Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.8 LAccepted-AOC 212 B 8 PARDEWANPUR LAL BANGLA KANPUR 208007 | KANPUR | KANPUR NAGAR | UTTAR PRADESH | 208007 | L1 | Accepted-AOC Being (L1) | |
| 2 | L2₹17.9 L+₹1.3 L (8.06%)Rejected-Finance | L2 | Rejected-Finance Other than (L1) | |
| 3 | L3₹18.1 L+₹1.6 L (9.47%)Rejected-Finance | L3 | Rejected-Finance Other than (L1) | |
| 4 | L4₹20.6 L+₹4.0 L (24.4%)Rejected-Finance BHU | L4 | Rejected-Finance Other than (L1) | |
| 5 | L5₹20.8 L+₹4.3 L (25.9%)Rejected-Finance | L5 | Rejected-Finance Other than (L1) |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
12 Nov 2022, 6:00 pmClosed
GE (AF) E/M Chakeri
GE (AF) E/M CHAKERI KANPUR-208008
REPAIR / MAINT / REPLACEMENT OF DG SET, UPS UPTO 33 KVA AND CONNECTED WORKS AT 7 AFH UNDER GE (AF) E/M CHAKERI, KANPUR
2022_MES_558025_1
8602/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (AF) E/M CHAKERI KANPUR
As per Tender Documents
8 documents required · 8 mandatory
₹500
GE (AF) E/M CHAKERI
₹50,000
Yes
14 Jan 2023
15 Oct 2022
18 Nov 2022
15 Oct 2022
12 Nov 2022
29 Oct 2022
Amount
Periodical maintenance and complete servicing of existing DG Set of capacity 500/400 KVA Make- Cummins/ Kirlosker including replacement of filters, di-assembling of operating mechanism / parts, well cleaning with chemicals, replacing unserviceable parts / assessories, oiling / greasing of complete moving parts, calibration and resetting of governer by the rep of reputed manufacturer, cleaning/calibration of injector nozzle, cleaning/descaling of radiator assembly with cleaning agent, removal of all deposited materials including oiling / greasing of exhaust fan & bearing etc. including re -assembling the DG set after replacing the unserviceable parts and components etc., repair of canopy from rivited joints to fix as existing and making DG Set in perfect operational in manual and electrical mode including repair maintinance of connected AMF Panel, replacement of burnt wiring cable with terminals complete cleaing of panel with vacuum cleaner & painted with sparay painting, repair of Panel box with riveted Joints for complete closure of Panel including testing of DG Set at full load complete all as specified and directed. Note:- (i) Spare parts will be measured and paid seperately under respective items of Sch 'A'. (ii) Make of parts shall be same as per OEM.
Supply only following spare parts complete all as specified and directed: Rubber hose pipes with fixing clamps Note for item No 2.00 & 2.01 to 2.14:- Taking down and fixing charges of the unserviceable items (2.00 & 2.01 to 2.14) is included in the quoted rate of Item No. 1.00 above. Nothing extra wiil be paid on this account.
Lubrication oil filter
Fuel filters
By Pass filters
Fuel pipe duly covered with supper fine steel wire with coupling, nut and bolts(19 No)
Fan belt (as per sample) Make:- Fanner
Engine gasket.
Lubrication Oil, Make - Castrol Servo.
Air filter
Hose Air Cleaner
Gasket oil filter
Gasket O - Ring
Ring Seal
Asbestos rope of size 20 mm
Thermostate
Periodical maintenance and complete servicing of existing DG Set of capacity 200/125 KVA Make- Cummins/Kirlosker/Greaves Cotton/Graves Power including replacement of filters, di-assembling of operating mechanism / parts, well cleaning with chemicals, replacing unserviceable parts / assessories, oiling / greasing of complete moving parts, calibration and resetting of governer, PCB by the rep of reputed manufacturer by computer, cleaning/calibration of injector nozzle, cleaning/descaling of radiator assembly with cleaning agent, removal of all deposited materials including oiling / greasing of exhaust fan & bearing etc. including re-assembling the DG set after replacing the unserviceable parts and components etc, repair of canopy from rivited joints to fix as existing and making DG Set in perfect operational in manual and electrical mode including testing of DG Set at full load complete all as specified and directed. Note:- (i) Spare parts will be measured and paid seperately under respective items of Sch 'A'. (ii) Make of parts shall be same as per OEM.
Supply only following spare parts complete all as specified and directed: Rubber hose pipes with fixing clamps Note for item No 4.00 & 4.01 to 4.14:- Taking down and fixing charges of the unserviceable items (4.00 & 4.01 to 4.14) is included in the quoted rate of Item No. 3.00 above. Nothing extra wiil be paid on this account.
Lubrication oil filter
Fuel filters
By Pass filters
Fuel pipe duly covered with supper fine steel wire with coupling, nut and bolts. (19 No)
Fan belt (as per sample) Make:- Fanner
Engine gasket.
Lubrication Oil, Make - Castrol Servo.
Air filter
Hose Air Cleaner
Gasket oil filter
Gasket O - Ring
Ring Seal
Asbestos rope of size 20 mm
Thermostate
Periodical maintenance and complete servicing of existing DG Set of capacity 75/62.5 KVA Make- Cummins/ Kirlosker/Greaves Cotton/Graves Power including replacement of filters, de-assembling of operating mechanism / parts, well cleaning with chemicals, replacing unserviceable parts / assessories, oiling / greasing of complete moving parts, calibration and resetting of governer, PCB by the rep of reputed manufacturer by computer, cleaning/calibration of injector nozzle, cleaning/descaling of radiator assembly with cleaning agent, removal of all deposited materials including oiling / greasing of exhaust fan & bearing etc. including re-assembling the DG set after replacing the unserviceable parts and components etc, repair of canopy from rivited joints to fix as existing and making DG Set in perfect operational in manual and electrical mode including testing of DG Set at full load complete all as specified and directed . Note:- (i) Spare parts will be measured and paid seperately under respective items of Sch 'A'. (ii) Make of parts shall be same as per OEM.
Supply only following spare parts complete all as specified and directed: Rubber hose pipes with fixing clamps Note for item No 6.00 & 6.01 to 6.13:- Taking down and fixing charges of the unserviceable items (6.00 & 6.01 to 6.13) is included in the quoted rate of Item No. 5.00 above. Nothing extra wiil be paid on this account.
Lubrication oil filter
Fuel filters
By Pass filters
Fuel pipe duly covered with supper fine steel wire with coupling, nut and bolts (19 No)
Fan belt (as per sample) Make:- Fanner
Engine gasket
Lubrication Oil, Make - Castrol Servo.
Air filter
Hose Air Cleaner.
Gasket oil filter
Gasket O-Ring
Ring Seal
Thermostate
M&L for repair and maint /servicing by high skilled technician/mechanic to repair self stater of 400/500 KVA DG set and repair of its defects with complete servicing and /rewinding / replacement of unserviceable part and refixing in DG set complete all as specified and directed.
M&L for repair and maint /servicing by high skilled technician/mechanic to repair self stater of 62.5/75/125/200 KVA DG set and repair of its defects with complete servicing and / rewinding / replacement of unserviceable part and refixing in DG set complete all as specified and directed.
Supply and filling of coolant for DG Sets of any capacity complete all as directed.
S&F in replacement Push Button actuator suitable for AMF Panel of DG Set 500/400 KVA all as per sample complete all as specified and directed.
S&F in replacement Power Contactor MNX 650, 3 pole, 415 volts, 50 Hz AC supply all as per sample complete all as specified and directed. Make: L&T/Siemens/ABB/GE Power
S&F in replacement Power Contactor MNX 110, 3 pole, 415 volts, 50 Hz AC supply all as per sample complete all as specified and directed. Make: L&T/Siemens/ABB/GE Power
S&F in replacement Power Contactor MCX 45, 4 pole, 415 volts, 50 Hz AC supply all as per sample complete all as specified and directed. Make: L&T/Siemens/ABB/GE Power
S&F in replacement Power Contactor MCX 41, 4 pole , 415 volts, 50 Hz AC supply all as per sample complete all as specified and directed. Make: L&T/Siemens/ABB/GE Power
S&F in replacement Power Contactor MCX 33, 4 pole, 415 volts, 50 Hz AC supply all as per sample complete all as specified and directed. Make: L&T/Siemens/ABB/GE Power
S&F in replacement Power Contactor MCX 22, 4 pole , 415 volts, 50 Hz AC supply all as per sample complete all as specified and directed. Make: L&T/Siemens/ABB/GE Power
S&F in replacement single phase preventer suitable for 400/500 KVA DG Set AMF Panel all as per sample complete all as specified and directed. Make: L&T/Havells/ABB/Legrand/Schneider
S&F in replacement Single phase preventor suitable for 62.5 to 200 KVA DG Set AMF Panel all as per sample complete all as specified and directed. Make: L&T/Havells/ABB/Legrand/Schneider
S&F in replacement of time switch suitable for 400/500 KVA DG Set AMF Panel all as per sample complete all as specified and directed.
S&F in replacement time switch suitable for 62.5 to 200 KVA DG Set AMF Panel all as per sample complete all as specified and directed.
S&F in replacement overload relay suitable for 400/500 KVA DG Set AMF Panel all as per sample complete all as specified and directed. Make: L&T/Havells/ABB/Legrand/Schneider
S&F in replacement overload relay suitable for 62.5 to 200 KVA DG Set AMF Panel all as per sample complete all as specified and directed. Make: L&T/Havells/ABB/Legrand/Schneider
S&F in replacement Fuse Link Unit suitable for 400/500 KVA DG Set AMF Panel all as per sample complete all as specified and directed.
S&F in replacement Fuse Link Unit suitable for 62.5 to 200 KVA DG Set AMF Panel all as per sample complete all as specified and directed.
S&F in replacement battery 12 volts, 180 AH having minimum 24 month free replacement warranty and initial charging including filling with necessary electrolyte solution all as specified & directed by Engineer-in-charge. Make- Exide/Amco/Amron/Tata
Supply and fixing in replacement of battery 12 volts, 90 AH having minimum 24 month free replacement warranty and initial charging including filling with necessary electrolyte solution complete all as specified and directed. Make- Exide/Amco/Amron/Tata
S&F in replacement battery 12 volts, 70 AH having minimum 24 month free replacement warranty and initial charging including filling with necessary electrolyte solution complete all as specified and directed. Make- Exide/Amco/Amron/Tata
S&F in replacement battery lead of copper conductor 25 sqmm single core stranded fitted with brass terminal and length of 1.5 RM and connection complete all as specified and directed.
S&F in replacement battery lead of copper conductor 25 sqmm single core stranded fitted with brass terminal and length of 0.8 RM and connection complete all as specified and directed.
S&F in replacement battery brass terminals complete with connection complete all as specified and directed.
S&F in replacement of battery charger 24 volts DC complete with incoming and out going PVC copper conductor cable of suitable size with MS holding clamp complete all as specified and directed.
M&L for repair and calibration of FIP Pump as per calibration procedure and norms including replacement of barel plunger and cup 'O' rings with replacement of defective parts for 500/400 KVA DG Sets complete all as specified and directed.
M&L for repair and calibration of FIP Pump as per calibration procedure and norms including replacement of barel plunger and cup 'O' rings with replacement of defective parts for 200/125 KVA DG Sets complete all as specified and directed.
M&L for repair and calibration of FIP Pump as per calibration procedure and norms including replacement of barel plunger and cup 'O' rings with replacement of defective parts for 70/62.5 KVA DG Sets complete all as specified and directed.
S&F in replacement Auto Voltage Regulator suitable for 400/500 KVA DG set complete as per existing type and capacity complete all as specified and directed.
S&F in replacement Auto Voltage Regulator suitable for 62.5 to 200 KVA DG set complete as per existing type and capacity complete all as specified and directed.
S&F in replacement diode suitable for 400/500 KVA DG set complete as per existing type and capacity complete all as specified and directed.
S&F in replacemnt oil temp switch of 400/500 KVA DG Set complete all as existing size and capacity complete all as specified and directed.
S&F in replacemnt oil temp switch suitable for 62.5 to 200 KVA DG Set complete all as existing size and capacity complete all as specified and directed.
S&F in replacement electric shock treatment chart on flex/PVC reflecting sheet with of size 50x100 cm complete all as specified and directed.
S&F in replacement indicating lamp assembly (LED) Red, green, yellow, blue and making necessary connection including taking down existing unserviceable indicating lamp assembly, complete all as specified and directed.
All as per item No 42.00 above but for checking of voltage.
M&L for earthing (in replacement) complete with galvanised or steel earth plate electrode of size 60cmx60cmx6mm thick burried directly in ground vertically (to a depth not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to strip 32x6 mm size with nuts, bolts, check nuts, washers, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick all around, top & bottom watering pipe 20mm bore of GI medium grade with funnel and wiremesh all as shown in electrical plate No. 3 of SSR-2009 Part-I and connecting to earthing test point, main switch board and testing on completion including PCC chamber concrete 1:3:6 type C-2(using 40mm graded crushed stone aggregate) and RCC cover 75mm thick with MS TMT bar 8mm dia @ 150mm c/c both ways in cement concrete(1:2:4) type B-1(using 20mm graded crushed stone aggregate) all as shown in electrical plate in No 3 of SSR(Part-I) 2009 complete all as specified and directed. Note:- Earth wire/strip upto 7.5 m connected to earth test point shall be deemed to be included in the quoted rate.
S&F in replacement galvanized iron strip of size 32x6 mm as earth continuity conductor provided in between earth test point terminal and upto the equipment including nuts, bolts and washers complete all as specified and directed.
S&F in replacement solonoid switch suitable for existing DG set of capacity 500/400 KVA complete all as specified and directed.
S&F in replacement solonoid switch suitable for existing DG set of capacity 125/200 KVA complete all as specified and directed.
S&F in replacement solonoid switch suitable for existing DG set of capacity 62.5/75 KVA complete all as specified and directed.
Decanning of diesel oil from diesel tank of any capacity in empty barrel, dismantling of inlet & outlet fuel connection, removing all deposited material from bottom, cleaning the diesel tank with 'K' oil, scraping of old paint from outer side of tank and applying two coats of synthetic enameled paint on outer surfaces of tank, marking & painting of oil levels on tank, making inlet and outlet connection, re-filling of decanned diesel in the tank complete all as specified and directed.
M&L for servicing /cleaning of ball bearing of alternator of any capacity of DG Set by cleaning agent, cleaning the slip rings, adjustment of carbon bushes, greasing the ball bearings, refittings and alignments of complete alternator with engine for smooth functioning complete all as specified and directed.
M&L for servicing of DG Set 500/400 KVA dynamo 12 V assemblly including replacement of worn out armature, union, carbon bush complete and refixing all the component in existing position with necessayy screw, nuts and bolts for smooth and efficient functioning complete all as specified and directed.
M&L for servicing of DG Set 200/125 KVA dynamo 12 V assemblly including replacement of worn out armature, union, carbon bush complete and refixing all the component in existing position with necessayy screw, nuts and bolts for smooth and efficient functioning complete all as specified and directed.
M&L for servicing of DG Set 75/62.5 KVA dynamo 12 V assemblly including replacement of worn out armature, union, carbon bush complete and refixing all the component in existing position with necessayy screw, nuts and bolts for smooth and efficient functioning complete all as specified and directed.
Clearing away all grass vegetation, saplings, shrubs, brush wood undergrowth roots and trees not exceeding 30cm girth (measured one metre above ground level) and removing rubbish upto a distance of 50m outside the periphery of the area under clearance soft/loose soil and getting out complete all as specified and directed.
S&F in replacement 1100 Volts grade heavy duty cable one twin core, flat or circular 6 Sqmm PVC insulated aluminium stranded conductor served with inner sheathing of PVC tapes and overall PVC sheathed in service connection complete all as specified and directed.
S&F in replacement 1100 Volts grade heavy duty cable one twin core, flat or circular 10 Sqmm PVC insulated aluminium stranded conductor served with inner sheathing of PVC tapes and overall PVC sheathed in service connection from pole to Main Switch complete all as specified and directed.
S&F in replacement 1100 Volts grade heavy duty cable one twin core, flat or circular 16 Sqmm PVC insulated aluminium stranded conductor served with inner sheathing of PVC tapes and overall PVC sheathed in service connection complete all as specified and directed.
S&F in replacement fuel level indicator pipe for 400/500 KVA DG set including all accessories required for fitting of fuel pipe complete all as specified and directed.
S&F in replacement LT PVC tape roll 3/4 inch size ISI marked of length 25/26 m complete all as specified and directed.
S&F in replacemenrt Aluminium Lugs/connectors of size 16 sqmm complete all as specified and directed.
S&F in replacemrnt Aluminium Lugs/connectors of size 25 sqmm complete all as specified and directed.
S&F in replacement Aluminium Lugs/connectors of size 35 sqmm complete all as specified and directed.
S&F in replacement Aluminium Lugs/connectors of size 50 sqmm complete all as specified and directed.
S&F in replacement Aluminium Lugs/connectors of size 70 sqmm complete all as specified and directed.
S&F in replacement Aluminium Lugs/connectors of size 95 sqmm complete all as specified and directed.
S&F in replacement Aluminium Lugs/connectors of size 120 sqmm complete all as specified and directed.
S&F in replacement Aluminium Lugs/connectors of size 150 sqmm complete all as specified and directed.
S&F in replacement Aluminium Lugs/connectors of size 185 sqmm complete all as specified and directed.
S&F in replacement Aluminium Lugs/connectors of size 240 sqmm complete all as specified and directed.
S&F in replacement Aluminium Lugs/connectors of size 300 sqmm complete all as specified and directed.
S&F in replacement Aluminium Lugs/connectors of size 400 sqmm complete all as specified and directed.
Maintenance and complete overhauling of servo stablizer of capacity 500 KVA including disassmbling of operating mechanism parts, well cleaning with petrol & CRC-226 and replacing wornout parts reassembling of parts including disconnection, connection, well cleaning the complete stablizer, oil tank, connection plate, de-carbonizing all joints, metal parts and making servo stablizer operating in manual and electric mode including all routine testing, calibration, overhauling of inbuilt ACB of any capacity with replacement of burnout mechanical contact if any complete as well as writing of SM/MES No. complete all as specified and directed. Note:- (a) Spray painting of complete servo stablizer is included in the quoted rates. (b) Any rewiring/changing of cable required for funtioning of stablizer is included in the quoted rate. (c) Major Spares to be paid separately as given Below.
Supply only following spare parts complete all as specified and directed: Electronic Cards Note for item No 75.00 & 75.01 to 75.07:- Taking down and fixing charges of the unserviceable items (75.00 & 75.01 to 75.07) is included in the quoted rate of Item No. 74.00 above. Nothing extra wiil be paid on this account.
Servo motor of 10 Kg-cm torque
Micro switch
R.C. Network for motor
Carbon Brushes
New Transhformer Oil of 50 KV Die electric Strength.
Dimmer as per existing capacity
Gears as per existing capacity
Excavation in trenches in any type of soil n.exc. 1.5m wide and n.exc 1.5m in depth for LT cables complete including bricks complete all as specified and directed.
Returning, filling in, any type of soil and spreading in layers n. exc 25cm thick each layer including watering & well ramming complete all as specified & directed.
Removal of surplus soil to a distance n.exc 50m & depositing where directed at a level n. exc. 1.5m above the starting point complete all as specified & directed.
Supply and laying in replacement XLPE insulated, armoured heavy duty electric cable with alumnium conductor, 1100 volts grade, corss sectional area 95 sqmm 3.5 core complete all as specified and directed. Make :- Havells / Polycab / Gloster Cables Ltd.
All as per item No. 79.00 above but 120 Sqmm 3½ core.
All as per item No. 79.00 above but 240 Sqmm 3½ core.
All as per item No. 79.00 above above but 300 Sqmm 3½ core.
M&L for brick protection to cable using old size sub class 'B' bricks, laid flat, dry butt jointed, laid lengthwise perpendicular to the axis of cable complete all as specified and directed.
M&L for sand cushioning with layer of sand 8 cm thick before laying of cable and 15 cm after lying of calbe in trenches complete all as specified & directed.
Making horizontal bore hole under road suitable for 80 mm bore size at the depth not less than 1.00 m below ground level for passing of LT underground cable complete all as specified and directed.
S&F in replacement GI pipe light grade 80mm bore for cable protection, fixed to pole/ alongwall/ floor/ under road/ across the drain or nallaha etc complete all as specified & directed. Make: Jindal/Tata/Prakash Surya/Zenith
M&L for repair of Turbo charger of 400/500 KVA DG set complete all as specified and directed.
M&L for repair of Turbo charger of 125/200 KVA DG set complete all as specified and directed.
M&L for repair of Turbo charger of 62.5/75 KVA DG set complete all as specified and directed.
S&F in replacement ACB 415 Volts 4 pole 800 Amps 50 Hz 50 KA with Manual Drawout type with microprocessor release of existing make model and type alonwith spreader terminal including lugs/thimbles of suitable size in existing panels complete all as specified and directed. Make: L&T/Schneider/Legrand/Havells Note: Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor.
BHARADWAJ BROTHERS
Gupta Constructions
Lalta Prasad vijay kumar Forwarding Agency
Preetpowercontrol
S B ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .