Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.1 LAccepted-AOC | L1 | Accepted-AOC Accepted being lowest quoting | |
| 2 | L2₹36.2 L+₹4.6 L (14.7%)Rejected-AOC | L2 | Rejected-AOC Rejected being higher quoting | |
| 3 | L3₹37.3 L+₹5.7 L (17.9%)Rejected-AOC | L3 | Rejected-AOC Rejected being higher quoting |
Tender Value
₹29.1 L
EMD Value
₹58,200
Closing Date
27 Jun 2022, 6:00 pmClosed
GE Hisar
Garrison Engineer Hisar Military Station Hisar 125006
CA NO GE(H)-03/2022-23 SPL REPAIR TO MCB DISTRIBUTION BOXES, CABLES AND ALLIED WKS AT HISAR MIL STN UNDER GE HISAR
2022_MES_517417_3
CA No GE(H)-03/2022-23
Open Tender
Miscellaneous Works
Item Rate
180 days
Hisar Mil Stn
As per Tender documents
7 documents required · 7 mandatory
₹500
GE Hisar
₹58,200
Yes
4 Jul 2022
6 Jun 2022
29 Jun 2022
6 Jun 2022
27 Jun 2022
14 Jun 2022
Amount
Excavation in trenches not exceeding 1.5 m wide and not exc. 1.5 m depth for laying cables, foundation for pole etc and getting out in soft/loose soil etc complete all as specified and as directed.
Removing excavated material to distance n. exc 50m and depositing where directed at a level n. exc 1.5m above the starting point etc complete all as specified and as directed. .
Returning filling in incl spreading leveling watering and well ramming in layers n. exc 25cm thick etc complete all as specified and as directed.
M&L for Sand cushioning 230mm thickness with dry sand (one layer of 80mm thickness before laying of cable and other layer of 150mm thickness after laying of cable) and punned down to 180mm after laying of cable in trenches for protection of cable complete all as directed. Note :- For the purpose of payment only punned thickness shall be measured.
Taking up bricks laid as cable covers and stacking serviceable brick for reuse at site etc complete all as specified and directed.
M&L for brick covering to underground electric cable using sub class ‘B’ bricks, laid dry, flat, perpendicular to the direction of cable etc complete all as specified and directed. .
M&L for cement concrete (1:4:8) type D-2 using 40 mm graded crushed stone aggregate as in foundation complete all as specified and directed.
M&L for PCC (1:2:4) type B-1 using 20 mm crushed graded stone aggregate as in coping and the like including weathering slightly rounded or chamfered angles etc complete all as specified and directed.
Taking out the old unserviceable LT underground cable upto 25 Sqmm 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors from trenches/wall/floor/road/ culverts or pole etc complete all as specified and directed. Note : Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately under relevant items of BoQ.
Supply , laying , jointing, testing and commissioning of size 16 sqmm 4 core LT underground cable , 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified. Note : Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Supply , laying , jointing, testing and commissioning of size 25 sqmm 4 core LT underground cable , 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified. Note : Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
S&F in replacement Galvanized iron tubing, 50mm bore light grade, ISI marked, including all fittings and laid in trenches/under road/drains, fixed to poles/walls with required size of flat iron (40mmx6mm) clamps, bolts, nuts and washers for protection of LT electric cable complete. Note :- Excavation & earthwork shall be measured & paid for separately.
M&L for cable jointing kit suitable for LT XLPE UG cable for strainght through heat shrinkable indoor termination type joint complete with jointing material and accessories suitable for 50 sqmm 3 core XLPE armoured aluminium conductor cable complete all as specified and directed.
S&F aluminium lugs suitable for 16 to 50 sqmm LT cable line complete all as specified & directed.
Supply, fixing and testing in replacement of factory made sheet metal enclosure, powder coated, indoor type (double door) of size 0.90x0.90x0.20m suitable for wall / floor mounting (incl all arrangement for fixing) made out of 2mm thick CRCA sheet having independent compartments suitable for S&F 01 x MCCB 4 Pole, refixing of 06 Nos x Single Phase energy meter and S&F outgoing 06 Nos x MCB SPN and one set of indicator lamp, provided with front hinged shutter with lockable arrangement and clear glass to visualize the meter reading without opening the compartment with sufficient working space, prewired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of size 6sqmm from bus bar to each meter compartment (for Phase, neutral and earth wire) and outgoing connections from meter to respective outgoing MCB duly crimped with copper thimbles complete all as specified and directed by Engineer-in-charge and consisting of following :- (i) Bus bar for 3 Phase system of 4 x 200 Amps rated insulated copper strip mounted on resin cast insulators in independent compartment having front openable shutter - 01 Set. (ii) MCCB 4 Pole 415 Volts, 100 Amps 16 KA with adjustable thermal magnetic release - 01 No (iii) MCB SPN 40 Amps 10 KA 'C' curve - 06 Nos (iv) Indicators lamps LED in Red/Yellow/Blue colour- 01 Set of three Note :- The quoted rates deemed to be inclusive of removing the serviceable energy meter from old panel and refixing complete. (ii) The layout sketch / schematic diagram and design of the panel should be approved by the Engineer-in-charge before starting of work.
Supply, fixing and testing in replacement of factory made sheet metal enclosure, powder coated, indoor type (double door) of size 0.90x1.85x0.20m suitable for wall / floor mounting (incl all arrangement for fixing) made out of 2mm thick CRCA sheet having independent compartments suitable for S&F 01 x MCCB 4 Pole, refixing of 06 Nos x Single Phase energy meter and S&F outgoing 06 Nos x MCB SPN and one set of indicator lamp, provided with front hinged shutter with lockable arrangement and clear glass to visualize the meter reading without opening the compartment with sufficient working space, prewired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of size 6sqmm from bus bar to each meter compartment (for Phase, neutral and earth wire) and outgoing connections from meter to respective outgoing MCB duly crimped with copper thimbles complete all as specified and directed by Engineer-in-charge and consisting of following :- (i) Bus bar for 3 Phase system of 4 x 200 Amps rated insulated copper strip mounted on resin cast insulators in independent compartment having front openable shutter - 01 Set. (ii) MCCB 4 Pole 415 Volts, 100 Amps 16 KA with adjustable thermal magnetic release - 01 No (iii) MCB SPN 40 Amps 10 KA 'C' curve - 06 Nos (iv) Indicators lamps LED in Red/Yellow/Blue colour- 01 Set of three Note :- The quoted rates deemed to be inclusive of removing the serviceable energy meter from old panel and refixing complete. (ii) The layout sketch / schematic diagram and design of the panel should be approved by the Engineer-in-charge before starting of work.
S&F in replacement sheet metal enclosure distribution board SP&N, 8 way, double door, powder coated, protection class IP-42, suitable for mounting MCB, DBs confirming to IS-13032, IS-8632, BS-5484 with min 200 Amp rating copper bus bar, complete all as specified & directed. Make :- Indo Asian Cat Part No 810321 or equivalent of makes mentioned in list of makes here-in-after .
S & F in replacement sheet metal enclosure, double door type, having door earthing, suitable for fixing MCBs, TPN with 200 Amps rated bus bar, 4 way, 240 Volts. Make :- Indo Asian Cat Part No 810336 or equivalent of makes mentioned in list of makes here-in-after .
S&F in replacement sheet metal enclosure distribution board VTPN, 4 way, double door, powder coated, protection class IP-54, isolated neutral bar, mechnical impact strength IK 09 suitable for mounting MCB, DBs confirming to IS-13032, IS-8632, BS-5484 with min 200 Amp rating copper bus bar, fixing on wall with nut, bolts, washers with proper cement mortar / PCC complete all as specified & directed.
S&F in replacement MCB SP upto 40 Amps 240 Volts , type 'C' curve, 10 KA, IS-8828 marked fixing in DB complete all as specified & directed. Note :-Make of MCB shall be same of that DB.
S&F in replacement MCB SPN, 32 to 63 Amps 240 Volts , type 'C' curve, 10 KA, IS-8828 marked fixing in DB complete all as specified & directed. Note :-Make of MCB shall be same of that DB.
S&F in replacement MCB TPN, 63 Amps 415 Volts , type 'C' curve, 10 KA, IS-8828 marked fixing in DB complete all as specified & directed. Note :-Make of MCB shall be same of that DB.
S&F in replacement MCB TPN, 100 Amps 415 Volts , type 'C' curve, 10 KA, IS-8828 marked fixing in DB complete all as specified & directed. Note :-Make of MCB shall be same of that DB.
Supply, installation, commissioning and testing in replacement of MCCB 100 Amp ( fixed on existing panel) 415 volt, 4 pole, 3 phase, 16 KA breaking capacity with adjustable current range for overload protection and thermal release complete with spreader terminals (legs) and with proper lugs complete all as specified and as directed.
Supply, installation, commissioning and testing in replacement of MCCB 63 Amp ( fixed on existing panel) 415 volt, 4 pole, 3 phase, 16 KA breaking capacity with adjustable current range for overload protection and thermal release complete with spreader terminals (legs) and with proper lugs complete all as specified and as directed.
Sameer Traders
m/s Rajesh Kumar
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .