HMJ631DE / SCHNEIDER, Cat No: LV432894/ LEGRAND, Cat No: 6676 65 /ABB, Cat No: 1SDA116388R1 / C&S Cat No.CS630NFMU*4P)
MCCB, 4 pole, 36 KA, thermal magnetic release, 250 Amps, Ics=100% of Icu, 415 Volts AC - 02 No (Make: L&T, Cat No: CM92109OOP1OG / HAGER, Cat No: HNT251DR / SCHNEIDER, Cat No: LV431640 / LEGRAND, Cat No: 6690 72 / ABB, Cat No: 1SDA116346R1 / C&S Cat No. CSE2SX250ATM4P-*)
MCCB, 4 pole, 25 KA, thermal magnetic release, 200 Amps, Ics=100% of Icu, 415 Volts AC - 01 Nos (Make: L&T, Cat No: CM90642OONO / HAGER, Cat No: HHT201DR / SCHNEIDER, Cat No: LV525312 / LEGRAND, Cat No: 4202 18 / ABB, Cat No: 1SDA116333R1 / C&S Cat No. CSE2M250ATM4P-*)
MCCB, 4 pole, 25 KA, thermal magnetic release, 160 Amps, Ics=100% of Icu, 415 Volts AC - 01 Nos (Make: L&T, Cat No: CM90642OOMO / HAGER, Cat No: HHS161DR / SCHNEIDER, Cat No: LV516313 / LEGRAND, Cat No: 6690 30 / ABB, Cat No: 1SDA116250R1 / C&S Cat No. CSE2M250ATM4P-*)
MCCB, 4 pole, 25 KA, thermal magnetic release, 100 Amps, Ics=100% of Icu, 415 Volts AC - 02 Nos (Make: L&T, Cat No: CM91712OOKOOG / HAGER, Cat No: HHS101DR / SCHNEIDER, Cat No: LV510317 / LEGRAND, Cat No: 4200 55 / ABB, Cat No: 1SDA116246R1 / C&S Cat No. CSE1M125ATM4P-*)
Astronomical Timer Switch with MNX 32 Amp, 3 pole cotactor - 01 No
MCB, 10 kA, 'C' Curve, SP, 06-32 Amps - 03 Nos
CT's ratio 600/5A - 01 Set (Set of 03)
LED indicating Lamp with holder for main supply & standby supply indicating RYB (Set of three) - 01 Set
Note:-(i) All incoming and out going cables, duly thimble along with suitable size of brass cable glands, to be connected to accessories. (ii) All ACB, MCCB & Changeover to be connected internally with suitable size of aluminium strip. (iii) All requisite accessories including spreader terminals shall be provided alongwith MCCBs and cost of the same shall be deemed to be inclusive in the quoted rates.
Taking out unserviceable LT panel board (of any size) and Supply, install, commissioning and testing of outdoor type LT panel board, cubical type, sloping canopy top roof, dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1800 mm x 1800 mm x 600 mm, fabricated in CPRI approved factory with front and back openable door (with locking arrangement) and making compartment for each ACB/MCCB/change over switch separately, duly powder coated over a coat of red oxide zinc chrome primer inclusive of four numbers aluminium bus bar of 1000 Amps capacity (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and two numbers Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 0.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with MS angle iron of size 50x50x6 mm complete with legs not more than 450mm long including grouting with PCC 1:2:4 type B1 complete all as directed by the Engr-in-Charge including supply and fixing of the following accessories :-
On Load Change Over Switch 630 Amps, 4 Pole, Manual Type, open execution, 415V, 3 phase - 02 Nos (Make: L&T, Cat No: CO46300OOOO / HAGER, Cat No: HI4581 / ABB, Cat No: 1SYN022785R6050 / C&S Cat No. CSCS315DM4CO or equivalent item in LEGRAND / SCHNEIDER)
Surge protection device, 3 phase, 4 module, 3P+N, type 1+2, for protection against direct and indirect lightning surge, maximum discahreg current 50 kA -01 No (MAKE: L&T, Cat No: AUS0123PN50 OR equivalent model in ABB / HAGER / SCHNEIDER / LEGRAND/SIEMENS)
MCCB, 4 pole, 36 KA, thermal magnetic release, 630 Amps, Ics=100% of Icu, 415 Volts AC - 03 Nos (Make: L&T, Cat No: CM94106OOT1OG / HAGER, Cat No: HNJ631DE / SCHNEIDER, Cat No: LV563309/ LEGRAND, Cat No: 6676 57 / ABB, Cat No: 1SDA116379R1 / C&S Cat No.CS630NFMU*4P)
MCCB, 4 pole, 36 KA, thermal magnetic release, 250 Amps, Ics=100% of Icu, 415 Volts AC - 01 Nos (Make: L&T, Cat No: CM92109OOP1OG / HAGER, Cat No: HNT251DR / SCHNEIDER, Cat No: LV525343/ LEGRAND, Cat No: 6690 72 /ABB, Cat No: 1SDA116346R1 / C&S Cat No. CSE2SX250ATM4P-*)
MCCB, 4 pole, 25 KA, thermal magnetic release, 160 Amps, Ics=100% of Icu, 415 Volts AC - 01 Nos (Make: L&T, Cat No: CM90642OOMO / HAGER, Cat No: HHS161DR / SCHNEIDER, Cat No: LV516313 / LEGRAND, Cat No: 6690 30 / ABB, Cat No: 1SDA116250R1 / C&S Cat No. CSE2M250ATM4P-*)
MCCB, 4 pole, 25 KA, thermal magnetic release, 125 Amps, Ics=100% of Icu, 415 Volts AC - 01 Nos (Make: L&T, Cat No: CM90642OOLO / HAGER, Cat No: HHS126DR / SCHNEIDER, Cat No: LV516312 / LEGRAND, Cat No: 6697 19 / ABB, Cat No: 1SDA116249R1 / C&S Cat No. CSE1M125ATM4P-*)
MCB, 10 kA, 'C' Curve, SP, 06-32 Amps - 03 Nos
CT's ratio 600/5A - 01 Sets (Set of 03)
LED indicating Lamp with holder for main supply & standby supply indicating RYB (Set of three) - 01 Set
Spare compartment with control wire for MCCB - 02 Nos
Note:-(i) All incoming and out going cables, duly thimble along with suitable size of brass cable glands, to be connected to accessories. (ii) All ACB, MCCB & Changeover to be connected internally with suitable size of aluminium strip. (iii) All requisite accessories including spreader terminals shall be provided alongwith MCCBs and cost of the same shall be deemed to be inclusive in the quoted rates.
TOTCO
HARSH ENGINEERING
MODERN AGENCY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .