Karnataka Power Transmission Corporation Limited
Rajkumar S Biradar
Combined package for Providing Additional 3rd 100MVA, 220KV Power Transformer at 220 KV Honnali Sub-Station in Honnali Taluk, Davanagere District (b)Augmentation of 2x100MVA 220/66kv Power Transformers by 2x150MVA 220/66kv Power Transformers at 220/66kv receiving station Antharasanahalli in Tumkur Taluk, Tumkur District on Total Turnkey basis
KPTCL/2025-26/SS/WORK_INDENT3049
KPTCL/2025-26/SS/WORK_INDENT3049
Open
Sub-Station
Two Tender Document System(Two Cover)
KPTCL CGM Tech Corporate Office Bengaluru
4 documents required · 4 mandatory
Documentary proof for clause no.2.2 (I) of ITT, such as P.O, LOI/LOA, DWA, Work done, Performance Certificates issued by the end users not below the rank of Executive/ Divisional Engineer of Lead Bidder & Consortium partner (In case of Consortium)
Documentary proof for clause no.3.2 (b)(i) of ITT, such as P.O, LOI, LOA, DWA, Work done, Performance Certificates issued by the end users not below the rank of Executive or Divisional Engineer of Lead Bidder or Consortium Partner.
Audited financial statements including Balance sheets, Profit and Loss statements, Turnover Certificate, Auditors Reports of the last five years preceding the date of bid submission of the Bidder & Consortium partner (In case of Consortium)
Bank Guarantee/Insurance Surety Bonds towards Bid Security (EMD) shall be furnished and uploaded in accordance with Cl. No. 13 of ITT
Self declarations of Lead Bidder & Consortium partner (In case of Consortium) in respect of Litigation, dis qualification due to non-performance, Risk & cost clause and Restriction on border sharing as specified in Annexure XVI& Annexure XVII as per Clause No.2.4of ITT
Documentary proof for Clause No: 3.6 of ITT: Assessed available tender capacity such as, Maximum value of works executed (KPTCL & Non-KPTCL) in any one year during the last five years taking into account the completed as well as works in progress and Statements showing the value of existing commitments and on-going works as well as the stipulated period of completion remaining for each of the works listed countersigned by the Employer in charge, not below the rank of an Executive Engineer or equivalent as sought in Note of the said clause in the prescribed format as in clause No: 1.5 of Qualification Information of the Bidder & Consortium partner (In case of Consortium)
Details of Works on hand and Ongoing contractual commitments of the Bidder & Consortium partner (In case of Consortium)
Bankers Certificate of the Bidder & Consortium partner (In case of Consortium) for assessing the Liquid Assets (Letter of Credit/ Certificate from banks meeting fund requirement) to assess Lines of Credit and availability of other Financial resources
Type test reports as per tender documents / technical specifications
Consortium Agreement (In case of Consortium).
Power of Attorney in favour of all the persons signing the documents, Power of Attorney for Consortium, combined power of attorney signed by the signatories of all the members of consortium as an evidence of authorization for nominating leader (Prime Bidder) of consortium
Copies of original documents defining the Constitution or Legal Status, place of Registration and Principal place of Business of the Bidder, written Power of Attorney to the Signatory of the Bid to commit the Bidder to the Contract along with the resolution passed in this regard by the Board of Directors / all the Partners of the Firm
Certificate of Incorporation of the Individual/ Consortium or any relevant document in respect of Partnership/Proprietorship firms as per the tender document
The bidder and Consortium Partner(in case of Consortium) should have valid GST registration with GSTIN number, PAN Card and ISO Certificates. Note: The successful Bidder and his consortium partner who have GST registration in other States should have GST registration in the State of Karnataka mandatorily at the time of execution of the Contract Agreement
No Deviation Letter of Undertaking as in Annexure-Vn Certificate
Letter of Undertaking as in Annexure-V
The Qualification and experience of key Personnel proposed for carrying out the Work
Description of the Tools & Plant available with them for execution of the Work
An undertaking to source the supply of equipment/material from KPTCL approved Vendors only as per the QR for Vendor registration, available in the KPTCL website i.e., https://kptcl.karnataka.gov.in, Link Tender and Procurement - application for Vendor registration etc
All self -declarations, legally enforceable deeds & Undertakings as per terms and conditions of the tender
All details as called for in the Technical specifications of all the equipments/ materials of the Tender
Any other required documents as per the qualifying requirements, terms and conditions of the tender
Any other required documents as per the qualifying requirements, terms and conditions of the tender
proposed methodology and program of construction as per clause No.1.13 of Section-3-Qualification Information
Filled in Techno commercial sheet shall be uploaded along with all other QR documents. Price Offers shall be quoted in the item-wise bid Financial offer, provisioned in the e-procurement portal. In case the Prices are uploaded in/along the Techno commercial Bid, then Bid will be summarily rejected. The Techno-commercial sheets shall be uploaded in KPTCL excel formats only.
Information on litigations in which the Tenderer is involved as per prescribed format as at 1.12 of Qualification Information
The Tenderer shall upload declarations for Deviations, if any as per Schedule-5 and Schedule-6 of the Techno Commercial sheets
As per Clause No. 2.3 of ITT above, Bidder shall upload valid Super Grade Electrical Contractors License issued by the Govt. of Karnataka of Lead Bidder & Valid Super Grade Electrical Contractors License OR Class-A/Class-1 Electrical Contractors License issued by any State/Central Government in India of Consortium partner (in case of Consortium) as on the date of bid submission
In case the consortium partner is not possessing SGL but having Class-A/ Class-1 Electrical Contractors License, Bidder shall upload an undertaking from the Consortium partner agreeing that, in case the Lead Bidder failed to execute the contract, the consortium partner shall get the work done by the Agency who is having valid SGL issued by GoK and have executed similar nature of work earlier after duly obtaining approval from KPTCL
₹7,500
₹35.9 L
2 Jan 2026
13 Dec 2025
3 Jan 2026
13 Dec 2025
13 Dec 2025
150 MVA, 220/66/11 kV Power Transformer :
3 Ph, 50 Hz, Core type, 3 winding Star/Star/Delta, transformer Vector Group: YNyn0d11, OLTC, Bushing CT for Tertiary of ratio 1000/1A, 5P20, 15VA, ONAN/ONAF/...
Circuit Breaker : SF6 gas circuit breaker with rigid bi- metallic terminal connectors suitable for DRAKE ACSR with Spring/semi-Pneumatic/Pneumatic type operating mechanism and with mounting structures...
b) 66 kV, 2000 A, 40 kA SF6 CB as per technical specifications
Isolators and terminal connectors, as per technical specification including solid core cylindrical post insulators. 220KV, 1250 A, 50KA Class Double Break electrically cum manually operated isolator ...
ii) Upright mounting type without earth switch Live Point height 5750mm
iii) Under hung mounting type without earthswitch.
(12850mm mounting height)
ISOLATORS : Isolators and Terminal connectors etc., as per Technical specification including solid core cylindrical post insulators and marshalling box.Terminal connectors for isolators shall be as fo...
ii) Upright mounting type without earth switch Live Point height 4250mm
iii) Under hung mounting type without earthswitch.
(Mounting height 10000 mm)
Current Transformer: Oil filled Current transformers with rigid bimetallic terminal connectors suitable for Drake ACSR with Marshaling box complete as per technical specifications.
i) 220 kV clas...
Surge Arrestor : Surge arrestors (Porcelain Housing) metal oxide gapless type with rigid bimetalic connectors suitable for Drake ACSR complete as per technical specifications
i) 198KV, 10KA Class - II...
ii) 60KV,10KA Class - II, Heavy Duty Metal Oxide type.
Control and relay panel complete
Relay and protection Panels :
a) 220/66/11kV Power Transformer panel - Type 2T6 (as per annexure RPP2-SAS)
1) The Accuracy Class of metering core of CTs and a...
Fabrication, galvanising and supply of Mild Steel
of Station structures , Mounting Structures (excluding Bolts & nuts)-Total Weight
Supply of galvanised Bolts & Nuts for Station structures , Mounting Structures -Total Weight
Rigid Bus with Taps & Clamps : Aluminium tube conforming to 6340 WP of IS - 5082 / 1969 (BS 1600 - Sch. 40)
a) 75mm size --- 220KV side
b) 63mm size for connecting isolator to vertical tap - 220KV side
c) 50 mm size connecting isolator to vertical tap - 66KV side.
a) Inverted 'V' taps made of 63mm Aluminium tube (BS - 1600) of 2500mm vertical height for vertical portion and cross bus on 220KV side with rounded off end.
b) Straight taps made of 63mm Aluminium tube (BS - 1600) of 1250mm vertical height for vertical portion & cross bus on 66KV side with rounded off end.
Post insulator clamps suitable for 75mm Aluminium pipe and Post Insulator Solid Core Type. : a) 220kV Side Rigid Type
b) 220kV Side Expansion type
C) Corona bell suitable for Aluminium Pipe of size
a) 75mm on 220KV side
b) End cap 50mm AL tube 66kV side
b) End cap 63mm AL tube 66kV side
BUS BAR FORMATION: Drake ACSR 220KVSide.
Insulators: Post insulators - Cylindrical solid core insulators as per IS : 5350, Part II & III. For 220KV side - 2 units /stack
i. Post Insulators...
ii. High Level Post Insulators for 100MVA,Tr.,
iii. For 66KV side - 1 unit /stack , a) Post Insulators for 100MVA, at level difference -03 nos
Disc Insulator String: 11KV, 120KN Disc Insulator
(a) 220KV Side -Tension String: String of 16 units
66KV Side - Double Tension String : 2 string of 6 unit each for 100MVA Transformer
11KV 90KN Disc Insulator
(220KV side Suspension string- String of 14 units
66KV side Suspension string- string of 6 units
INSULATOR HARDWARES & CLAMPS
Bolted Type tension clamp to suit Drake ACSR 120KN 20mm
Bolted type Tension clamps for twin Drake ACSR conductor 90KN 16mm
Bolted Type Double Tension clamp to suit Drake ACSR for 66Kv side of 100MVA Transformer 120Kn 20mm
Bolted type suspension clamp to suit Drake ACSR 90KN 16mm
Bolted type suspension clamp to suit Double Drake ACSR for 66KV side of 100MVA Transformer
C type wedge Type connector (T-Type) suitable for Drake to Drake ACSR-220 kV Side
C type wedge Type connector suitable for Double Drake to Double Drake on 66KV side of 100MVA Transformer
PI Clamp suitable for post insulator & Drake ACSR - 220KV Side
PI Clapm suitable for post insulator & Double Drake ACSR- (for 66KV Side of 100 MVA Transformer)
Spacers for Double Drake ACSR
LT POWER CABLE :
1.1 kV class 4 x 70 Sq mm Aluminium L T Cable with glands /lugs/ferrules (AC Supply for Lighting, ACDB etc.,)
AC disrtibution box (outdoor)
1. Double front type, 24 terminals, 1200 x 1350 x 600mm, 2 I/C of 100A, MCCB 20KA + 24 O/G MCB 16A + 2 O/G of 100A , HRC fuse.
AC disrtibution box single front type, 6 terminals, 750x1350x300 mm, 1 I/C of 100A, MCCB 20KA + 6 O/G MCB 16A + 1 O/G of 100A , HRC fuse.
PVC Insulated Copper Control Cable with lugs/ferrules Sizes of Cable i) 19 core 2.5 Sq mm
ii) 10 core 2.5 Sq mm
iii) 4 core 2.5 Sq mm
v) 4 Core 4 Sq mm
iv) 4 Core 6 Sq mm
vii) 4 Core 16 Sq mm
FIRE FIGHTING EQUIPMENTS WITH NECESSARY MOUNTING STANDS : Supply, Erection and testing and commisioning of Fire Fighting equipment with necessary mounting stands etc:
a. Nitrogen Injection fire exting...
Mechanical foam Extinguisher type
ii. 9.0 litters
Water Type ( Gas Pressure Type )-9.0 Litters
Corbon Dioxide Type -4.5Kgs
Sand Type i. G.I bucket 9 liters
ii Steel Stands for above to have 4 buckets each stand
STATION & YARD LIGHTING (OUTDOOR) (To be designed, assessed & quoted by the bidder) i) Supplying and erection of street lighting lattice type structure along with GI pipe for fixing of LED lamp (0.18...
Supply of LED Street light luminaire with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded poly...
Supply and installation/ Fixing/ Provision of Outdoortype Thermoplastic Modular Panel enclosure with transparent Polycarbonate Lid, shockproof, IP65 (WeatherProof), rustproof, dustproof, waterproof...
iii) PVC Insulated Copper Control Cables : 1.1 KV PVC insulated Copper Control Cable with glands/Lugs/ Ferrules etc as per technical specification.
Equipment name plates and earthing name plates including fixing at outdoor yard
Rubber mats 2000 mm x 1000 mm x 12 mm size suitable for 11kV class
Replacement of Relays as per recommendation of RT Division
1. Numerical Differential relay with IEC 61850 Protocol
Numerical REF relay with IEC 61850 Protocol
Numerical Non Directional backup relay with IEC 61850 protocal
ERECTION PORTION
Power Transformer: Released good 100 MVA, 220/66/11 kV, 3 Ph, 50 Hz, Core type 2 winding Auto Transformer star/delta, vector group: Yna0d11, OLTC, bushing CT for tertiary of ratio 1000/1 A, 5P20, 15VA...
150 MVA, 220/66/11 kV Power Transformer :
3 Ph, 50 Hz, Core type, 3 winding Star/Star/Delta, transformer Vector Group: YNyn0d11, OLTC, Bushing CT for Tertiary of ratio 1515/1A, 5P20, 15VA, ONAN/ONAF/...
Circuit Breaker : SF6 gas circuit breaker with rigid bi- metallic terminal connectors suitable for DRAKE ACSR with Spring/semi-Pneumatic/Pneumatic type operating mechanism and with mounting structures...
b) 66 kV, 1250 A, 40 kA SF6 CB as per technical specifications
Isolators and terminal connectors, as per technical specification including solid core cylindrical post insulators. 220KV, 1250 A, 50KA Class Double Break electrically cum manually operated isolator ...
ii) Upright mounting type without earth switch Live Point height 5750mm
iii) Under hung mounting type without earthswitch.
(12850mm mounting height)
ISOLATORS : Isolators and Terminal connectors etc., as per Technical specification including solid core cylindrical post insulators and marshalling box.Terminal connectors for isolators shall be as fo...
ii) Upright mounting type without earth switch Live Point height 4250mm
iii) Under hung mounting type without earthswitch.
(Mounting height 10000 mm)
Current Transformer: Oil filled Current transformers with rigid bimetallic terminal connectors suitable for Drake ACSR with Marshaling box complete as per technical specifications.
i) 220 kV clas...
Surge Arrestor : Surge arrestors (Porcelain Housing) metal oxide gapless type with rigid bimetalic connectors suitable for Drake ACSR complete as per technical specifications
i) 198KV, 10KA Class - II...
ii) 60KV,10KA Class - II, Heavy Duty Metal Oxide type.
Control and relay panel complete
Relay and protection Panels :
a) 220/66/11kV Power Transformer panel - Type 2T6 (as per annexure RPP2-SAS)
Note: 1) The Accuracy Class of metering core of CTs and a...
b) Integration Charges with existing RTU System and gate way for 110kV Honnalli S/S
Fabrication, galvanising and supply of Mild Steel
of Station structures , Mounting Structures (excluding Bolts & nuts)-Total Weight
Supply of galvanised Bolts & Nuts for Station structures , Mounting Structures -Total Weight
BUS BAR FORMATION: Main bus/cross bus ( all the three phases in a segment) of using Falcon/Drake/Lynx/ Coyote-single/double conductors with fixing of insulator spacers, levelling of string conductors ...
ii) Formation of main bus / Cross bus using Twin DRAKE ACSR 66KV Side.
Insulators: Post insulators - Cylindrical solid core insulators as per IS : 5350, Part II & III. For 220KV side - 2 units /stack
i. Post Insulators...
ii. High Level Post Insulators for 100MVA,Tr.,
iii. For 66KV side - 1 unit /stack , a) Post Insulators for 100MVA, at level difference -03 nos
LT POWER CABLE : 1.1 kV class 4 x 70 Sq mm Aluminium L T Cable with glands /lugs/ferrules (AC Supply for Lighting, ACDB etc.,)
AC disrtibution box (outdoor)
1. Double front type, 24 terminals, 1200 x 1350 x 600mm, 2 I/C of 100A, MCCB 20KA + 24 O/G MCB 16A + 2 O/G of 100A , HRC fuse.
AC disrtibution box single front type, 6 terminals, 750x1350x300 mm, 1 I/C of 100A, MCCB 20KA + 6 O/G MCB 16A + 1 O/G of 100A , HRC fuse.
Post insulator clamps suitable for 75mm Aluminium pipe and Post Insulator Solid Core Type. : a) 220kV Side Rigid Type
b) 220kV Side Expansion type
C) Corona bell suitable for Aluminium Pipe of size
a) 75mm on 220KV side
b) End cap 50mm AL tube 66kV side
b) End cap 63mm AL tube 66kV side
BUS BAR FORMATION: Drake ACSR 220KVSide.
Releasing and Reerection portion :
Post insulator Cylindracal solid core insulators 220kV class, 2Unit/Stack
Re-commissioning of NIFPS in case of replacement of Transformers
(includes modification works required to connect all the accessories of NIFPS) All Voltage Class Transformers
Replenishment of Nitrogen gas
Replacement of Relays as per recommendation of RT Division
i) Numerical Differential relay with IEC 61850 protocol
Numerical REF relay with IEC 61850 protocol
Numerical Non-Directional Backup relay with IEC 61850 protocol
Earth Mat formation : Supplying and laying of 50 x 6 mm MS flat welding and applying ACB paint to welded portion without sodium bentnite clay as per drawing/standard specifications (all other material...
Grounding of equipments with 50 x 6 mm G I flat and connecting equipments to the earth mat/ground pit each point of earthing with all formation of works like bending, twisting , drilling of holes a...
Providing 25mm dia, round rod 1.05mtr. long Earthmat Spike including, bending top 50mm overlap, flatering and making spike edge at one end driving into the earth below the ground level and welding th...
Grounding of equipments by providing C.I. Pipe of 100mm ID 13mm thick 2.75 mtr. long with 2 part clamps out of GI Flat 50x6mm contnously welded all around the pipe using cast iron welding electrode as...
Supplying and providing 450mm dia and 450mm height 1.5" to 2" thickness RCC Hume pipe collars(non pressure type) for earth pits including transportation, all lead and lifts etc.
Dismantling of Existing 100MVA 220/66kV Power Transformer & Parts like Radiator, Bushings, Draining of Oil From Transformer, complete as per the Directions of Site Engineer incharge fo work. ( Total W...
Moving of Transformer from the plinth to the loading point. (50Mtr*340MT)=17000Mt/Mtr
Loading of Power Transformer
Un loading of Power Transformer
Transportation of transformer, loaded in 81 to 120MT truck & trailer from 220/66kV Antharsanahalli to 220/66kV Honnalli Sub Station (Minimum Distance taken =250 kms).
Note : Bidder has to quote in Rs...
Transportation of transformer accessories including Oil Drums complete, loaded in 10 MT lorry from 220/66kV Antharsanahalli to 220/66kV Honnalli Sub Station (Minimum,Distance taken =250 kms)
Releasing of 66KV Breaker (66kV 1250A 31.5kA SF6 breakers)
Releasing of Existing 66kV 1250A 31.5kA Double Break Manually opearated Isolators
1. Upright Mounting Type without E/S with LPH:5500mm
Releasing of existing 220Kv CTs of Ratio
Releasing of existing 66Kv CTs of Ratio
Dismantling of existing NCT and CT Structures
a. 220kV NCT's - 2Nos
Dismantling of existing NCT and CT Structures
a. 66 KV Side CT's - 2Nos
Releasing of Control Cables of various sizes
MANDATORY SPARES
Power transformer (100MVA): Oil Collecting bottle
Terminal Connector Clamps,
a. Suitable for 245kV class bushing to suit single Drake ACSR
b. Suitable for 66kV class bushing to suit single Drake conductor
a. Drain valve (100mm to 200mm size) suitable for 220kV class
b. Top/Bottom filter valve (50mm to 100mm size)
c. Top/Middle/Bottom Oil sampling valve with plug (15 to 25mm)
d. Header pipe valve
e. Gate/Butterfly valves of various sizes ranging from 50mm to 200mm
Prismatic Gauge
Starters, contactors, relays
Pressure Relief Device (PRD or PRV)
Oil Surge relay
Tap position indicator
Fixed and moving contacts for diverter switch
Fixed and moving conatcts for selector switch 220kV and above class
WTI with 4 contatcs, 15 meters capillary length with built in CCU RTD and external remote indicator, range 0-150 deg C with SCADA/SAS compatibility
OTI with 2 contacts, 15 meters capillary length with built in CCU RTD and external remote indicator range 0-150 deg C with SCADA /SAS compatibility
PT 100 sensor along with probe of suitable lengths
CIVIL PORTION ANTRASANHALLI
Excavation: Earth work excavation by manual means for drains, canals, waste weir, draft, approach channels, key trenches, foundation of bridges and such similar works in all kinds of soils, as per dra...
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes...
Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with supe...
Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/w...
CIVIL PORTION HONNALLI
Construction of Embankment by excavating the available approved Gravel/Murrum deposited at a place or borrow pits during or prior excavation with all lifts and lead, transportation to site, spreading,...
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by r...
Earth work excavation by manual means for drains,canals, waste weir,draft, approach channels, key trenches, foundation of bridges and such simillar works in all kinds of soils , as per drawing and tec...
Earth work excavation by manual means for drains,canals, waste weir, draft, approach channels, key trenches, foundation of bridges and such simillar works in all kinds of soils , as per drawing and te...
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes...
Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with supe...
Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with supe...
Providing and laying in position Cement Concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height....
Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/...
Earth work in surface excavation by mechanical means for lowering & leveling the ground for all works other than foundation in all kinds of soils & upto depth not exceeding 300mm as per drawing and t...
Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Materia...
Construction of dry lean cement concrete Sub- base over a prepared sub-grade with coarse and fine aggregate conforming to IS: 383, the size of coarse aggregate not exceeding 25 mm,aggregate cement rat...
Construction of M40 grade un-reinforced, dowel jointed, plain cement concrete pavement over a prepared sub base with Cement at 420 kg/m3, coarse and fine aggregate conforming to IS 383:2016, maximum s...
Filling available excavated earth (excluding rock) in trenches, plinth,
sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by r...
Removal of Unserviceable Soil with Disposal upto a suitable distance as directed by the Engineer incharge of work
Providing Thermo-Mechanically Treated bars of grade Fe-550D or more Steel reinforcement for R.C.C. work ready to use "cut and bend" rebars of approved make from factory/workshop to construction site i...
Providing and fixing Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel et...
Providing and laying in position Reinforced cement concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixe...
Providing and installing at site of work P.V.C. pipes including cost of pipes and specials and labour, including lowering into trenches, laying true to line, level and perfect linking at joints leak p...
Providing Size Stone masonry with hard stone in foundation & plinth
with Cement mortar 1:6 (1 cement : 6 coarse sand)
Providing and laying in position Reinforced cement concrete for all Substructures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m...
Supplying S&S RCC SPUN / VIBRATED CAST PIPES (REINFORCED)
pipes NP-3 Class conforming to IS:458-1988 with latest amentments using ordinary portland cement, for sanitary works and conveying to work sit...
Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS...
Providing Flush/ Ruled pointing: Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) after raking joints to depth nicely lining, including cost of materials, labour, curing as per s...
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direct...
Fencing with G.I. barbed wire Angle iron post placed at required distance embedded in cement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and...
Grounding of equipment with 50 x 6 mm G.I. Flat and connecting Equipment to the earthmat/ground pit. Each point of earthing with all formation works like bending, twisting, drilling of holes and conne...
Providing Brick work with common burnt clay Non Modular bricks of class designation 3.5 in superstructure above plinth level in all shapes and sizes in Cement mortar 1:6 (1 cement : 6 coarse sand) inc...
Providing, Laying and Fixing GI pipes conforming to IS 1239:1990 with latest amendments complete with GI fittings (excluding the cost of fittings) with cuts and threads wherever necessary, including t...
Providing 20 mm cement plaster of mix :1:6 (1 cement: 6 fine sand) to brick/stone masonary including rounding off corners wherever required smooth rendering, providing and removing scaffolding, includ...
Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade: New work (Two coats applied @ 1.43 ltr/10 m² over and including priming coat of exterior primer a...
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate sections and other sections of approved make conforming...
Providing 12 mm cement plaster with cement mortar 1:4 (1 cement:4 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, inc...
Providing & fixing and laying pressed clay tiles (as per approved pattern 20 mm nominal thickness of approved size) on roofs jointed with cement mortar 1:4 (1 cement: 4 coarse sand) mixed with 2% inte...
Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 m...
Providing skirting, dadooing, rises of steps with colour glazed tiles 6mm thick on 10mm thick cement plaster 1:3 and jointed with white cement slurry over existing rough plaster surface using glazed t...
Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade: One coats on old work as per specifications and as per directions of Engineer in charge & Applying pr...
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete as per sp...
Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :Two coats on new work over an under coat of suitable shade with ordinary paint of appro...
Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joint...
Constructing brick masonry chamber of internal dimension 600x600mm and depth of 600mm (inner dimensions) with modular bricks of CD 75 in cement mortar 1:6, bed concrete 150mm thick with 1:3:6, plaster...
Jelly spreading : Spreading 20/25 mm jelly in station yard including conveing stacking for measurement, sprading in layer of 100 mm over all
Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture of size 595 x 595 mm in true horizontal level, suspended on ...
Supplying of .. TR Invertor type split Air conditioners suitable for operation on A/C supply single phase 50 Hz 230 V with hermetically sealed inverter compressor with air cooled condenser, latest R41...
Installation charges for split type air conditioner with allied works for one indoor and one outdoor unit is to be mounted on suitable Angle Iron support upto 3.0 Ton split/cassette type A/C.
Supply and delivery at site GM (copper alloy) gate valves confirming to Class-I as per IS 778 with latest amendments, 1 No. screwed in bonnet inside screw, rising spring spindle integral seat screwed ...
Supplying and wiring adopting loop system in existing PVC Conduit /casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to...
Supplying and wiring adopting loop system in existing PVC Conduit /casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to...
Supplying and wiring adopting loop system in existing PVC Conduit /casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to...
Supplying heavy gauge PVC Conduit Pipe ….dia .......mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and ...
Supplying heavy gauge PVC Conduit Pipe ….dia .......mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and ...
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 1...
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 4...
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 6...
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 8...
Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capa...
Supplying and fixing of round or oblong type bulk head fitting glass cover
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing m...
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing m...
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing m...
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing m...
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.6A One Way Switch
Supplying of .....feet -PVC Batten with integrated LED tube .... W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI 80. Power Input: 220-240V@ 50/60Hz & Po...
Supplying of recess mounting non integrated type LED down light...W luminaire comprising of pressure decast/ extruded aluminium housing, with spring loaded false ceiling clA, LED of Power/COB with CCT...
Fixing all types and all capacities of fluorescent /false ceiling / spot light / CFL / LED fittings indoor on the wall/ ceiling / rafters / girders using 23/0.0076" twin twisted PVC insulated wires, r...
Supplying 6A flush type socket and 6 A flush type SP switch either surface/flush mounting in existing gang box or in 4mm thick plastic sheet and fixing over a flush mounted wooden box and wiring using...
Providing and fixing Chorinated Poly Venyl Chloride (CPVC) pipes conforming to IS 15778 having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings, thi...
Providing and fixing Chorinated Poly Venyl Chloride (CPVC) pipes conforming to IS 15778 having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings, thi...
Supply and delivery at site 25 mm dia GM (copper alloy) gate valves confirming to Class-I as per IS 778 with latest amendments, 1 No. screwed in bonnet inside screw, rising spring spindle integral sea...
Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS:12823 Grade l Type ll, in panelling fixed in aluminum doors, window...
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of...
Providing and fixing double action hydraulic floor spring of approved brand anufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door wei...
Filling the gap in between aluminium/ stone/ wood frame and adjacent RCC/Brick/ Stone/ wood/ Ceramic/ Gypsum work by providing weather/structural non sag elastomeric PU sealant over backer rod of appr...
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT AN Hally.pdf
Others - Notification to Tender • 0.93 MB
Circulars and Guidelines.zip
Others - Circulars and Guidlines • 4.76 MB
4 techno commercial AN Halli and Honnalli.xlsx
Technical Information / Worksheet • 0.64 MB
5 tender doc sections An Halli and honnalli.docx
Tender Document • 0.48 MB
1 Advisory Note to Bidders.pdf
Instructions to Tenderers • 1.02 MB
Technical Specificaiton 220kv 13 02 2025.zip
Others - Specifications • 9.07 MB
proccedings.pdf
Others - PRE BID MEETING PROCEEDINGS • 0.66 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .