Executive Engineer Electrical SKIMS Soura
Office of the Executive Engineer Electrical SKIMS Soura
a,b,c and d part of tender documents.please refer tender document for CHC Sumbal
2019_SKIMS_87999_1
eNIT SIMS HEE EET 18 of 2019-20 Dt.11.12.2019
Open Tender
Electrical Works
Item Rate
30 days
CHC Sumbal of SKIMS
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
Director Finance SKIMS Soura
₹20,500
Yes
25 Feb 2020
13 Dec 2019
11 Jan 2020
13 Dec 2019
6 Jan 2020
13 Dec 2019
Amount
PART_A Disconnecting, dismantling of existing 63 KVA distribution transformer. The job includes transportation, loading and unloading of said transfomer from CHC Sumbal to SKIMS Soura
Supply and Erection of 410 SP 56 ST poles 11mtr Long complete with Base Plate and top Cap Confirming to IS2713 with upto date ammendments in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.
Providing & making of cement concrete bottoming for steel tabular poles in Ratio 1 : 2 : 3 with (1 x 1/2' dia ) fom bottom of pole upto 1' above of ground level including circular form work, plastering and other civil workd and excavation
Supply ,Installation.Testing & Commisioning of 250KVA,11/0.433KV 50Hz,Outdoor type,Dyn-11 oil immersed,CopperWound,ONAN Cooled, step down energy efficient level-2 Distribution Transformer having C.R.G.O core ,Confirming to IS: 1180 Part-1:2014 with latest amendments dully tested,painted and Oil filled to IS: 335 of 1983 with Latest amendments.The transformer shall be complete with following fittings:- a) Oil conservator with oil level indicator , minimum level marking and drain plugs. b) Off circuit type tap changer with position indicator and locking arrangement. c) 100mm dial type /Stem type thermometer with metal gaurd. d) Lifting lugs and Bi-directional roller. e) Rating Diagram and terminal marking plate f) Explosion Vent and valves for filtration ,drainage and filling e.t.c with necessaryplugs ,including air release plug. g) Radiator assembly and silica gel breather. (ALBA/ABB/BHEL/Crompton/Jk transformers make)
Supply erection of 75mm x 40mm x 6mm channel iron cross-Arms including drilling holes for insulator pins & nuts and bolts as required at site.
P/laying of 0.05 ACSR conductor
Providing and Laying of 300 mm sq. single core XLPE Armoured Al. cable (Havells/ Polycab/ Paramount make)
Supplying and erection of three piece nonlinear resistor type lightning arrestor suitable for 3 wire, 11 KV overhead lines with rated voltage 9KV(rms) and nominal discharge current rating of 5 KA (Station class ) and complete with galvanised clamping arrangement, G.I. bolts, nuts, washers etc. as required. ( Oblum/Lamco Make)
Supplying and erection of 200A 11KV Dropout fuse unit with 40 amp fuses, galvanised channel , Post type insulator, tinned copper contacts complete in all respects
Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required.(Oblum/Lamco make)
Providing and making of end termination 300 mm sq. single coreLT cable including Thimbling, crimping tapping, testing and connecting as per site requirements (dowels/3D make)
Supply and Erection of 200 AMP Vertical type Gang Operating Switch with galvanised channel post type insulator , Tinned copper contacts arching homes ,G.I Pipe operating handle with locking arrangement etc as required at site .
Provinding and laying of G.I Strip 25mm x 5mm.The job includes welding and use of suitable size galvanised nuts and bolts wherever necessary
Making of earth point includes salt charcoal copper plate of size 600 mmx600x3mm pit should be dug 3 mtr from the surface including copper strip from plate to surface and laying of I ½ G.I watering pipe to the plate complete as per latest specification.
Part-B
Providing fixing of Recessed / Surface type 2X2 feet LED Square Panel ip20 with system temperature 6000/6500 k having minimum system lumens efficiency 80 with power coated CRCA sheet steel housing with profilled /Flat efficiency diffueser along with constant current electronic driver (philips RC 365/ Osram /Zumtobel /trilux make )
Part-C
Supply installation testing and commissioning of 250 mm dia 900/1600 RPM exhaust fans with plastic shutters and including the cost of wall opening and making good etc complete as required in 1) Washrooms =4 no's 2) Wards =2 no ' (Havells/Crompton/Bajaj Make)
Providing/fixing of ceiling Fans 1200 mm copper wound in manifold trust hospital. (Havells/Crompton/Bajaj Make) ward 1= 2 no"s Ward 2= 2 no's Dressing Room =01 no Dental room =01 no Lab =2 no's X-ray Room =01 no Theatre =01 No
Providing/fixing of wall mounted fans 400 mm copper wound. (Havell's/Crompton /Bajaj make) Offices
PART- D
P/f of LED street light fixture IP65/66 powder coated (Bajaj/Philips/Havells make) with with following specification 1. Input voltage : 150 V to 270 V 2.Lumens : Min 3000 3. Power factor : >0.90 4. Life expecting : more than 40,000 hours 5. No of hours usage / day : 10 to 12 hours/day 6. Rated watt : 30-40W 7. Luminous flux :3000 to 4000 lumens 8. Colour Temperature : 5,500 to 6,500 K with test certificate 9. Ingress protection : IP 65/IP 66 as per IS/IEC60529-2001 with test certificate. 10. Total harmonic distortion (THD): <10% with test certificate 11. Colour rendering index : Ra > 80 12. Working Temperature : 0 deg to 50 deg 13. LED thermal management : LED shall be mounted on heat sink conductive aluminum 14. Driver board : Details shall be given for getting spare. 15. Luminary Casing : Pressure die cast Aluminum with toughened glass cover and water proof fixture
P/f of LED Flood lightIP65/66 comprising of single piece pressure die-cast aluminium housing, powder coated (Bajaj/Philips/Havells make) with following specification 1. Input voltage : 150 V to 270 V 2.Lumens : Min 6500 3. Power factor : >0.90 4. Life expecting : more than 40,000 hours 5. No of hours usage / day : 10 to 12 hours/day 6. Rated watt : 60-70W 7. Luminous flux : 6500 to 7500 lumens 8. Colour Temperature : 5,500 to 6,500 K with test certificate 9. Ingress protection : IP 65/IP 66 as per IS/IEC60529-2001 with test certificate. 10. Total harmonic distortion (THD): <10% with test certificate 11. Colour rendering index : Ra > 85 12. Working Temperature : 0 deg to 50 deg 13. LED thermal management : LED shall be mounted on heat sink conductive aluminum 14. Driver board : Details shall be given for getting spare. 15. Luminary Casing : Pressure die cast Aluminum with toughened glass cover and water proof fixture
Providing and laying 10 mm sq. 2 core XLPE / PVC insulated Al. cable Armoured in place of damaged/burnt out ones through PVC Pipes. (Polycab/Havells/Skytone/Paramount make)
Providing and making of end termination of 10 mm sq. 2 core LT cable including Thimbling, crimping tapping, testing and connecting as per site requirements (dowels/3D make)
P/laying of PVC pipe B-class 2" dia 10' long ( Ravindra /Finolex/Prince make)
P/F of looping box made of sheet steel 16 SWG size 10"x6"x4" complete with lockable, hinged type door, gas kitted, clips, nuts and bolts, MCB strip neutral connection, earthing nut bolt and painting powder coated for street lighting.
Providing & fixing of LED Lamp (Pin Type/Screw Type ) having atleast 900 Lumens for Globe type Street light in Place of fused Ones . (Havells/Wipro/Philips make)
Supplying and fixing following rating, 240/415 volts, “C”curve,10KA miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Legrand/Schneider acti -9/Siemens make) a) 6 to 10 AMP SP MCB
Circuit wire to be laid / Replacement of damaged wire as per site requirements using multi strand pvc insulated copper wire (Havells /Finolex/ Polycab/Paramount make FR) (excluding the cost of conduit) a) 1.5 mm sq. multi strand pvc insulated copper.
Providing and fixing of Busbar Chamber with angle iron stand measuring 2' x 3'x 1.5 TPN 100AMP, Aluminium buses. The job includes providing fixing of 100 Amp MCCB 4-pole 16 KA in the chamber
PART-E
Providing, fixing of fresh lighting point (5-6 amp) exposed,using double locked PVC channel 25x2 mm thick or PVC conduit 1" dia 1.5 mm thick with accessories to be fixed on the surface of the wall with rowel plugs, saddles, screws, using multi-strand 3 x1.5 mm sq. pvc insulated copper wire (P+N+E) (Havells/Finolex/ Polycab/Paramount make FR) complete with P/F of switch 5/6 amps F/T (SSK/Havell's Reo make) to be fitted on 3mm Bakelite sheet suitable size,M.S/Wooden box, rowel plugs & screws etc. complete Point.
Wiring to be carried out for fresh heating point in surface manner through pvc conduit of 25 dia. 2 mm thick using multi strand 3 x 2.5 mm.sq pvc insulated copper wire (Havells/Finolex/ Polycab/Paramount make FR) complete with P/F of switch socket combine 15/16 amps 5 pin F/T SSK/Havell's make to be fitted on Bakelite sheet suitable size, M.S/Wooden box, rowel plugs & screws etc. complete Point with civil work .
P/F of Led 4feet long batten 6000/6500k Light having extruded aluminium heat sink with anti-glare diffuser with energy efficient electronic driver CRI greater than 85 with minimum sytem lumens 2000 and maximum wattage 22 including connection with multistrand copper conductor 3 core cable etc as required at site.(philips/trilux/osram/zumtobel make)
Providing/fixing of ceiling Fans fans 1200 mm copper wound (make Havell's/Crompton /Bajaj ).
Replacement/supply and fixing of following piano type accessories ( SSK/ Havells Reo make). a) Fan Regulator stepped type (two way).
b) S/S combine 3 pin 5A/3 pin 15 A.
c) S/S combine 3 pin 5A/ 3 pin 15 A Box Type.
Circuit wire to be laid / Replacement of damaged wire as per site requirements using multi strand pvc insulated copper wire (Havells /Finolex/ Polycab/Paramount make FR) (excluding the cost of conduit) a)2.5 mm 2 multi strand pvc insulated copper wire .
b) 4mm 2 multi strand pvc insulated copper wire .
c)10mm 2 multi strand pvc insulated copper wire .
Supplying and fixing following way, single pole and neutral, sheetsteel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper insulated bus bar, neutral bus bar, earth bar,din bar, interconnections, powder painted including earthing etc.as required (SSK /Havells/Indo Asian/Schneider make) a) 8 Way SPN
Supplying and fixing following rating, 240/415 volts, “C”curve,10KA miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Legrand/Schneider acti -9/Siemens make) a)MCB single pole 6 A to 32 A
b)MCB double pole 63 A
Providing and fixing following rating and breaking capacity and Four pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.. (Legrand /Hager/ Schiender NSX/Siemens(3VL) make )( Adjustable range from .7 to1) a)MCCB 125 A having 25KA B/capacity
M/s BILAL ELECTRIC GOODS
M/S N. A. TRADERS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .