Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹6.6 Cr
Closing Date
1 Dec 2021, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Supply, Installation, Testing and Commissioning of HVAC, BMS and Fire Fighting work relating to Construction of World Class Library with Conference Hall and Modern Auditorium at Angul District, Odisha.
NBCC/PMGSY-ZONE/ODISHA/Angul/2021/53
NBCC/PMGSY-ZONE/ODISHA/Angul/2021/53
Open Tender-Domestic
Electronics Equipment
Anugul, Odisha
₹11,800
Exempted
1 Dec 2021
17 Nov 2021
1 Dec 2021
1 Dec 2021
10 Dec 2021
Name of Work: Supply, Installation, Testing and Commissioning of HVAC, BMS and Fire Fighting work relating to
Construction of World Class Library with Conference hall and Modern Auditorium at Angul District, Odisha.
S.No Description of work unit Amount
A HVAC WORKS Rs. 44686253.00
B BMS WORKS Rs. 15193120.00
C FIRE FIGHTING WORK Rs. 6472887.00
Total (A+B+C) Rs. 66352260.00
RAKESH Digitally signed by RAKESH
NARAYAN SINHA Date: 2021.11.17 17:20:38
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
1.0 High Side Works
Note 1 : Higher value COP to be considered for the VRV Equipments.
Note 2 : Out Door units should function properly at peak temperature say 48 deg C.
Same to be considered under selection.
1.10 VRF Air Conditioning Equipments :
Supply, Installation, testing and commissioning of VRV/VRF air-conditioning system
comprising of Modular type high efficiency DC Scroll / Twin Rotary Multiple Compressor
with DC inverter, High efficiency heat transfer Cooling Coil suitable for Environment
friendly HFC R410A / R407C refrigerant & 4 way Heat exchanger foe better heat transfer,
Air cooled propeller type condenser fan with DC motor drive, interconnecting piping,
insulation etc., Micro-processor control panel suitable for automatic operation, High
speed calculation inverter control, active oil control mechanism, accumulator
incorporating all safety functions as per technical specifications & other points listed
below. Units above shall have a mimumum of 2 compressors. And each compressor
shall run independently even though there is a failure in the other compressor.
1.1.1 Outdoor Unit(ODU) Capacities area as follows :
2.00 ODU FOR TFA UNITS
2.1 TFA OUT DOOR UNIT-02 - 20 HP - SERVING SECOND FLOOR AREAS. Nos 1 586268.18 586268.18
3.0 VRV/VRF Indoor Units
Indoor Unit(IDU): Cooling Only :
All the units should be supplied with Cordless remote control. The following Indoor unit
capacities are required for each type of Room
3.1 4 way Cassette Units for the following capacities :
3.2 Ductable vrv units
c 11 TR (AUDITORIUM) Nos 14 218466.86 3058536.04
4.0 Supply of Treated fresh air UNIT:
4.1 Treated Fresh air units with VRV condenser units
Supply, Installation, testing and commissioning of Treated Fresh air unit with all sections
4.11 like fan section , coil section , filter section and mixing box section og below said
5.00 Copper piping
Supply , Installation, Testing & Commissioning & Handing over of the Copper piping for
the VRF works :
Supply ,Installation of copper piping with necessay fittings imported fittings, Y-joints and
headers etc.(This includes the pressure testing and refrigerant charge ).
SITC of Copper tubes 99.90% pure copper and Phosphorous 0.015 to 0.04% confirming
to ASTM B280/ JIS H3300:1997/ EN12735-1 or equivalent, manufactured using High
Residual Phosphorous De-oxidised Copper Alloy C1220. Tubes shall be horizontally
marked with Brand, Standard, Dimensions printed on the Tube with necessary factory
test certificates .FITTINGS - Jointing of Copper tubes shall be with Mechanical type
Crimp joint UL Certified Copper Fittings comprising Elbow, TEE, Couplar, Ref and Flare
Joints etc, capable of withstanding 48 bars (700 psig). working pressure and Fittings O
5.3 Ring suitable to specified refrigerants, fittings shall carry 10 year product warranty.
Fittings shall be supplied in plastic bag clearly marked with size, type, and application
with a zip lock facility to keep fittings clean.Pipes shall be insulated with 13 mm thick
tubular nitrile rubber insulation with weather protection for outdoor installation (Refer
Drawings issued). The quoted price shall include necessary power, control cabling.
Providing Electrical Feeder at distance of 3 meter near the unit with isolator will be in
electrical scope. The refrigerant piping runs on wall floor shall be laid in perforated type
cable trays with cover.(One run per Unit. Each run comprises Liquid and Gas Line).
5.4 Gas line with 19 mm thick insulation + Liquid line with 13 mm thick insulation
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
5.5 Imported fittings,Y-Joints Set 70 6236.60 436561.65
6.00 HDPE PVC pipe of following sizes for drain with necessary supports and fittings.
9.00 Sheet Metal Ducting
Sheet Metal Work with Ductmate Flanges for all sizes of the duct. Fabrication as per
SMACNA Standards
Galvanizing shall be Class VII – light coating of zinc, nominal 120 gm / sqm surface area
and Lock Forming Quality prime material along with mill test certificates. In addition, if
deemed necessary, samples of raw material, selected at random by owner’s site
representative shall be subject to approval and tested for thickness and zinc coating at
contractor’s expense.
All duct construction and installation shall be in accordance with SMACNA standards. In
addition ducts shall be factory fabricated utilizing the following machines to provide the
requisite quality of ducts.
All ducts shall be fabricated and installed in workmanlike manner, conforming to relevant
The Duct shall be supported with Hi-tech Supports at regular intervals as mentioned in
the technical specifications. The sheet metal ducting running in AHU Rooms should be
supported with special acoustic hangers to avoid transmission of vibration from AHU
Room to adjacent sensitive areas.
10.00 4 / 2 Way Square Diffusers
Powder coated, extruded aluminium, removable center core type, supply / return air
diffusers without volume control dampers of aluminium construction of the following neck
sizes. The diffuser shall be mounted in the GI box (not in scope), with inlet conn
Supply and Installation of Ra and Sa diffuser
all are of 600 X 600 mm Outer to Outer size
Circular Supply air Diffusers without vcd to carry out min 300 to 600 CFM ( Approx.
350mm dia ) with collar dampers
b Spill air Boxes to suit the above said circular diffusers Nos 250 769.95 192487.50
c Circular Return air diffuser Nos 22 1625.43 35759.46
13.00 Insulation (Thermal Insulation)
Supply & installation of Thermal insulation of the sheet metal duct with closed cell
elastomeric insulation of Class 'O' material with density of 40 - 55 kg/cum as per the
13.1 thickness mentioned below, with fire retardant adhesive and joints sealed with 3mm thick,
50mm wide nitrile rubber self adhesive tape all in accordance with technical
specifications.
Supply, erection of Duct liner (Acoustic Insulation) of specified thickness of Open cell
Elastromeric Rubber Insulation with antimicrobial protection manufactured as per ASTM
13.2 E 84 test & which should also meet NFPA 90A supplementary materials for air
distribution system which should not absorbs less 0.2% water by volume . Adhesive shall
be of low VOC preferably Fevicol ac duct king optima / equivalent.
13.3 Supply, erection of UNDERDECK INSULATION (EPS TYPE)
14.00 AIR TERMINAL DEVICES
Volume control Damper
a Supply, installation, testing and commissioning of multiblade box type volume control
damper of 16G Aluminum frame and 16G opposed type aerofoil blades for ducts to be
provided with suitable links, levers and quadrants for manual control of volume of air flow
and for proper balancing of the air distribution system , in accordance with technical
specifications, for manual control of volume of air flow and for proper balancing of the air
distribution system .
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
14.1 Back Draft damper (Size: 200x150mm) Nos 2 14543.50 29087.00
Linear Square grills in min 16 G extruded Aluminum Powder Coated construction with
0/15/30 deg deflection with end flanges, in accordance with technical Sqm 125 16254.50 2031812.50
14.2 specifications.(800rmt cont. grille) 150 mm wide. with collar dampers
square / rectangular grille in min 16 G extruded Aluminum Powder Coated construction
with 0/15/30 deg deflection with end flanges, in accordance with technical
specifications.(for double ht. entrance and auditorium block including the smoke
14.3 extraction system grilles)
Heavy duct flexible double layer fire retardant canvas connection shall be provided at the
outlet of AHU/CSU/ TFA Fan and also for expansion joints. Quoted price should be
inclusive of all flanges, joints, supports etc ( Cross sectional area to be considered for
14.4 measurement)
Disc Valves in powder coated extruded Aluminum construction for Toilet Exhaust and
14.5 TFA discharge system suitable for the requried cfm along with VCD (150 DIA )
Fire/Smoke Damper with motorized actuator including control panel and sensor made out
of min 16 G Galvanized steel frame and with opposed blades of min 16 G galvanized Sqm 5 29087.00 145435.00
steel sheet as per the layout with UL 555 Certification for minimum 90 minutes rating.
14.7 supply and installation of jet diffuser for the auditorium and dobule ht. entrance area Nos 44 6844.00 301136.00
control cable for the above said casseete units and ductable units between IDU to ODU
15.5 with conduits and necessary fittings & accessories.(3 core / 2.5 sqmm/6 sqmm/ suitable Rmt 3000 188.21 564630.00
15.6 cable trays
a 300mm cable tray Rmt 150 1112.15 166822.50
b 150mm cable tray Rmt 150 855.50 128325.00
15.7 REFRIGERANT CHARGING KG 400 1197.70 479080.00
Active Networking
1 L3 Giga cum core Switch
Supply, fitting, fixing, connecting and testing of switch with 24 x 10/100/1000T ports and
4 x 100/1000X 10G SFP ports, Switching Capacity 100Gbps and Forwarding Rate 300
Mpps, operaating temperature 0°C to 50°C, Switch should support link reccovery within
50ms for Ring architecture, SDN or similar kind of technolgy should support, Warranty 5
year from Day 1 .
The above L3 Core Data Switch consists of the following:-
1. Power cord India, right angle.
2. Both side Cable connector.
3. 1 year free service pack.
Interface-24 x 10/100/1000T ports and 4 x 100/1000X10G SFP ports
Switching Capacity/Forwarding Rate :- 100Gbps/300Mpps
Performance:- Up to 16K MAC addresses, 256MB DDR SDRAM
Management:- Console port, GUI, Telnet, SSH,SNMPv1,2 and 3, powerful centralized
management and zero-touch device installation and recovery like SDN,
Security:- Console port, GUI, Telnet, SSH,SNMPv1,2 and 3, powerful centralized
management and zero-touch device installation and recovery like SDN,
Routing:- IPv4 static routing and RIP.
Fail-over:- Switch capable of recovery within 50ms in a ring for application high
IPv6:- Device management over IPv6 networks with SNMPv6, Telnetv6, SSHv6 and
Diagnostic:- Optical Digital Diagnostics Monitoring,Automatic link flap detection and port
shutdown,Port and VLAN mirroring (RSPAN)
Standard Protocol:- IEEE 802.1Q,IEEE 802.1w,IEEE 802.1s,IEEE 802.1p,IEEE
802.1AB,IEEE 802.1AX,IEEE 802.3ad
Operating Temparature:- 0°C to 50°C
Certification:- EN,UL and RoHS
Warranty:- 5 Years.
Cost of L3 Giga cum Core Switch Nos 1 3,80,126.91 3,80,126.91
2 L2 PoE Access Switch - -
Supply, fitting, fixing, connecting and testing of switch with 24 x 10/100/1000T PoE ports
and 4 x 100/1000X SFP ports, Switching Capacity 56Gbps and Forwarding Rate
41.7Mpps, Switch should support PoE and PoE+ with 370W minimum power budget,
operaating temperature 0°C to 50°C, Switch should support link reccovery within 50ms
for Ring architecture, SDN or similar kind of technolgy should support, Warranty 5 year
from Day 1 . - -
The above L2 Managed Data Switch consists of the following:- - -
1. Power cord India, right angle. - -
2. Both side Cable connector. - -
3. 1 year free service pack. - -
Interface- 24 x 10/100/1000T ports and 4 x 100/1000X SFP ports - -
Switching Capacity/Forwarding Rate :- 56Gbps/41.7Mpps - -
Performance:- Up to 16K MAC addresses, 256MB DDR SDRAM - -
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
Management:- Console port, GUI, Telnet, SSH,SNMPv1,2 and 3, powerful centralized
management and zero-touch device installation and recovery like SDN, - -
Security:- Console port, GUI, Telnet, SSH,SNMPv1,2 and 3, powerful centralized
management and zero-touch device installation and recovery like SDN, - -
Routing:- IPv4 static routing and RIP. - -
Fail-over:- Switch capable of recovery within 50ms in a ring for application high
availability - -
IPv6:- Device management over IPv6 networks with SNMPv6, Telnetv6, SSHv6 and
Diagnostic:- Optical Digital Diagnostics Monitoring,Automatic link flap detection and port
shutdown,Port and VLAN mirroring (RSPAN) - -
Standard Protocol:- IEEE 802.1Q,IEEE 802.1w,IEEE 802.1s,IEEE 802.1p,IEEE
802.1AB,IEEE 802.1AX,IEEE 802.3ad - -
Operating Temparature:- 0°C to 50°C - -
Certification:- EN,UL and RoHS - -
Warranty:- 5 Years. - -
Cost of L2 PoE Access Switch Nos 12 1,64,684.16 19,76,209.96
3 Indoor access Points - -
The IEEE 802.11ac Wave 6 Indoor Access Point should have in-built virual controller for
controlling minimum 50 similar make AP as well as support for cloud based controller.
Interfaces: 1 x 10/100/1000BASE-T autosensing (RJ-45), Power over Ethernet (PoE).
Management console port (RJ-45) - -
Indicators: Status LED indicates boot loader status, association status, operating status,
boot loader warnings, boot loader errors - -
Mounting: mounting bracket should be supplied with AP - -
Physical Security: Torx security screw, included with the access point - -
Environmental:● Operating
◦ Temperature: 32° to 104°F (0° to 40°C)
◦ Humidity: 10% to 90% (noncondensing)
◦ Max. altitude: 9843 ft (3000 m) @ 40°C
● Nonoperating (storage and transportation)
◦ Temperature: -22° to 158°F (-30° to 70°C)
◦ Humidity: 10% to 90% (noncondensing)
◦ Max. altitude: 15,000 ft (4500 m) @ 25°C - -
AP System Capacity:● 1 GB DRAM
● 710 MHz quad core - -
Compilance:● Safety:
● Radio approvals:
◦ FCC Part 15.247, 15.407 ◦ RSS-247 (Canada) ◦ EN 300.328, EN 301.893 (Europe)
◦ ARIB-STD 66 (Japan) ◦ ARIB-STD T71 (Japan) ◦ EMI and susceptibility (Class B)
◦ FCC Part 15.107 and 15.109 ◦ ICES-003 (Canada) ◦ VCCI (Japan)
◦ EN 301.489-1 and -17 (Europe) ◦ EN 50385
● IEEE standards:
◦ 802.11i, WPA3, WPA2, WPA ◦ 802.1X ◦ AES
● Extensible Authentication Protocol (EAP) types:
◦ EAP-Transport Layer Security (TLS)
◦ EAP-Tunneled TLS (TTLS) or Microsoft Challenge Handshake Authentication Protocol
Version 2 (MSCHAPv2)
◦ Protected EAP (PEAP) v0 or EAP-MSCHAPv2
◦ EAP-Flexible Authentication via Secure Tunneling (FAST)
◦ PEAP v1 or EAP-Generic Token Card (GTC)
◦ EAP-Subscriber Identity Module (SIM) - -
Cost of Wave 6 based access points Nos 30 61,242.77 18,37,283.01
4 Router / UTM - -
Supply, fitting, fixing and testing of UTM/Router with LAN: 2 x 1000X SFP / 2 x
10/100/1000T RJ-45 combo, WAN: 2 x 1000X SFP / 2 x 10/100/1000T RJ-45 combo ,
HA: 2 x 10/100/1000T RJ-45, Should support URL Filtering, DoS and DDoS attack
detection and protection, Antivirus, Malware protection, Static, Dynamic (BGP4, OSPF,
RIPv1/v2), source-based routing, policy-based routing and IGMPv1/v2/v3. Warranty 5
year from Day 1. - -
The above router consists of the following:- - -
Cisco 2901 AC Power Supply (PWR-2901-AC) - -
AC Power Cord (India, South Africa), C13, BS 546, 1.8m - -
Blank faceplate for HWIC slot on Cisco ISR - -
Cisco Config Pro Express on Router Flash - -
512MB DRAM for Cisco 2901-2921 ISR (Default) - -
256MB Compact Flash for Cisco 1900, 2900, 3900 ISR - -
IP Base License for Cisco 2901-2951 - -
Cisco 2901-2921 IOS UNIVERSAL - -
2-Port Serial WAN Interface Card - -
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
Security License for Cisco 2901-2951 - -
1 year free service pack - -
INTERFACE:- LAN: 2 x 1000X SFP / 2 x 10/100/1000T RJ-45 combo, WAN: 2 x 1000X
Processor and memory:- 800MHz dual-core, 1GB (RAM), 4GB (Flash) - -
Firewall / UTM (Unified Threat Manager) :- Deep Packet Inspection, Bandwidth limiting
control for applications, Bridging between LAN and WAN interfaces, Data leakage
prevention, URL Filtering, DoS and DDoS attack detection and protection, Antivirus,
Malware protection, (Intrusion Detection System), IPS (Inclusion Prevention System)
antivirous, anti spywire with 3 yrs subscription. This equipment will also protect & prevent
outsider or visitors who are not assined in the existing Network i,e Office Network System
can not availed by any otsiders or they can not curropt the Network System. ( For Active
& Passive mode) - -
Routing and Multicasting:- Static, Dynamic (BGP4, OSPF, RIPv1/v2), source-based
routing, policy-based routing and IGMPv1/v2/v3 - -
NAT:- Static, IPsec traversal, Dynamic NAPT. - -
High availability:- VRRP, VRRPv3 - -
Management & authentication:- Web-based GUI,Industry-standard CLI, SNMPv2 & v3,
RADIUS, TACACS+, internal user database, web authentication - -
Warranty:- 5 Years on Hardware. - -
Cost of Router / UTM Nos 1 7,30,597.94 7,30,597.94
For Board Band system input may be connected from any broad band service provider for
LAN networking system. Broad Band service along with LICENCE has to be provided by
the user at the time of final testing and commissioning. Any software required shall be
provided by the end user. - -
Provision of Managed Lease Line (MLLN) from BSNL/RILTAIL along with all required
accessories, components, OFC Cable liencense for provision of MLLN including
connection , commissioning and testing shall be in the scope of end user. - -
Provision of all type of Equipments cost (Cisco Router) including connection ,
commissioning and testing shall be also in the scope of end user. - -
Along with the assigned scope of work for Data networking following things has to be
considered by the contractor:- - -
Installation, commissioning and testing for Passive Components. - -
Installation, commissioning, testing and submission of Active Components Activation
Report with Networking Live/Active Installation along with submission of SLD.
Contractor will take full responsibility of Project supervision, Monitoring, testing,
commissioning and submission of Penta Scanning Report for the given Nodes as
mentioned in the BOQ for Data Networking. - -
Data networking- Data out let to wall mounted Rack shall be with CAT-6 Cable and Rack
to Rack shall be 6 core fiber cable. - -
For Data Networking any deviation is not permissible unless and other wise permission
granted by the consultant. - -
For Data Net Working System Contractor to quote and supply currently available
equipments as per / better / higher than the tender specifications and should ensure that
solution functionality remains unchanged and without any change in prices after prrior
approval by Architect/Consutant. All Shop drowings of Data Networiking system shall be
prepared by the contrector for approval by the Architect/ Consutant.
5 Indoor IP Dome Camera - -
supply, fitting, fixing and testing of 4 MP IR VF Metal Dome Network
Camera(DAY/NIGHT),1/3" Progressive Scan CMOS,2560 × 1440@30fps, 2.8 to 12 mm
motorised Varifocal lens, Color: 0.01 Lux @ (F1.2, AGC ON),0.018 Lux @ (F1.6, AGC
ON), 0 Lux with IR,H.265+, H.265, H.264+, H.264,Three streams,120dB WDR, 2 behavior
analyses, and face detection, BLC/3D DNR/ROI,IP67, IK10,Built-in micro
SD/SDHC/SDXC card slot, up to 128 GB,3-Axis adjustment, Up to 50 Mtr IR Range, 3D
DNR; ICR; EXIR, up to 50m; DC12V&PoE; Built-in micro SD/SDHC/SDXC slot; cloud
service, should have protection level of IP67, IK10 TVS 2000V Lightning Protection,
Surge Protection and Voltage Transient Protection, should support ONVIF (PROFILE S,
PROFILE G), ISAPI. Nos 64 31,049.52 19,87,169.09
6 IP PTZ Camera - -
Supply , installation , testing and commissioning of Supply, Installation, Testing &
Commissioning of 4 MP PTZ Camera , ONVIF profile S , G and Q , UL,CE,FCC Certified
, 36 X Optical Zoom , Focal length 4.3mm to 129 mm , 12 X digital zoom , Quad stream
,H.265 , H.264 video compression support , frame rate 25 FPS @ 3MP , 50 FPS @ 2
MP ,2 streams simultanepusly at 1920 X 1080 p ,Shutter Speed : 1/1 ~ 1/10000 sec ,
360° endless Pan , -20° ~ 200° tilt , Pan Manual Speed : 0.1° ~ 300°/s , Tilt Manual
Speed :0.1° ~ 200°/s , 256 presets , 120 dB WDR ,Edge analytics : Abandoned Object,
Intrusion Detection, Tampering, Wrong Direction, Loitering Detection, Object Counting,
Stopped Vehicle, Object Removal , Inbuilt IR LED , IR Distance upto 200 mtrs , IP 66.
7 NVR Processor - -
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
64 Channel NVR Processor :- Dual-core embedded processor,Operating System : Pre-
loaded Licensed OS,IP Camera Support : Min 32 Channel or higher,Two way talk : 1
Channel O/P and 1 Channel I/P,Compression : H.265, H.264, MJPEG4,Video Resolution:
Should support up to 8MP IP Camera. Video Recording (Incoming bandwidth) : 256
Mbps,Video Display Split : 1/4/8/16/32,Video Loss : Support,Camera Blank :
Support,Alarm Input/ Output : Min 16 channel / Min 4 Channel or betterHard Disk : Min 8
SATA ports , up to 32TB , Raid(Redundancy), ,Smart Phone : iPhone, iPad, Android,
Windows,Phone,Protocol : IPv4/IPv6, HTTP, HTTPS, SSL, TCP/IP,UDP, UPnP, ICMP,
IGMP, SNMP,RTSP, RTP, SMTP,NTP, DHCP, DNS, PPPOE, DDNS, FTP, IP
Filter,ONVIF Profile S,User Account : 10 Users,Trigger Event : Recording, Alarm, Video
Push, Email,FTP,Recording Mode : Manual , Schedule , STOP,Search Mode : Time/Date
, Alarm , Motion Detection ,Exact Search (accurate to second), Smart Search,Playback :
Play, Stop, Pause, Rewind, Fast Play, Next file, Previous file, Next Camera, Previous
Camera, Full Screen, Backup Selection,Backup Mode : USB Device / Internal SATA /
NetworkInterface Ports : 2 USB 2.0 , 1 RS485 , 1,RS232, 2 RJ45,Ethernet Ports : 2 RJ-45
port (10/100M/1000M),Power SITC : AC 100V~240V 50/60Hz,Regulatory : CE, FCC,UL
8 Supply installation of 8TB surveillance SATA HDD. Nos 4 29,440.12 1,17,760.46
9 Digital SIP based EPABX Systems - -
IP PBX SYSTEM:- Supply, fitting, fixing, commissioning and testing of IP based 100%
non-blocking IP PABX System should be a IP Compatible with rich feature set of the
system and can be connected with pure Voice over IP (VoIP) communication network
across corporate Local and Wide Area Networks (LAN and WAN) as & when required.
Central Processing Unit: The system main software should be open architecture based.
The CPU of main system shall be 32 bit processor working at 2.0 GHz or better. The
system should be Wall mountable.
• System Architecture should be latest pure IP and should be wall Mountable. Meet-me
conference 30 party X 2 from day 1 must be available.Must Support Unified
Communications. Equipped with 48 Analog extensions and expandable further. in built
charger, battery with one our back up facitity. 8 Analog Trunk Ports, 8 Digital, 1 PRI , 02
Ports Auto Attendant- IPABX.
10 10 KVA UPS with SMF batteries suitable for minimum back time 60 minutes : -
(A) SITC of 1 no. 10 KVA UPS with SMF back-Up batteries, suitable for 30 minutes
configuration with :- 415V, 3ph input & single phase output ON-LINE UPS system
backup protection for 60 minutes and all standard accessories as required. The Inverter
will have in built protection for ground fault, DC reverse polarity, DC over voltage and
current limitation, AC short circuit, AC over Voltage and current limitation. The UPS
technology should consists of high double-conversion efficiency IGBT Based rectifier on
line type UPS. - -
Configuration of UPS :- - -
3 Phase input & single Phase output - -
The above mentioned on-line UPS must have following features - -
1) Upgradeability :- Suitable for 20 KVA UPS, and Should be upgradable to work as
parallel redundant UPS in load sharing mode. - -
2) Intelligent LCD display with event logging facility. - -
3) Double conversion. - -
4) Built in paralleling kit. - -
5) IGBT technology for Rectifier and Inverter. - -
6) Split Static, Manual & Maintenance Bypass. - -
7) Input power factor correction less than 0.95. - -
8) Input harmonic distortion less than 5% at 50% load. with the application of
IGBT(Insulated Gate By polar Transistor) based rectifier, but 6/12 pulse is not applicable.
9) Software communication :- RJ-45 port to communicate with BMS and Should be
SNMP (Simple Network Management protocol) compatibility. - -
10) Phase reverse sequence operation - -
11) Automatic static bypass - -
12) Maintenance Bypass. - -
13) Technology : Micro processor based controls, true online, double conversion type,
should have cold start facility. - -
14) Overall Efficiency :> 90% - -
15) Charger :- Should have built in charger of minimum 10 Amp. (separate from rectifier)
16) Back-up time :- 60 min. with SMF Batteries. - -
17) Minimum Guranttee /Warranty Period:- 24 Months from the date of installation, - -
(B) SITC of Sealed Maintenance free batteries Shall be along with DC breaker with
enclosure of suitable capacity along with No-volt coil with suitable capacity of contactor ,
U-Tube, required size and length of 4 core copper flexible cables along with terminals
and all accessories as required for protection of UPS. (For 10 KVA UPS). Minimum
Guranttee /Warranty Period:- 24 Months from the date of installation.
( C ) SITC of Battery Rack and inter Link Cables. - -
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
Total Cost of 5 KVA ON LINE UPS (3 phase in coming and Single Phase out going) &
sealed maintenance free Batteries with Rack and inter Link Cables. (A+B+C) (Cost for 1
set of 5 KVA UPS with Batteries & Rack) Nos 1 3,37,179.22 3,37,179.22
Passive Networking - -
11 Optical Fiber:- Providing, drawing, connecting and testing of 12 Core unarmoured
unitube single Mode OM3 OFC (Fiber Optics cable) from wall mounted rack to server
room Rack,i,e Rack to Rack Connectivity) in existing heavy duty 25 mm PVC Pipe.
12 PVC Conduit:- Supplying and fixing of following sizes of Med. Class PVC conduit along
with the accessories in surface / recess & cutting the wall and making good the same in
case of recessed conduit as required. - -
13 Cat 6 Cable:- Supplying and drawing of UTP 4 pair CAT6 LAN & VOICE cable (AWG
23)in the existing surface /recessed steel /PVC conduit as required. (for
Data/Voice/CCTV Outlet in existing conduit). - -
14 Cat 6 Patch Panel:- Supplying, fitting, fixing, connecting and testing CAT6 UTP RJ45
Loaded patch panel & connector - 24 port loaded 19" panel - 1 U, Panel: DC01
galvanised sheet steel, Compliant with standards: ISO/IEC 11801 Edition 3.0 CENELEC
EN 50173-1 2007 ANSI/EIA/TIA 568 C2-1 IEC series 60603-7, NFC 20730, Standard
8877 – 603.7, Contacts: gold/nickel, thickness of gold > 0.8 μm minimum, Equipped with
rear cable guide to hold cable during maintenance,The connectors are connected from
the front without a special tool. Equipped with 4 cassettes of 6 RJ45 Cat. 6 connectors
with toolless fast connection, marked 568 A/B, Max. number of connections and
disconnections: 5 without replacing the wire, Endurance: 2500 operations (plug-in/pull-
out) IK03, Operating temperature: -40°C to +70°C.
15 Cat 6 Outlet:- Providing, fixing, fitting, connecting and testing of white RJ 45 Cat 6 Data
outlet / Toolless information outlets with white coloured RJ-45 transparent shuttered
modular scoket outlets with front plate. ETL verified to meet or exceed TIA / EIA category
6 requirements, universal wiring label permitting to either T568A or T568B, UL listed, for
computer networking complete in all respect suitable to fix in modular plate type switch
system with connections as required. Nos 220 814.20 1,79,124.00
16 Cat 6 Patch Cord:- Supply fitting, fixing, and testing of BLUE/YELLOW color CAT6
LCS2 U/UTP 1 MTR (3.5 ft) factory made LCS2 Patch cord with boot Factory Crimped
PVC,Performance at 250MHz Should be as per Standards - IEC 61935-2 - Ed. 3.0
ISO/IEC 11801, Usage Temp – 20 to + 60°C, No of Twists 500, No of insertions 750, 24
AWG for rack end. Nos 356 537.37 1,91,304.43
17 Cat 6 Patch Cord:- Supply fitting, fixing, and testing of BLUE/YELLOW CAT 6 LCS2
U/UTP 3 MTR (10 ft) factory made LCS2 Patch cord with boot Factory Crimped
PVC,Performance at 250MHz Should be as per Standards - IEC 61935-2 - Ed. 3.0
ISO/IEC 11801, Usage Temp – 20 to + 60°C, No of Twists 500, No of insertions 750, 24
AWG at end user side. Nos 70 631.01 44,170.35
18 Fiber LIU:- Providing, fixing, connecting and testing of Modular of 24 port loaded LIU SC
19 Fiber LIU:- Providing, fixing, connecting and testing of Modular of 12 port loaded LIU SC
20 Fiber Patch Cord:- Providing, fixing, fitting, connecting and testing of OS1/OS2 SC/LC
duplex patch cords 3 mtr, PC Nos 24 4,081.86 97,964.54
21 Fiber SFP:- Supply, Installtion & Commisioning of Single Mode Fiber Module . Data rate
minimum 1 Gbps . Fiber connector – LC type, Operating temperature minimum 0-60
Degree, RoHS Compliant, Should support Digital optical mirror, Hot swappable. Preffered
22 Krone box:- - -
Providing, fixing, connecting & testing of Krone box (Telephone Tag Block) in a
thermoplastic, IP 65 (weather proof) enclosure, internally embedded gasket, anti
corrosive, insulated and shock proof with provision for cable through IP 65 glands
complete in all respects. - -
20 pair Tag Block (krone Box) (300 mm x 300 mm x 70 mm) Nos 6 2,985.40 17,912.40
50 pair Tag Block (krone Box) (750 mm x 750 mm x 90 mm) Nos 1 5,970.80 5,970.80
CLI Telephone:- Supply installation and commissioning of analogue phones with CLI Nos 35 1,058.46 37,046.10
24 Display Telephone:- Supply installation and commissioning of analogue phones with CLI
and display. Nos 13 5,495.85 71,446.05
25 Floor Mount 32 U Rack:- - -
Suply, fixing, fitting, installation and testing of floor mount 36 U networking cabinet 19"
along with all standard accessories CAT No.-634801, 800mm (W), 800mm (D), approx.
Wt.120 Kg, CRCA 'D' grade 1.2mm thick sheet, pwoder coated for cabinet RAL- 9017,
4mm Toughened Tinted Glass Door and along with following accessories:-
1. Cooling fan 220/230V AC, of 90 CFM-------4 Nos. - -
2. Cable manager Metal ------3 Nos. - -
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
4. Cable Channel 100mm wide. -----2 Nos. - -
5. Heavy Duty Stationary Shelf 600mm(W)X475mm(D) -1 - -
6. Mounting Hardware (20 Sets of M-6 screws, washers, cage, nuts (Nickle Coated)-------
7. Earthing strips copper 150mm H -----1 Nos. - -
8. Door Lock -----1 Nos. - -
9. Caster Wheels (with breake) -----2 Nos. - -
10. Caster Wheels (without breake) -----2 Nos. - -
11. Front Metal Band-----------1 No. - -
In the rack there must be maintained1 U = 1.75 inches space. - -
Cost of Floor Mount 42 U Network Rack Nos 1 50,385.41 50,385.41
26 Wall Mount 12 U Rack:- - -
Providing, fixing, fitting, installation and testing of of 9U Wall Mounted Networking
Cabinet 504.65X600X500 (HXWXD): Rack must be along with the following components
like; Width (mm)-600, Depth (mm) - 500, Approx.Net Wt (kg) - 20, CRCA 'D' Grade
thickness (mm) - 1.2, RAL 9017 (Matt Black), Glass - 4mm Toughened Tinted Glass
Door, Accessories:, Cooling Fan (230V A/C 90 CFM) - 2 Nos, PDU 230VAC - 1 No,
Cable Manager Metal- 2 Nos, Mounting Hardware (20 sets of M6 screws,washer,cage
nuts (nickel coated)) - 1 No, Wall Screws (4 sets of 2'' screws, washer,rubber grommet
(nickel coated)) - 1 No, Door Lock - 1 No, Front Metal Band -1 No. In the rack there must
be maintained 1 U = 1.75 inches space. - -
Cost of 12 U Rack set Nos 6 21,033.50 1,26,201.00
Audio Systems for Conference Hall - -
27 Supply, Installation, Commisiong and Testing of Table top Boundry layer delegate digital
long microphone unit with following features:- - -
Technical specifications - -
Frequency response:200 Hz to 12.5 kHz - -
Headphones load impedance:> 32 ohms < 1k ohm - -
Loudspeaker nominal output:72 dB SPL - -
Length of microphone :480 mm (18.9 in) - -
Operating temperature:0 ºC to +35 ºC - -
Plug and play functionality for ensuring fast - -
installation and reconfiguration times - -
Immunity to mobile phone interference - -
Functions - -
Possible-to-speak indication - -
Request‑to‑speak indication - -
Built-in loudspeaker with volume control - -
Built‑in 3.5 mm (0.14 in) stereo headphones socket - -
Built‑in volume control for headphones - -
Color-coded LED indicator above microphone button for showing the following states:
microphone on, request‑to‑speak, and possible‑to‑speak - -
Total Cost of Deligate Digital Microphone Unit. Each 20 76,127.70 15,22,554.00
28 Supply, Installation, Commisiong and Testing of Table top Boundry layer Chairman
digital long microphone unit with following features - -
Technical specifications - -
Frequency response:200 Hz to 12.5 kHz - -
Headphones load impedance:> 32 ohms < 1k ohm - -
Loudspeaker nominal output:72 dB SPL - -
Length of microphone :480 mm (18.9 in) - -
Operating temperature:0 ºC to +35 ºC - -
Plug and play functionality for ensuring fast - -
installation and reconfiguration times - -
Immunity to mobile phone interference - -
Functions - -
Possible-to-speak indication - -
Request‑to‑speak indication - -
Built-in loudspeaker with volume control - -
Built‑in 3.5 mm (0.14 in) stereo headphones socket - -
Built‑in volume control for headphones - -
Color-coded LED indicator above microphone button for showing the following states:
microphone on, request‑to‑speak, and possible‑to‑speak - -
Total Cost of Chirman Digital Microphone Unit. Each 2 76,411.31 1,52,822.63
29 Supply, fitting, fixing, testing and commissioning of Mixer High-Performance12-input
small format analogue mixers with onboard effects, Iconic Ghost mic preamps with ultra-
low noise performance , British EQ with sweepable mid-bands per channel, Effects
Engine featuring award-winning Reverbs, Delays, Choruses and Modulations ,Limiters
(High-ratio Compressors) on input channels,2-in/2-out USB audio playback and
recording*Switchable Hi-Z inputs for guitars, basses and other instruments, Hi-Pass
Filters (low-cut) and 48V Phantom Power on all mic channels, Comprehensive GB Series
audio routing, Smooth premium-quality faders, Robust metal construction for tour-grade
build quality and reliability, Internal universal power supply Each 1 1,79,517.53 1,79,517.53
30 Supply, Installation, Commisiong and testing of Digital Central Control Unit for Digital
Discussion. - -
Technical specifications - -
Built‑in MP3 recorder with internal memory and USB recording - -
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
Built‑in Digital Acoustic Feedback Suppression - -
Quick and easy connection upto 80 discussion devices - -
Native support for automatic HD camera control - -
Signal to noice :> 94 dBA - -
Frequency response for input :30 Hz to 20 kHz - -
Recording/ Playback (bit rate):64, 96, 128, 256 Kbit/sec - -
Nominal loudspeaker output:72 dB SPL - -
Operating temperature: 5 ºC to +45 ºC - -
Relative humidity: 5% to 98% non-condensing - -
Functions - -
Plug-and-play functionality - -
Web browser control - -
Open microphone control - -
Built-in MP3 recorder - -
Discussion control - -
Total Cost of Digital Central Control Unit. Set 1 3,14,700.51 3,14,700.51
31 Supply, fitting, fixing, commissioning and testing of 50 W cabinet speakerBuilt-in
100v/70v transformer, 4” +1.5” coaxial speaker unit.Power output RMS 30W @100V.
Built-in crossover for hi-fi level use. Metal grille and metal baffle. Each 8 26,461.50 2,11,692.00
32 Supply, fiting, fixing, commissioning and testing of Four Channel Class-D Digital Power
Amplifier of 240W, 230V;RMS with Switch power technology for power electricity saving.
33 Supply,installation, testing and commissioning of handheld Wireless Mic system set with
two transmitters dynamic microphone, Frequency Response 40Hz-15,000 Hz, Surge
mode PLL Phase lock, Dynamic Range >90dB, THD < 0.5%, S/N ratio > 90dB, Carrier
frequency range 720 - 830 MHz. (Wire Less Lapel Micro Phone with Receiver Unit along
with all acessories and charger unit and suitable battery. Set 4 62,055.61 2,48,222.44
34 Wiring with of 2.5 Sq.MM Unarmoured Flexible Speaker Cable as per site with 2mm
thick rigid 25 mm PVC pipe, modular boxes, plate, fitting, fixing, connecting and testing of
the same etc. as required. Mtr 200 373.18 74,635.00
35 Equipment Rack-17 U - -
Providing, fixing, fitting, installation and testing of of 9U Wall Mounted Networking
Cabinet 504.65X600X500 (HXWXD): Rack must be along with the following components
like; Width (mm)-600, Depth (mm) - 500, Approx.Net Wt (kg) - 20, CRCA 'D' Grade
thickness (mm) - 1.2, RAL 9017 (Matt Black), Glass - 4mm Toughened Tinted Glass
Door, Accessories:, Cooling Fan (230V A/C 90 CFM) - 2 Nos, PDU 230VAC - 1 No,
Cable Manager Metal- 2 Nos, Mounting Hardware (20 sets of M6 screws,washer,cage
nuts (nickel coated)) - 1 No, Wall Screws (4 sets of 2'' screws, washer,rubber grommet
(nickel coated)) - 1 No, Door Lock - 1 No, Front Metal Band -1 No. In the rack there must
be maintained 1 U = 1.75 inches space. Set 1 40,031.50 40,031.50
Video Display System for conference hall - -
36 Supply, Installation, Testing & Commissioning of Multi Media XGA LCD Projector 6,000
lumens WXGA high brightness compact projector Display System: 3 LCD system
Size of effective display area: 0.75”(19mm) x 3 Bright Era LCD Panel Aspect ratio
16:10,Number of pixels : 3,072,000 (1280x800 x 3) pixels
Throw Ratio :1.10:1 to 1.79:1,Zoom – Ratio : Approx. x 1.6,Contrast ratio (full white / full
black) 20000:1 *2,Speaker: Speaker 16 W (monaural)
INPUT A : RGB / Y PB PR input connector: Mini D-sub 15 pin female Audio input
connector: Stereo mini jack,INPUT B: RGB input connector: Mini Dsub 15 pin female
Audio input connector: Stereo mini jack,INPUT C: HDMI input connector: HDMI 19-pin,
HDCP support Audio input connector: HDMI audio support,INPUT D: HDMI input
connector: HDMI 19-pin, HDCP support Audio input connector: HDMI audio support,S
VIDEO IN : S Video input connector: Mini DIN 4-pin,VIDEO IN: Video input connector:
Phono jack OUTPUT : MONITOR output connector: Mini D-sub 15 pin female Audio input
connector: Stereo mini jack,LAN : RJ-45, 10BASE-T/100BASE-TX,USB: Type-A & Type-
B MICROPHONE IN: Microphone jack: Mini Jack Display resolution: Maximum display
resolution: 1600 x 1200 dots, fV:60Hz Screen size : 30" to 300" (0.76 m to 7.62 m)
(measured diagonally).
37 Supply,Installation,Testing & Commissioning of Projector Mounting Kit (Ceiling Mount Kit)
- 3' x 3'. Powder Coated. Set 1 8,684.80 8,684.80
38 Supply, Installation, Testing & Commissioning of Electronic 8'x6' White Matt motorized
Projection screen with RF Remote control, Aspect ratio - 4 : 3. The Motorized Screen - 8'
x 6' with RF Remote Control, 16:9 Aspect ratio supported. Application : Versatile for
Multiple Applications - Cine White, Material : Fabric (Sheer Weave), Type : White, Screen
Gain : 1.1, Viewing, Angle : 160 (80° + L&R), Mildew Resistance : Yes, Hand Clean :
Yes, Wall & Screen : CineTension2 Sable Frame, ezFrame, Lunette, Peregrin
Twin*, Aerie Tension*
39 Supply fitting, fixing and testing of Network cable assembly, (10 m.X2 ) Set 1 26,461.50 26,461.50
40 Supply, fitting, fixing and commissioning of Passive wall plate VGA+Audio and HDMI.
41 Supply, fitting, fixing and commissioning of 10 Mtr HDMI Cable; Bulk 1 15,605.50 15,605.50
42 Supply, laying, fixing, terminationg and testing of10 Mtr VGA Cable; Bulk 1 15,605.50 15,605.50
43 Supply fitting, fixing and testing of Cables, Connectors & Accessories. Make- OEM Bulk 1 10,856.00 10,856.00
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
For conference system the contractor to quote and supply currently available equipments
as per the tender specifications or better / higher than the tender specifications (with
declaration from OEM regarding roll over model if current model is end of sale) and
should ensure that without changing the solution functionality and without chnaging in
above prices. -
Contractor should be either and original equipment manufacturer (OEM) or Contarctor
should attached an authorisation letter from the OEM specific to the attached
specifications and addressed to department / Architect /Consultant . All shop drawing as
per above specification shall be prepared by the contractor and shall be approved by the
Architect/Consultant . -
The execution of above audio video conference system in Conference Hall of Black
Daimond, Angul has to be carried by any authorized system intrigrator/ channel partner of
Original Equipment Manufacture ( OEM) and for that final approval has to be taken from
the Architect/ Consultant. -
FIRE FIGHTING WORK
1.0 Pumps and Equipments
Providing ,fixing , testing and commissioning of diesel Engine driven common stand by
pump, horizontal centrifugal end suction back pull out type with gland packing and
capable to deliver 2280 LPM at 55 MWC. The pump shall coupled to suitable HP of
Diesel engine radiator water cooled type with speed of 1800 RPM and complete set shall
be mounted on common base frame. Batteries & battery leads with stand, Fuel tank ( for
1.1 6 Hrs. operation & double container type) with stand & gauge glass, Fuel piping with Nos 1 6,15,198.00 6,15,198.00
valves. The quoted rate shall includes water re - circulation piping, Pressure relief valve,
radiator water cooling piping(if required) coupling guard and other standard accessories,
foundation bolts, etc. complete as per the manufactures recommendations.
Providing ,fixing , testing and commissioning of electrical motor driven Jockey pump of
horizontal centrifugal end suction back pull out type with gland packing and capable to
deliver 180 LPM at 55 MWC.The pump shall be coupled to TEFC motor of suitable HP
with speed of 2900 RPM and complete set shall mounted on common base frame. The
1.2 quoted rate shall includes providing & fixing of compound gauge, coupling, coupling Nos 1 1,02,391.00 1,02,391.00
guard, foundation bolts etc,complete as per the manufactures recommendations
Providing ,fixing , testing and commissioning of electrical motor driven main pump of
horizontal centrifugal end suction back pull out type with gland packing and capable to
deliver 2280 LPM at 55 MWC.the pump shall be coupled to TEFC motor of suitable hp
1.3 with speed of 2900 rpm and complete set shall mounted on common base frame. The Nos 1 3,30,204.00 3,30,204.00
quoted rate shall includes providing & fixing of compound gauge , coupling, coupling
guard, foundation bolts etc, complete as per the manufactures recommendations .
Providing ,fixing , testing and commissioning of electrical motor driven main pump of
horizontal centrifugal end suction back pull out type with gland packing and capable to
deliver 450 LPM at 35 MWC.the pump shall be coupled to TEFC motor of suitable hp with
speed of 2900 rpm and complete set shall mounted on common base frame. The quoted
1.4 rate shall includes providing & fixing of compound gauge and suitable size of metal Nos 1 85,291.00 85,291.00
expansion bellows at both side of the pumps ,anti vibration pad, water re-circulation
arrangement, pressure relief valve, coupling, coupling guard, foundation bolts etc,
complete as per the manufactures recommendations
Providing, fixing ,testing and commissioning of compartmentalized common control
panel with mechanical and electrical interlock facility for the fire pumps. All the
components shall be housed in a common cubical made of 16 SWG. M.S. sheet with
required stiffeners). The panel shall be powder coated of approved color both inside &
outside. The panel shall have both bottom & top cable entry provisions and panel shall be
mounted on Pedestal of 300 mm height. The given feeder size is ony indicative , actual
shall be as per OEM , vendor has to consider the same in their qoute .: CPRI approved
1.5 Incoming Feeder Nos 1 2,87,855.00 2,87,855.00
a. 2 nos. 400A TPN MCCB (50 KA) and shall be motor operated type
b. 2 Sets of 400 Amps. TPN Al. Bus bars with color coded heat shrinkable PVC sleeves.
c. 1 Set of RYB indicating lamps with individual MCB.
d.1 No. 0-400 Amps. Ammeter with selector switch and suitable rated current
e.1 No. 0 - 400V. Voltmeter with selector switch
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
Feeder For DG Driven Pump -1 no
1. 20Amps DPMCB - 1 Nos.
2. Battery charger with transformer with rectifier resistance DC ammeter
3. DC voltmeter, Trickle / booster / off selector switch -1 No
4. Following indication lamps- 1 sets
Phase indication, Battery charger on, Over load relay, DC supply on,control switch on , - -
Engine fails to start, Pump on, Low oil pressure,High water temperature and Auto
manual selector switch
5. Following push button stations - 1 Sets
Engine Start,Engine Stop, Engine hooter, Engine fault reset, Selector switches for Engine
control & mode selector
6. Hooter Industrial type for audio alarm - 1 No.
Feeder For Jockey Pump - 1 Nos
a. 1 Nos. 32A TP MCCB without releases
b. DOL with over load relay, single phase preventer and indicating lamps with ON / OFF
c. 1 No. Auto manual selector switch
d. 2 Nos. of NO/NC contacts for extending the status to the Fire alarm panel
Feeder For Main Pump -1 Nos
a. 1 Nos. 150A TP MCCB without releases
b. DOL with over load relay, single phase preventer and indicating lamps with ON / OFF
c. 1 No. Auto manual selector switch
d. 2 Nos. of NO/NC contacts for extending the status to the Fire alarm panel
Feeder For booster Pump - 1 Nos
a. 1 Nos. 32A TP MCCB without releases
b. DOL with over load relay, single phase preventer and indicating lamps with ON / OFF
c. 1 No. Auto manual selector switch
d. 2 Nos. of NO/NC contacts for extending the status to the Fire alarm panel
Supplying, installing ,testing and commissioning of FRLS,PVC outer sheathed, steel
armored, aluminum conductor, 1100 Vgrade power cables with glands etc.The cables
shall be laid in tray / Hume pipe / in trenches/on walls/ floor etc. as required. For cables
1.6 laid out door the rate shall include earth excavation providing brick and sand protection, - -
refilling and compacting the earth.The rate shall excludes tray & Hume pipes.The
minimum size & length of the cables shall be considered as required for the complete
12 C x 2.5 Sqmm. Copper cable Diesel engines Rmt 30 449.30 13,478.85
4 C x 25 Sqmm. Aluminum cable Jockey pumps Rmt 30 282.98 8,489.25
2 C x 2.5 Sqmm.Copper cable for Instrumentation Rmt 120 155.93 18,711.00
3.5C x 120 sq.mm Aluminum cable for main pumps Rmt 60 438.00 26,280.00
Providing ,fixing , testing and commissioning of perforated G.I.sheet cable tray with
necessary angle iron suspension supports, anchor fasteners etc. complete. Maximum
height of suspension shall not exceed 500 mm.Size / length of the tray shall be suitable
for laying the above mentioned cables.
Providing ,fixing , testing and commissioning of G.I. Earthing strips of 50mm x 6mm
1.8 thick, strip shall be run on floor / ceiling / walls, from the MCC panel to all equipments as Rmt 20 132.83 2,656.50
per standard with necessary accessories as required.
Providing ,fixing , testing and commissioning of C.I.flanged "Y" type Strainer with SS
mesh, suitable flanges, nuts, bolts, gaskets etc. complete.any ISI mark
Providing ,fixing , testing and commissioning of PN 10 C.I.Gate valves as per IS:14846
with rising spindle type with flanges, bolts, nuts, washers, gaskets etc.
100mm nominal dia Nos 1 14,428.00 14,428.00
150mm nominal dia Nos 1 22,550.00 22,550.00
200mm nominal dia Nos 2 39,133.00 78,266.00
250mm nominal dia Nos 1 46,318.00 46,318.00
Providing ,fixing , testing and commissioning of PN 16 swing check type C.I. Non-return
1.11 valves as per IS:5312 with required flanges, nuts, bolts and gaskets etc. complete - -
80 mm nominal dia Nos 1 7,539.00 7,539.00
150 mm nominal dia Nos 3 17,577.00 52,731.00
Providing ,fixing , testing and commissioning of PN 16 CI butterfly valves as per BS 5155
1.12 standard slim seal lever/gear operated type with required flanges, nuts, bolts etc. - -
80 mm nominal dia - Lever operated Nos 1 4,842.00 4,842.00
150mm nominal dia - Lever operated Nos 5 8,699.00 43,495.00
Providing ,fixing , testing and commissioning of 150 mm dia electronic digital display flow
meter on Test line to measure 175 % of pump flow.
Providing ,fixing , testing and commissioning of Pressure switches of suitable range for
pump sets with Ball valves, Fittings like unions / colors / reducers etc.
Supplying, installing ,testing and commissioning of Pressure gauges of suitable range for
pump sets and pipe lines for the respective floors near to the flow switches with Ball
valves, siphon, Fittings like unions / colors / reducers etc. Glycerin filled pressure gauges
to use on pump discharge lines.
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
Providing ,fixing , testing and commissioning of GI Pipes confirming to IS 1239 Pt - I
Heavy grade up to 150 mm & 3589,6mm thick for above 150 mm dia, with painting,
suitable type of supports( fabricated by angles, channels, flats etc, with painting with
fasteners), anchor fasteners, bolts nuts ( Galvanized), clamps, "U" bolts, malleable
1.17 specials such as Reducers,Tees, elbows (as per IS 1239 Pt II), flanges. Including cutting, - -
Welding, fixing in / on walls, ceiling by using suitable supports etc, as per drawings. The
quoted rate shall also inclusive of civil work in walls and making them good with filler
material and finished in cement mortar etc. complete.
80mm nominal dia Rmt 8 1,252.00 10,016.00
100mm nominal dia Rmt 6 1,627.00 9,762.00
150mm nominal dia Rmt 18 2,269.00 40,842.00
200mm nominal dia Rmt 6 3,280.20 19,681.20
250mm nominal dia Rmt 8 3,932.78 31,462.20
2.0 Hydrant System - -
Providing ,fixing , testing and commissioning of Single headed hydrant valve(Internal) as
per IS 5290, made of gunmetal with 63 mm dia instantaneous out & 80 mm dia fanged
inlet , Blank cap , chain and hand wheel etc complete and a) 2 lengths of 15 M long,
2.1 63mm dia RRL hose,b)1 no. Gun metal short branch pipe with nozzle,c)Hose reel drum Nos 9 21,235.00 1,91,115.00
of swinging type with 19mm dia Rubber braided hose of 36M length with ball valve and
Shut off nozzle with required accessories to install the equipments etc., complete.
Providing ,fixing , testing and commissioning of Fire duct Shutter fabricated out of M.S
sheet and frame, door (SWG 16) and powder coated of approved red color both inside
2.2 and out side. The size shall be 900mm x 1200 mm min. & fixed with 6 mm thick Glass, Nos 9 - -
and key with suitable Rubber beading and Locking arrangement as per the tender
Providing ,fixing , testing and commissioning of fire brigade inlet connection of 4 way
with 4 nos. 63 mm dia. built - in Gun metal Non- return valves instantaneous coupling
2.3 type arranged on 150 mm dia. Pipe manifold and connected to wet riser main. Quoted Nos 1 13,822.00 13,822.00
rate shall be included with C.I. Butterfly valve, C.I. Non-return valve and M.S. cabinet of
suitable size with mounting supports etc. complete.
Providing ,fixing , testing and commissioning of GI Pipes confirming to IS 1239 Pt - I
Heavy grade up to 150 mm & 3589,6mm thick for above 150 mm dia, with painting,
suitable type of supports( fabricated by angles, channels, flats etc, with painting with
fasteners), anchor fasteners, bolts nuts ( Galvanized), clamps, "U" bolts, malleable
2.7 specials such as Reducers, Tees, elbows (as per IS 1239 Pt II), flanges. Including cutting, - -
Welding, fixing in / on walls, ceiling by using suitable supports etc, as per drawings. The
quoted rate shall also inclusive of civil work in walls and making them good with filler
material and finished in cement mortar etc. complete.
80mm nominal dia Rmt 38 1,252.00 47,576.00
100mm nominal dia Rmt 0 - -
150mm nominal dia Rmt 120 2,269.00 2,72,280.00
Providing ,fixing , testing and commissioning of GI. Pipes confirming to IS 1239 Pt - I
Heavy grade up to 150 mm & 3589,6mm thick for above 150 mm dia, with suitable type
of supports, malleable specials such as Reducers,Tees, elbows(as per IS 1239 Pt II),
flanges. Including cutting, Welding as per drawings. The rate quoted should be included
with anticorrosive treatment with 4 mm thick polymer corrosion resistant tape as per IS
10221, overlap shall be maintained at 15mm minimum.
150mm nominal dia Rmt 300 2,269.00 6,80,700.00
Providing ,fixing , testing and commissioning of PN 16 CI butterfly valves as per BS 5155
2.90 slim seal standard lever operated type with required flanges, nuts, bolts etc. complete. - -
150mm nominal dia Nos 3 8,699.00 26,097.00
3.0 Fire Extinguishers - -
Providing ,fixing , testing and commissioning of Portable Carbon-di-oxide Gas Type Fire
Extinguisher 4.5 Kgs, squeeze Grip,Controllable discharge mechanism with nozzle, bend,
Hose and wall mounting bracket etc.The Can is made of Seamless Clinger and External
Coating done by Spray Painting.The thickness shall not less than 4.5 mm made of Sheet
metal.The Fire Extinguishers shall be ISI Approved as per IS 15683:2006.Vendor shall
consider the suitable signages along with the extinguishers.
Providing ,fixing , testing and commissioning of Portable AFFF Foam Type fire
extinguisher 9 Lt Capacity, Stored Pressure Type with Pressure Gauge, hose and
brackets etc .The discharge Range shall be minimum of 6 mtrs.The Internal Coating of
3.2 Can shall be Epoxy Powder coating and External painted with Epoxy Polyester Powder Nos 4 3,993.99 15,975.96
coating .The thickness shall not less than 2mm made of Sheet metal.The Fire
Extinguishers shall be ISI Approved as per IS 15683:2006.Vendor shall consider the
suitable signages along with the extinguishers.
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
Providing ,fixing , testing and commissioning of Portable ABC powder type fire
extinguisher 6 Kg capacity containing Mono Ammonium Phosphate Powder 50, Stored
Pressure Type, fitted with Discharge hose, brackets etc., The discharge Range shall be
3.3 minimum of 4 mtrs.The Internal Coating of Can shall be Epoxy Powder coating and Nos 26 4,088.70 1,06,306.20
External painted with Epoxy Polyester Powder coating.The thickness shall not less than
1.6 mm made of Sheet metal.The Fire Extinguishers shall be ISI Approved as per IS
15683:2006.Vendor shall consider the suitable signages along with the extinguishers.
Providing ,fixing , testing and commissioning of Fire buckets round bottom type enamel
3.4 painted, white inside & Red out side and Letter "FIRE" in black out side and handle with Nos 10 1,432.20 14,322.00
mounting bracket.The buckets hall be filled with sand.
Providing ,fixing , testing and commissioning of Fire bucket stand fabricated by MS
angles to install 2 Nos. of buckets.
Providing ,fixing , testing and commissioning of Portable ABC powder type fire
extinguisher 10 Kg capacity containing Mono Ammonium Phosphate Powder 50, Stored
Pressure Type, fitted with Discharge hose, brackets etc., The discharge Range shall be
minimum of 4 mtrs.The Internal Coating of Can shall be Epoxy Powder coating and
External painted with Epoxy Polyester Powder coating.The thickness shall not less than
1.6 mm made of Sheet metal.The Fire Extinguishers shall be ISI Approved as per IS
15683:2006.Vendor shall consider the suitable signages along with the extinguishers.
Main electrical rooms
Providing ,fixing , testing and commissioning of Portable WATER type fire extinguisher 9
lit capacity Stored Pressure Type, fitted with Discharge hose, brackets etc., The
discharge Range shall be minimum of 4 mtrs.The Internal Coating of Can shall be
3.7 Epoxy Powder coating and External painted with Epoxy Polyester Powder coating.The Nos 2 4,097.94 8,195.88
thickness shall not less than 1.6 mm made of Sheet metal.The Fire Extinguishers shall
be ISI Approved as per IS 15683:2006.Vendor shall consider the suitable signages along
with the extinguishers.
4.0 Signages - -
Providing ,fixing of in position the following type of sign boards made out of 3mm thick
"Opaque" PVC foam board with computer cut, PVC Non-reflective self adhesive vinyle - -
painted foam board, complete with mirror fasteners.
A sign shall read “IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED
OTHERWISE”. The lettering shall be at least 12.5 mm block letters in red and white
background. Such lettering shall be properly spaced to provide good legibility. The sign
shall be at least 250 mm x 300 mm, where the diagram is also incorporated in it and 62.5
mm x 250 mm where the diagram is omitted. In the latter case, the diagram sign shall be
at least 200 mm x 300 mm. The sign shall be located directly above a call-button and
squarely attached to the wall or partition. The top of the sign shall not be above 2 m from
the floor level.
Fire exit signage at Each stairway and each elevator back shall be identified by an
alphabetical letter. A sign indicating the letter of identification shall be posted and
maintained at each elevator landing and on the side of the stairway door from which
egress is to be made.The lettering on the sign shall be at least 75 mm high, of bold type
and of contrasting colour from the background
A sign shall be posted and maintained within each stair enclosure on every floor,
indicating the number of the floors.The numerals shall be of bold type and at least 75 mm
4.3 high. The numerals and background shall be in contrasting colors. The sign shall be Nos 6 1,006.01 6,036.03
securely attached to the stair side of the door.
Stair Re-entry Signs sign shall be posted and maintained on each floor within each
stairway and on the occupancy side of the stairway where required, indicating whether re-
entry is provided into the building and the floor where such re-entry is provided.The
4.4 lettering and numerals of the signs shall be at least 12.5 mm high of bold type. The Nos 6 1,129.59 6,777.54
lettering and background shall be of contrasting colours and the signs shall be securely
attached approximately 1.5 m above the floor level.
Fire order board should contain the following matter on 3mm thick "Opaque" PVC foam
board of computerized cut, PVC Non-reflective self adhesive vinyle painted foam board of
1. Alert the security at security room by actuating manual call point located at strategic
4.5 2. Evacuate the occupants by using fire exits and emergency exits only and assemble at Nos 1 1,437.98 1,437.98
various assembly points.
3. If possible try to extinguish the fire by using nearest / suitable portable extinguisher or
water from nearest wet riser.
4. Be calm and do not give any room from panic, walk, do not run.
5. If you encounter serious difficulty in evacuation, flat and try to attract attention of
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
Action by security/reception upon receipt of information through fire alarm or fire
detectors or by using public address system.
1. Alert the occupants by using public address system.
2. Inform fire control through any one of the following phone numbers: 101 /(local
3. Refer evacuation plan from evacuating standard people.
4. Guide the fire force, on their arrival to the seat of fire.
5. In case of the casualties, call ambulance by dialing number 108.
5.0 Civil Works - -
Excavation of trenches of 1500 x1000 mm for laying pipes up to 150mm dia. Including
forming bottom surface to required level, refilling the trenches with selected excavated
earth around the pipe in layers of 150mm thick, watering, consolidating. Quoted price
inclusive of disposing off / Carting away the surplus earth out side the site to a dump yard
acceptable local bodies or as directed by the site engineer with a lead of 300 mts. etc.
5.1.1 Excavation in all kinds of soil Cum 450 331.49 1,49,168.25
5.1.2 Cutting of Rock with chiseling Cum 2 358.05 716.10
Providing ,fixing , testing and commissioning of RCC Hume pipes of 300 mm dia & NP 2
Class with collars for road / below floor crossing. The rate shall includes excavation, PCC
( 1:4:8 100 mm thick)bed and ends shall be closed with Brick masonry work as directed
by site engineer.
Construction of valve chamber with 230 mm Brick masonry wall with best quality TM
bricks & CM 1:4,on a PCC 1:5;10 bed of 150 mm thcik.The wall shall be plastered
internally smooth in CM 1:3, water proofing as required and externally rough plastered
5.3 with sponge finish, including curing. The chamber shall be provided with M.S 8 mm thick Nos 3 12,987.98 38,963.93
plate fabricated top cover in leaves with necessary hinges and locking arrangement. The
size of the chamber shall be 1200mm x 1200mm x1500mm in depth.
Providing ,fixing , testing and commissioning of PCC (1:2:4) pedestals / supports for
5.4 Under ground / above ground pipes. Quoted rate shall inclusive of excavation ( if required Cum 2 528.99 1,057.98
), chipping / chasing, shuttering, plastering ( if required) etc. complete.
Providing ,fixing , testing and commissioning of Sealing of MEP shafts at all floor levels
by using M.S. angle Iron frame around the shaft M.S. chequered plate of 6mm thick and
PCC ( 100mm thick) of 1:2:4 on the plate for whole shaft area as per drawings and
engineer - in - charge.
6.0 Addressable Fire Detection & Alarm System - -
Providing ,fixing , testing and commissioning of Analogue addressable Fire Alarm
Control panel WITH battery back up for 48 hours normal operation and 15 minutes alarm
operation. The control panel, battery charger etc, power supply units shall be EN54 &VDS
/ MIL461E certification. The panel shall be 3 loop capacity & expandable upto 5 loops .
The panel shall have min of 7" Color LCD touch screen display withIntegrated Ethernet
Ports/ RS 485 for networking. The panel shall be complete with all accessories Vendor
shall consider the required listed power supply unit for hooters and suitable signages
along with the panel.
Providing ,fixing , testing and commissioning of Addressable Intelligent smoke detector
with inbuilt isolators base as per NFPA 72 Junction box and other accessories as
required and Detectors shall be EN54 &VDS / MIL461E certification
Providing ,fixing , testing and commissioning of Addressable Intelligent ROR heat
detectors with inbuilt isolators base as per NFPA 72 Junction box and other
accessories as required and Detectors shall be EN54 &VDS / MIL461E certification
Providing ,fixing , testing and commissioning of Response indicator for all detectors
located above false ceiling and below false flooring areas.
Providing ,fixing , testing and commissioning of Loop Powered Hooter cum Strobe with
inbuilt isolators rated at 90 dBA @ 3m for Audible annunciation and 75cd flashing at 1 Hz
for visual indication.The Hooter cum Strobe shall be as per technical specification . EN54
&VDS / MIL461E certification .
Providing ,fixing , testing and commissioning of Intelligent Manual call station having an
integrally mounted addressable module with builtin isolators that monitors and reports
contact status.The MCP shall be as per technical specification and module shall be of
EN54 &VDS / MIL461E certification.
Providing ,fixing , testing and commissioning of Addressable Intelligent Duct sensor
detector with multiple sensitivity levels, programmable for timed automatic sensitivity
selection with base and fixing accessories as required and Detectors shall be EN54
&VDS / MIL461E certification .
Providing ,fixing , testing and commissioning of Control relay module with builtin isolators
shall be capable of providing tripping of Lift/Access constrol/HVAC machines .The
Addressable control relay module shall be as per technical specification and module shall
be of EN54 &VDS / MIL461E certification.
Providing ,laying , testing and commissioning of 2C x 1.5 armoured cable confirming to
6.9 IS standards and specifications. The quoted rate shall inclusive of suitable saddles, Rmt 3500 141.00 4,93,500.00
hardware etc, complete
Sl. No. DESCRIPTION UNIT QUANTITY RATE AMOUNT
Providing ,laying , testing and commissioning of 20 mm dia.PVC FRLS flexible conduits
6.10 on ceiling / wall / floor etc. complete with accessories like, Junction boxes, Collars, Bends Rmt 250 10.44 2,610.00
Providing ,fixing , testing and commissioning of PVC FRLS as per IS standards conduits
6.11 on ceiling / wall / floor etc. complete with accessories like, Junction boxes, Collars, Bends - -
Supplying and fixing of perforated G.I.sheet cable tray with necessary angle iron
suspension supports, anchor fasteners etc. complete. Maximum height of suspension
shall not exceed 500 mm.Size of the tray is 40mm x 200mm x 40mm and 2mm thick.For
fire alam and PA system
7.0 Two way Talk Back System - -
Providing ,fixing , testing and commissioning of 15 Zone Talk back controller made of
CRCA sheet housing and rack as required. The Controller shall be micro processor
based priority module , mixing amplifier, all call / call back facility with key pad, power
7.1 supply unit & goose neck micro phone etc complete as per the technical specifications. Nos 1 1,26,399.00 1,26,399.00
The Console shall have minimum of 8 hrs battery back up and it should also work on AC
single phase power. The Controller shall be as per the technical specifications.
Providing ,fixing , testing and commissioning of B-class Amplifier of 120 W RMS out put
7.2 in rack, including necessary control wires, jocks etc. complete as per the technical Nos 1 1,45,780.00 1,45,780.00
specifications.
Providing ,fixing , testing and commissioning of 6W two way talk back Speakers WITH
7.3 talk back switch made of CRCA sheet fabricated and of wall mounted type with required Nos 9 1,780.00 16,020.00
junction boxes and complete fixing accessories.
Providing ,laying , testing and commissioning of 2C x 1.5 armoured cable confirming to
7.4 IS standards and specifications. The quoted rate shall inclusive of suitable saddles, Rmt 800 141.00 1,12,800.00
hardware etc, complete
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT_53.pdf
Tender Document
BOQ.pdf
Tender Document
GCC Contractor with amendments9.pdf
Tender Document
Approved Make.pdf
Tender Document
Milestone.pdf
Tender Document
SPECIAL CONDITIONS.pdf
Tender Document
Signed IP.pdf
Tender Document
BMS DRAWING.pdf
Tender Document
HVAC DRAWING.pdf
Tender Document
addendum-dff19f95ef8f-amendments.pdf
pdf • 0.14 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .