Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.7 LAccepted-AOC D1C 47A JANAK PURI NEW DELHI 110058 | NEW DELHI | DELHI | DELHI | 110058 | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹24.0 L+₹3.7 L (18.4%)Rejected-AOC 6 341 RATAN VIHAR NANGLOI DELHI 110041 | DELHI | WEST DELHI | DELHI | 110041 | L2 | Rejected-AOC L2 Bidder | |
| 3 | L3₹30.5 L+₹10.3 L (50.7%)Rejected-AOC | L3 | Rejected-AOC L3 Bidder |
Tender Value
Refer Docs
EMD Value
₹75,800
Closing Date
22 Dec 2020, 6:00 pmClosed
GE I RND DELHI
MILITARY ENGINEER SERVICES, GARRISON ENGINEER (I) RND, LUCKNOW ROAD, TIMARPUR, DELHI-110054
REPAIR/MAINT OF LT PANELS, LT UG CABLE, ALL TYPES OF DG SET, AMF PANEL AND CERTAIN ALLIED CONNECTED WORKS AT METCALFE HOUSE AND JCB LAB UNDER GE I RND DELHI
2020_MES_390375_1
GE/RND-66/DLI/2020-2021
Open Tender
Civil Works
Item Rate
180 days
DELHI
Class D, Cat b(i)
2 documents required · 2 mandatory
₹500
GE I RND DELHI
₹75,800
Yes
22 Jan 2021
27 Oct 2020
24 Dec 2020
27 Oct 2020
22 Dec 2020
10 Dec 2020
Amount
M&L for painting of LT Panel Indoor/Outdoor type with spray gun with two coats of synthetic enamel heat resistant grey paint area exceeding 6 Sqm but not exceeding 8 Sqm including preparation of old painted surfaces/removing old faded/rust/ cemented material of surface of complete LT panel, complete all as directed.
M&L for structural steel work including cutting, welding etc fabrication of angle iron of size 40x40x5mm thick frame for LT Panel complete including dismantling old unserviceable & fixing new at site all as specified and directed.
M&L for repair to LT panel of any size/make incl cutting, welding of front panel, replacement of back cover and top cover made of CRCA steel sheet of size not less than 3.15mm thick, matching with existing incl hinges and locking devices complete all as specified and directed.
S&F in repair of aluminium bus bar PVC insulated in RED, yellow, Blue & Black colours of rating 400 Amps complete all as specified and directed.
S&F in repair of aluminium bus bar PVC insulated in RED, yellow, Blue & Black colours of rating 800 Amps complete all as specified and directed.
S&F in repair of aluminium bus bar PVC insulated in RED, yellow, Blue & Black colours of rating 1500 Amps complete all as specified and directed.
S&F in repair of bus bar insulator of appropriate size with existing one complete all as directed
M&L for disconnecting the power cable for necessary repair and servcing of ACB 1000 Amps to 2000 Amps including necessary connected parts and testing complete all as specified and directed. Note: Shutdown shall be taken by the contractor before execution of this work.
Supply and fix in repair 3 Pole MCCB, 630 Amp, 50 Hz, 415 V with rupturing capacity 36 KA complete all as specified and directed.
Supply and fix in repair 4 Pole MCCB, 630 Amp, 50 Hz, 415 V with rupturing capacity 36 KA complete all as specified and directed.
S&F in repairs power factor meter digital type for frequency range (45-65 Hz) as per matching to existing one including all accessories and wiring complete all as specified and as directed.
S&F in repair three phase overcurrent earth fault relay MC-61 as per matching to existing one including all accessories and wiring complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 Sqmm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 Sqmm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 400 Sqmm 3.5 core complete all as specified and directed.
Material and Labour for earthing complete with GI earth plate electrode 600mmx600mmx6mm thick burried in ground vertically to a depth not less than 2.25meters below ground level with top edge of the earth plate at a depth not less than 1.5 meter below the ground level, earth plate surrounded 15cm thick layers of common salt and charcoal dust starting from ground below 15 cm of earth plate and up to 15 cm above the same. GI plate connected with galvanised iron strip of 25x4 mm by means of Copper nuts, bolts and washers. Strip laid in 40mm dia light grade GI pipe as protection from top of the plate up to test point (cost of protection pipe up to 7.5 meters from earth electrode will be included in the rates quoted by the contractor) with following complete all as specified and shown in electrical plate No 3 of SSR Part-I & testing on completion :- (a) GI strip of size 25mm x 4mm. (b) Watering pipe GI light grade 20mm dia from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit. (GI Funnel should properly tightned on GI watering pipe and embeded in PCC floor of earth pit with open top suitable for watering of earth pits) (c) Excavation & earthwork in any type of soil PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 plaster including RCC pit cover 50mm thick 1:2:4 type B1 reinforced with 8mm dia mild steel bar 75mm centre to centre with 2 Nos MS handles of 12mm dia suitable for carrying of pit cover.
M&L for PCC 1:3:6 type C-1 using 20 mm graded stone aggregates) for repairing of LT pole foundation etc including filling in road cuts/ hard standing etc all as specified and as directed.
M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or any other indicated situation for loop earthing etc as required 25x4 mm galvanised iron strip complete all as specified and directed.
Supply and fixing in replacement of APFC relay for 10 KVAR, 10 Stages complete all as specified and directed.
Supply & fix in repleacement of LED type Indicating lamp type of voltage AC/DC set of RYB, as per matching to existing.
Supply and Fix in replacement of Capacitor Bank MPP-H, 05 KVAR capacity rated 440 Volts AC,3ø,50HZ ,Delta connection, Round type complete all as specified and directed.
Supply and Fix in replacement of Capacitor Bank MPP-H, 10 KVAR capacity rated 440 Volts AC,3ø,50HZ ,Delta connection, Round type complete all as specified and directed.
Supply and fixing in replacement of capacitor duty, contactor MO C5 complete all as specified and directed.
Supply and fixing in replacement of capacitor duty, contactor MO C 12.5 complete all as specified and directed.
Supply and fixing in replacement of capacitor duty, contactor MO C 25 complete all as specified and directed.
Supply and fixing in replacement of capacitor duty, contactor MO C 50 complete all as specified and directed.
Supply, installing, testing and commissioning factory made panel approx size 1500mm x 750 mm x 1700 mm and tested CPRI approved LT Panel indoor type, double door, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system, IP-54 having bus bar chamber with insulated electrolytic Aluminium bus bars TPN of capacity 1000 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, and inner & outer sheet made out of 3.15 mm thick CRCA mild steel sheet and mild steel & Mounting Channel frame work made out of MS angle 75X40 x 6 mm duly coated with zinc metal coating, front opening type for installation of separate cable alleys, busbar chamber and switchgear compartments. Provision in cable alleys to be kept for bottom cable entry for incoming and outgoing cables. A clear space of 200 mm to be kept from floor level for switchgear compartment. Extended busbar links/ terminals to be provided for heat dissipation. Air ventilation breathers to be provided for heat dissipation. Suitable sized knock-out holes for cables, gland shall be provided as per respective schematic drg of the following equipments/ instruments. Each compartment shall be numbered/ letterd as per the approved drg. Affixing MV Danger plate as suitable intervals/ location, panel board compartment size should be suitable to accomodate the switchgear and other accessories as per IE rules, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLSH cable of adequate size but not less than 2.5 sqmm complete. All steel metal works including frame shall be painted with anticorrosive coating with seven tank process and finally epoxy based make as per shade approved by Engineer-in- charge, after taking down the Old rusted panel from it's position after taking proper shutdown all as specified and as directed and comprises with the follwing :-
Supply, installing, testing and commissioning factory made panel approx size 1500mm x 750 mm x 1500 mm and tested CPRI approved LT Panel indoor type, double door, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system, IP-54 having bus bar chamber with insulated electrolytic Aluminium bus bars TPN of capacity 800 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, and inner & outer sheet made out of 3.15 mm thick CRCA mild steel sheet and mild steel & Mounting Channel frame work made out of MS angle 75X40 x 6 mm duly coated with zinc metal coating, front opening type for installation of separate cable alleys, busbar chamber and switchgear compartments. Provision in cable alleys to be kept for bottom cable entry for incoming and outgoing cables. A clear space of 200 mm to be kept from floor level for switchgear compartment. Extended busbar links/ terminals to be provided for heat dissipation. Air ventilation breathers to be provided for heat dissipation. Suitable sized knock-out holes for cables, gland shall be provided as per respective schematic drg of the following equipments/ instruments. Each compartment shall be numbered/ letterd as per the approved drg. Affixing MV Danger plate as suitable intervals/ location, panel board compartment size should be suitable to accomodate the switchgear and other accessories as per IE rules, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLSH cable of adequate size but not less than 2.5 sqmm complete. All steel metal works including frame shall be painted with anticorrosive coating with seven tank process and finally epoxy based make as per shade approved by Engineer-in- charge, after taking down the Old rusted panel from it's position after taking proper shutdown all as specified and as directed and comprises with the follwing :-
Excavation in tranches in soft/loose soil not exceeding 1.5m depth not exceeding 1.5m in width over energised LT cables for carrying out brick work for preparation of cable duct including for taking out and relaying of LT Cables
All same as per item srl No 31.00 above but hard/dense soil
Returning filling in including spreading levelling watering and well ramming in layers not exceeding 25cm thick as in soft/loose soil complete all as specified and as directed.
Removing surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level and not exceeding 1.5 mtr above the starting point complete all as specified and as directed.
Supply & laying dry fine sand for cushioning of underground cable laid in trenches/duct complete all as specified and as directed
M&L for sub class 'B' burnt brick flat across the cable, for protection of cable laid in trenches complete all as specified and directed
Labour only for relaying of serviceable sub class 'B' burnt brick flate across the cable, for protection of cable laid in trenches complete all as specified and directed. Note: Old serviceable bricks obtained shall be reused.
Supply and laying GI pipe mideum grade in replecement of 150mm dia laid in trenches for protection of UG cable complete all as specified and directed
Supply and laying GI pipe mideum grade in replecement of 100mm dia laid in trenches for protection of UG cable complete all as specified and directed.
Supply and laying GI pipe mideum grade in replecement of 50mm dia laid in trenches for protection of UG cable complete all as specified and directed.
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
M&L for B check general servicing by authorised rep of manufacturer of DG set of capacity 20 to 30 KVA, replacement of oil filter, fuel filter, air filter, by pass filter cleaning of radiator with chemical after draining out engine/ lubrication oil, coolant flushing and cleaning of oil chamber after opening of tappet cover/ top cover tappet clearence setting with injector timing adjustment re-fixing of tappet/ top cover including replacement of tappet cover packing set, bonding and leak proof solution, oil pan/ chamber gasket at the servicing and other work comes under B Check service as mentioned in B Check by the manufacturer all as speciied and as directed. Note-Engine oil & Coolant will be paid separately under respective item.
All as per item No 52.00 above but of capacity 100 to 180 KVA
All as per item No 52.00 above but of capacity 200 to 300 KVA
All as per item No 52.00 above but of capacity 750 KVA
S&F in repair of self starter 12 V including rewinding of armature with super enamaled copper conductor wire of superier quality as per existing gauge, turn and pattern and replacement of bendex drive, carbon brush including services suitable for DG set 20 KVA to 30 KVA complete all as specified and directed.
S&F in repair of self starter 24 V including rewinding of armature with super enamaled copper conductor wire of superier quality as per existing gauge, turn and pattern and replacement of bendex drive, carbon brush including services suitable for DG set 125KVA to 180 KVA complete all as specified and directed.
All as per item ser No 57.00 above but of capacity 200 to 300 KVA
All as per item ser No 57.00 above but of capacity 750 KVA
Supply & Fixing in repair of automatic battery charger with auto cut OFF suitable for charging of 2X12V 180AH batteries complete with all required necessary wiring complete all as specified and directed.
M&L for repair of wiring complete to AMF panel for capacity upto 300 KVA of DG set including interlock system of AMF panel with existing size of copper wiring including proper connection and testing complete as directed.
All as per item Ser No 61.00 above but of capacity 750 KVA
Supply and Fix in repair of self starter 24 volts suitable for upto 125 KVA DG sets complete as directed.
Supply and Fix in repair of self starter 24 volts suitable for upto 180 KVA DG sets complete as directed.
Supply and Fix in repair of self starter 24 volts suitable for upto 200 KVA DG sets complete as directed.
Supply and Fix in repair of self starter 24 volts suitable for upto 250/ 300 KVA DG sets complete as directed.
Supply and Fix in repair of self starter 24 volts suitable for upto 750 KVA DG sets complete as directed.
Supply & Fix in repair of power contactor 400 Amps capacity suitable for AMF panel of DG sets a per matching to existing complete as directed.
Supply & Fix in repair of power contactor 200 Amps MCX 45. Three phase & four pole capacity suitable for AMF panel of DG sets a per matching to existing complete as directed.
Supply and Fix in repair of battery brass terminals heavy duty suitable for 12V 180 AH battery with minimum 3 RM Battery Lead of multistrand copper Cable single core all as directed by engr-in-charge.
Supply and Fix in repair of relay 24 V 8 pin type as per matching to existing complete as directed.
Supply and Fix in repair of engine starting relay suitable for DG set of capacity 20 KVA to 30 KVA as per matching to existing relay complete all as specified as directed.
Supply and Fix in repair of engine starting relay suitable for DG set of capacity 100 KVA to 180 KVA as per matching to existing relay complete all as specified as directed.
Supply and Fix in repair of engine starting relay suitable for DG set of capacity 200 to 300 KVA as per matching to existing relay complete all as specified as directed.
Supply and Fix in repair of engine starting relay suitable for DG set of capacity 750 KVA as per matching to existing relay complete all as specified as directed.
Supply and Fix in repair of Electronic timer suitable for AMF panel of DG set as per matching to exisitng, 230 V AC 50 Hz timer complete all as specified as directed.
Supply & Fix in repair of Voltmeter analog type for voltage range of (0-24V) as per matching to existing complete with all accessories and wiring complete all as specified as directed.
Supply & Fix in repair of Voltmeter analog type for voltage range of (0-500V) complete with all accessories and wiring complete all as specified as directed.
Supply & Fix in repair of Ammeter analog type for current range of (0-24Amps) as per matching to existing complete with all accessories and wiring complete all as specified as directed.
Supply & Fix in replcement of Ammeter analog type for current range of (0-1000Amps) as per matching to existing complete with all accessories and wiring complete all as specified as directed.
Supply & Fix in repair of power contactor ML 4 suitable for AMF panel of DG sets a per matching to existing contactor complete all as specified as directed.
Supply & Fix in repair of power contactor ML 3 suitable for AMF panel of DG sets a per matching to existing contactor complete all as specified as directed.
Supply and Fix in repair of under voltage relay suitable for DG set upto 300KVA capacity complete all as specified as directed.
Supply and Fix in repair of complete wiring with single core multistranded copper cable with flexible conduit for DG set of various capacities complete all as specified as directed.
Supply only Coolant for DG Set (5 litres each pack)
Supply only wet dry Cotton Cloth for cleaning of DG Set.
Supply, fixing and testing Electronic Governor Controller for capacity 180 KVA DG Set including taking down old Governor Controller complete all as specified as directed.
Supply, fixing and testing Electronic Governor Controller for capacity 250KVA DG Set including taking down old Governor Controller complete all as specified as directed.
S&F in repair actuator for 300 KVA DG Set complete all as specified as directed.
Opening the DG set of 300 KVA , repair to any leakage in radiator, greasing of all movable parts & equipments and replacing all flexible/steel wire mesh type hose pipes including fuel pipe line , belts & Bearings including re-assembling the complete Parts and Testing complete all as specified and as directed. Note : Spare Parts required for replacement shall be measured & paid seperately.
S&F Piston ring and liner for 300 KVA DG Set as per existing make & OEM complete.
Supply only Head valve, Head Guide, Head sheet & Head seal for 300 KVA DG Set as per existing make & OEM complete.
Supply only Injector sleeves & Head gasket for 300 KVA DG Set as per existing make & OEM complete.
Supply only Packing Kit for 300 KVA DG Set as per existing make & OEM complete.
S&F for repair of Head and fuel injector assembly complete for 300 KVA DG Set.
S&F in repair of Turbo assembly complete for 300 KVA DG Set.
Opening the DG set of 250 KVA , repair to any leakage in radiator, greasing of all movable parts & equipments and replacing all flexible/steel wire mesh type hose pipes including fuel pipe line , belts & Bearings including re-assembling the complete Parts and Testing complete all as specified and as directed. Note : Spare Parts required for replacement shall be measured & paid seperately.
S&F Piston ring and liner for 250 KVA DG Set as per existing make & OEM complete.
Supply only Head valve, Head Guide, Head sheet & Head seal for 250KVA DG Set as per existing make & OEM complete.
Supply only Injector sleeves & Head gasket for 250 KVA DG Set as per existing make & OEM complete.
Supply only Packing Kit for 250 KVA DG Set as per existing make & OEM complete.
M&L for repair of Head and fuel injector assembly complete for 250 KVA DG Set.
M& L for repair of Turbo assembly complete for 250 KVA DG Set.
Opening the DG set of 180 KVA , repair to any leakage in radiator, greasing of all movable parts & equipments and replacing all flexible/steel wire mesh type hose pipes including fuel pipe line, belts & Bearings including re-assembling the complete Parts and Testing complete all as specified and as directed.
S&F Piston ring and liner for 180 KVA DG Set as per existing make & OEM complete.
Supply only Head valve, Head Guide, Head sheet & Head seal for 180 KVA DG Set as per existing make & OEM complete.
Supply only Injector sleeves & Head gasket for 180 KVA DG Set as per existing make & OEM complete.
Supply only Packing Kit for 180 KVA DG Set as per existing make & OEM complete.
M&L for repair of Head and fuel injector assembly complete for 180 KVA DG Set.
M& L for repair of Turbo assembly complete for 180 KVA DG Set.
Supply and Fix in repair Fan belt of existing size for DG Set of capacity 20 to 30 KVA
Supply and Fix in repair Fan belt of existing size for DG Set of capacity 100 to 180 KVA
Supply and Fix in repair Fan belt of existing size for DG Set of capacity 200 to 300 KVA
Supply and Fix in repair Fan belt of existing size for DG Set of capacity 750 KVA
Supply and Cladding with glass/rock wool and aluminium sheets of exhaust manifold for DG sets 20 to 30 KVA including removing of existing asbestos rope or any other type of insulation.
All as per Ser item No 115.00 above but of capacity 180 KVA
S&F in repair fly wheel ring of DG Set of capacity 125 KVA.
S&F in repair fly wheel ring of DG Set of capacity 180 KVA.
S&F in repair fly wheel ring of DG Set of capacity 200 KVA.
S&F in repair fly wheel ring of DG Set of capacity 250/300KVA.
S&F in repair fly wheel ring of DG Set of capacity 750 KVA.
Draining out the diesel tank, cleaning/washing out the sludge and re-filling with diesel for the DG Set of capacity 20 to 30 KVA.
Draining out the diesel tank, cleaning/washing out the sludge and re-filling with diesel for the DG Set of capacity 100 to 180 KVA.
Draining out the diesel tank, cleaning/washing out the sludge and re-filling with diesel for the DG Set of capacity 200 to 300 KVA.
Draining out the diesel tank, cleaning/washing out the sludge and re-filling with diesel for the DG Set of capacity 750KVA.
Repair to radiator of 20 to 30 KVA DG set ,arresting leakage if any by welding/brazing and refixing the same for (Necessary coolant and distrilled water required will be measured and paid seperately)
All as per Ser item No 126.00 above but of capacity 180 KVA
All as per Ser item No 126.00 above but of capacity 250 KVA &300 KVA
All as per Ser item No 126.00 above but of capacity 750KVA
Removing old U/S insulating material asbestos rope and fixing of new of existing size and shape complete all as directed
M&L for Spray painting of diesel generating set of capacity 20 to 30 KVA. with one coat of synthetic enamel paint , body colour shall be apple green,black for foundation base frame, red for all guards for all as directed.
M&L for Spray painting of diesel generating set of capacity 100 KVA to 180KVA with accostic enclosure one coat of synthetic enamel paint, body colour shall be apple green,black for foundation base frame, red for all guards for all as directed.
M&L for Spray painting of diesel generating set of capacity 200KVA to 300 KVA with accostic enclosure one coat of synthetic enamel paint, body colour shall be apple green,black for foundation base frame, red for all guards for all as directed.
M&L for Spray painting of diesel generating set of capacity 750KVA with accostic enclosure one coat of synthetic enamel paint, body colour shall be apple green,black for foundation base frame, red for all guards for all as directed.
Supply and fix in repair AVR system for DG set of capacity 125 KVA complete as directed.
Supply and fix in repair AVR system for DG set of capacity 180 KVA complete as directed.
Supply and fix in repair AVR system for DG set of capacity 200 KVA to300 KVA complete as directed.
Supply and fix in repair AVR system for DG set of capacity 750KVA complete as directed.
S&F in repair Retro Reflective hIgh intensity prisonatic type glossy sign board made of stainless steel for DG Set where installed sizes 1.5X1.0 Mtr (LxW) as per sample the `Military Engineering Services, MES logo and Deisel Generating Set details to be written on the board including fixing stainless steel tubular poles 50mm dia-02 Nos 4 mtr height from ground level and grouting into 1m depth below ground & necessary excavation and earth work & PCC 1:2:4 type B-1 complete all as specified and directed.
S&F in repair turbo chargers repairs kit suitable for DG set 180KVA.
S&F in repair of 3 Pole MCCB, 250 Amp, 50 Hz, 415 V with rupturing capacity 36 KA, fixed type complete as directed.
S&F in repair of 3 Pole MCCB, 400 Amp, 50 Hz, 415 V with rupturing capacity 36 KA, fixed type complete as directed.
S&F in repair of 3 Pole MCCB, 630 Amp, 50 Hz, 415 V with rupturing capacity 50 KA, fixed type complete as directed.
S&F in repair of 4 Pole MCCB, 250 Amp, 50 Hz, 415 V with rupturing capacity 36 KA, fixed type complete as directed.
S&F in repair of 4 Pole MCCB, 400 Amp, 50 Hz, 415 V with rupturing capacity 36 KA, fixed type complete as directed.
S&F in repair of 4 Pole MCCB, 630 Amp, 50 Hz, 415 V with rupturing capacity 50 KA, fixed type complete as directed.
Supply only Engine oil 20W/40 for DG Set complete as directed.
Supply and laying in repair XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured electric power cable (Heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 150 Sqmm 3.5 core complete all as specified and directed.
Supply and laying in repair XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured electric power cable(Heavy duty) ewith aluminium conductor, 1100 volts, grade cross sectional area 70 Sqmm 3.5 core complete all as specified and directed.
-BLANK-
M/s Wazer Enterprises
Surjit and Sons
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .