SUPERINTENDING ENGINEER
33/11 KV SUB STATION PURANIYA ALIGANJ LUCKNOW
Installation of Additional 5MVA at 33/11KV Vikas Nagar in administrative area of EUDC-X, LESA Transgomti, in Lucknow district of MVVNL.
2022_MVVNL_696052_1
05/EUDC-X/2022-23
Open Tender
Electrical Works
Item Wise
15 days
EDD-RAHIM NAGAR, LESA
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
EE EDD BKT LESA LUCKNOW
₹7,500
10 May 2022
4 May 2022
9 May 2022
4 May 2022
9 May 2022
4 May 2022
180 days
Amount
Carriage of all the concerning material from store center to JE's dump store& from dump store to the site work including loading,unloading and proper stacking at the site etc.
11 KV 3x300 sq mm XLPE Cable
11 KV 3x300 sq.mm Cable Jointing Kit I/D
11 KV 3x300 sq.mm Cable Jointing Kit O/D
33 KV VCB 800 Amp 750 MVA
Single T/F Control Panel
11 KV VCB I/C CTR 600/300/5 amp, 350 MVA
11 KV VCB O/C CTR 200/100/5 amp, 350 MVA
Bus Coupler 350 MVA
33 KV Line Isolator
33 KV Lightening Arrestor
33 KV Bus Isolator
33 KV CT 200/100/1 amp
Steel Materials
Rail 105 Lbs 9 Mtr Long
Temporary installation and energisation of 5 MVA T/F.
Temporary fencing of Bay and 5 MVA T/F.
Construction of plinth of size 3x4 Mtr. for Power T/F having 0.9 Mtr. above and 0.9mtr below to existing ground level without earth filling (After earth filling should be 0.4 Mtr above and 1.4 Mtr below to grond level) . The work including excavation of foundation base concreting in CC 1:6:12 ratio (cement ,fine sand & brick ballast)first class brick work in cement morter of ratio 1:4 foundation CC in 1:4:8 ratio (cement ,fine sand & brick blast) and RCC working ratio 1:2:4 (cement ,coarse sand and stone grit of 20mm gauge using MS Bars of 10mm dia( tor ) in reinforcement including its cutting ,bending &binding in required shape .The work also includes laying of 2 No. 4 Mts. long each rail pieces complete with cutting & proper fitting etc. The plinth will be plastered/ finished on top and sides of the plinth .
Fabrication & erection of Isolator stucture as per RESSPO Norms. (steel material provided by deptt.)
Fabrication & erection of L.A. & C.T. stucture as per RESSPO Norms. (steel material provided by deptt.)
Construction of VCB plinth of size 2.0 mtr x 1.5 mtr x 1.4 mtr suitable for erection of upper structure for 33KV VCB including grouting of anchor bolts in proper alignment and level. Scope of work includes excavation of foundation base concreting in CC 1:6:12(cement, fine sand & brick ballast ),1st class brick work in cement mortor of ratio 1:4 CC in ratio 1:4:8 and RCC work in ratio 1:2:4 (cement coarse sand and stone grit of 20mm gauge )as per RESSPO norms.
Erection and installation of 33/11kV, Power transformer in a levelled position on the plinth. The work includes shifting of transformer to the site of installation within the substation premises, assembling fixing and fitting of all accessories and filling of transformer oil to the desired level and ensuring that there is no leakage. Providing & fixing Copper.L-piece 07 no.for transformer. All the jumpering & connection are included in the scope of work.
Earthing by way of boring and lowering of "B" class GI pipe 50mm dia from ground upto the water level (minimum 30 meter deep) as per standard practice
Fabrication and grouting of M.S Angle 75x75x6 or 65x65x6mm in L shape & in proper size and alignment to provide support for the separate earthing strips for power transformer neutral including supply and fixing of flexible copper bonds for neutral earthing. (Steel provided by diptt.)
Fabrication & eretion of Cable stand as per RESSPO Norms. (steel material provided by deptt.)
Assembling and installation of line /bus isolator on the isolator structure, In case of line isolator proper operation of earth links shall also be insured. The work includes fabrication for proper flexing if required.
Assembling and installation/ Mounting of lightning arrestors on the L.A.Structure as per Resspo norms.
Installation of CTs on the CT structure, along with C.T. Junction box .(Junction box to provided by controclor).
Installation of 33KV VCB- complete work including commissioning.
Jumpering of all equipments with Panther conductor in swicth yard with P.G. clamps & proper size aluminium lugs. (all materials provided by contractor)
Providing & fixing of special type connector for CT,isolator,VCB & T/F etc as per GTP.
Shifting carefully & safely 11KV I/C,O/G & B/C switchgear from outside of the switchgear room in proper position and alignment and checking-complete work with Mounting of P.T on incoming Switch gear.
Fixing and making bus bar connections in between all switchgearsafter cleaning and taping with H.T. Tape, empire tape and PVC tape properly. Providing and fixing of 6 mm thick Bakelite separators and plugging of all opening & holes with plastic compound-complete work including cost of all material (except copper Bus Bars)strictly to the satisfaction of site in- charge.
Shifting carefully & installation of 33KV single circuit transformer control panel in control room including its grouting.
Earthing of indoor and outdoor equipments by means of M.S strip 50x6mm & connecting to Pipe type earthing as per RESSPO norms. Joints will be welded with high quality arc welding.
Cable laying 11KV,3X300 and above size sq D/C in normal soil by digging of trench 900 mm deep, 450 mm wide including supply of required material as fine sand, 1st class bricks, stone slab. (All the material required for laying will be supplied by the contractor except 11 KV XLPE cable). Spare cable shall be left and burried in the trench in the shape of rings at both ends. Cable laying work includes unrolling, cutting, making rings and sealing both ends of the cable.
Cable laying in existing trench S/C all size cable.
Hoisting of 11 KV cable on 11 switchgear & Cable Stand.
Providing and Laying of following size copper, control cable through underground/cable trench/trenching SGR interlinking through proper connections to transformer control panel/protection board /Battery and Battery Charger/Relays 33/11 KV Transformer junction box/ 33KV VCB ,CTs etc as per site conditions.
Providing & installation of control cable tray.
Carefully shifting of existing panels etc. (which will be required) for making space in the control room as per instruction of site engineer , due to installation of new panels including opening controll cable and after shifting reconnection properly. (All materials provided by contractor which will be required for shifting.)
Opening and shifting of 11 KV cable from the existing 11 KV O/G VCB panel to new installed 11 KV O/G VCB panel with hoisting and connecting. (All materials provided by contractor which will be required for shifting as Straight through and Indoor J/K.)
Testing of 5 MVA and newly installed switch gears.
RAJ ENTERPRISES
M/S AARADHYA AND ADHYATM ASSOCIATES
SINLESS ELECRICAL CO. PVT. LTD.
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .