Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹2.4 Cr
EMD Value
₹3.6 L
Closing Date
30 Aug 2025, 10:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Krishna Bhagya Jala Nigam Limited
Santoshkumar
Construction of 1x17.5MVA standby power Transformer bay at 110/6.6KV switch yard and allied works of Indi LIS(Gutti Basavanna) pump house( KBJNL) at Kembhavi, Yadagiri dist. with five years maintenance at Indi LIS and shifting of 1x12.5MVA 110/6.6KV Transformer commissioning at ALBC Head work.
KBJNL/2025-26/LI/WORK_INDENT1559/CALL-4
KBJNL/2025-26/LI/WORK_INDENT1559/CALL-4
Open
Lift Irrigation Scheme
Two Tender Document System(Two Cover)
KBJNL Division I.B.C Division 1 Kembhavi
9 documents required · 9 mandatory
List of existing commitments and ongoing works
List of works for which tenders already submitted
Banker Details for reference
Reports on the financial standing of the tenderer, such as profit and loss statements and auditor’s reports for the last five years
Qualification and experience of the key technical and management personnel in permanent employment with the tenderer and those that are proposed to be deployed on this contract, if awarded
List of Financial Resources with Certificates
The intending bidder should have in last 5 years i.e. from 2020-21 to 2024-25 satisfactorily completed(not less than 90% of the contract value) as a prime contractor, one similar work costing not less than 50% of amount put to tender (50% of amount put to tender Rs.121.02 Lakhs in last 5 years for more information please refer DTP
The intending bidder should have executed a minimum quantity of following critical items of work (Usually 80% of the peak annual rate of construction in any one financial year, during the last five financial years reckoned back from 2024-25. The certificate should be issued by an officer not below the rank of Executive Engineer of the concerned Division/equivalent officer and countersigned by the SE of the concerned Circle/ next higher officer.
A copy of the valid Registration certificate of CEIG Class-I Electrical contractor
Copy of Valid Employees Provident Fund Registration Certificate.
Copy of Valid GST Registration Certificate.
The Requisite earnest money deposit in e-cash.
The intending bidder should have a achieved a minimum financial turnover of not less 2 times the estimated annual payments i.e.Rs. 968.16 Lakhs for more details please refer DTP
Each bidder should furnish liquid assets and/or availability of credit facilities of not less than 122.00Lakhs
Tenderers who meet the above specified minimum qualifying criteria, will only be qualified, if their available tender capacity is more than the total tender value
₹5,000
₹3.6 L
20 Aug 2025
20 Aug 2025
2 Sept 2025
25 Aug 2025
26 Aug 2025
Construction of 1x17.5MVA standby power Transformer bay at 110/6.6KV switch yard and allied works of Indi LIS(Gutti Basavanna) pump house( KBJNL) at Kembhavi, Yadagiri dist. with five years maintenance at Indi LIS and shifting of 1x12.5MVA 110/6.6KV Transformer commissioning at ALBC Head work.
ISOLATORS : 110 kV, 1250 A, 40 KA class double break Electrically cum manually operated isolator with solid core insulators Upright mounting type without Earth switch.LPH 4600mm
CURRENT TRANSFORMER : Current transformer Single phase, oil filled outdoor type with R bimetallic terminal connectors suitable for rigid bus bar.110 kV class, 40 KA, 3 Core, CT of ratio 400-200/1-1-1A...
CIRCUIT BREAKER : SF-6 Gas circuit breaker with semi-pneumatic / pneumatic operated / spring type operating mechanism including mounting arrangements R bi-metallic terminal connector complete suitable...
Lightning Arrestors SURGE ARRESTOR : (Procelain housing) metal oxide, Gapless type with R bimetallic connectors suitable for rigid bus bar.96 kV, 10 KA, class - II, Heavy duty Metal oxide type
Station Structures : (Lightning Mast)
A) 110kV Side station structure fabricated out of galvanized mild steel including Bolts and Nuts (Approx. Unit Wt. in MT add 5% towards B&N). i) Station towers (v...
MOUNTING STRUCTURES :110KV isolator, LPH 3.05mtr (0.76 MT per tower)
MOUNTING STRUCTURES Current transformer. 110 kV (0.149 MT per tower)
MOUNTING STRUCTURES Lightening arrestors. 110 kV . (0.072 MT per tower)
MOUNTING STRUCTURES Pedestal insulators. 110 kV . (0.147 MT per tower)
MOUNTING STRUCTURES BUS-Potential transformer. 110 kV (0.149 MT per tower)
BUS BAR FORMATION :Rigid Bus with Taps & Clamps:i) Aluminium pipe conforming to 6340WP of IS-5082/ 1969 (BS 1600-Sch. 40 ) of following nominal diameter. a) 50mm-110kV Main Bus.
BUS BAR FORMATION :Rigid Bus with Taps & Clamps:i) Aluminium pipe conforming to 6340WP of IS-5082/ 1969 (BS 1600-Sch. 40 ) of following nominal diameter. b) 50mm size connecting isolator to vertical t...
BUS BAR FORMATION :ii) A) Straight taps suitable for 50mm Aluminium tube(BS-1600) of 1250mm vertical height for vertical portion & cross bus on 110kV side with rounded off end.
BUS BAR FORMATION :ii) B) Straight/ angular taps suitable for 50mm Aluminium tube(BS-1600) for connecting rigid bus to 50mm Al pipe connected between 2 isolators
BUS BAR FORMATION :iii) A) Post insulator clamps suitable for 50mm Aluminium pipe & Post insulator solid core type.a) Rigid Type
BUS BAR FORMATION :iii) A) Post insulator clamps suitable for 50mm Aluminium pipe & Post insulator solid core type.b) Expansion type
BUS BAR FORMATION :iii) A) Post insulator clamps suitable for 50mm Aluminium pipe & Post insulator solid core type.c) Sliding Type
INSULATORS Post insulator Solid core Insulator 110 kV as per IS5350,part II & III.
HARDWARES :Power Connectors, Expansion Type Terminal Connectors suitable for Aluminium pipes
HARDWARES :Post insulator clamp suitable for Rigid bus bar Size 50mm ID, 110 kV
Power Cables:-3R x 1 Core,1000 Sq.mm. AL, XLPE, FRLS, PVC Sheathed armoured power Cables. (From Transformer to Incomer HT Switchgear Panel) voltage 6.6kv/11kv.
Power Cables:-1R x 1 Core,1000 Sq.mm. AL, XLPE, FRLS, PVC Sheathed armoured power Cables. (From Transformer to NGT Panel)voltage 6.6kv/11kv.
Power Cables:1R x 1 Core, 150 Sq.mm. AL, XLPE, FRLS, PVC Sheathed armoured power Cables. (From NGT Panel to NGR)voltage 6.6kv/11kv.
Power Cables:1R x 3 Core, 400 Sq.mm. AL, XLPE, FRLS, PVC Sheathed armoured power Cables. (From HT Switchger Panel to Capacitor bank Panel)voltage 6.6kv/11kv.
Copper Control Cables : 19 Core 2.5 Sq.mm. Copper Control Cables (From T'mer Marshalling box to C&R panel (1R) / OLTC to RTCC Panel-2R / SF6 to C&R Panel)
Copper Control Cables : 4 Core 4 Sq.mm. Copper Control Cables (From LT ACDB to Power T'xmer OLTC motor supply / Isolator to C&R Panel )
Copper Control Cables : 2 Core 4 Sq.mm. Copper Control Cables (From LT ACDB to Power T'xmer Marshalling box / Isolator to C&R Panel )
Cable trays for Power Cables & Control Cables Supplying & Laying cable trays including welding fixing of supports 700 mm width (Suitable for cable ducts of A, B & C type)
Cable trays for Power Cables & Control Cables Supplying & Laying cable trays including welding fixing of supports. 600 mm width (Suitable for cable ducts of A, B & C type)
Cable trays for Power Cables & Control Cables Supplying & Laying cable trays including welding fixing of supports.300 mm width (Suitable for cable ducts of A, B & C type)
Cable trays for Power Cables & Control Cables Supplying & Laying cable trays including welding fixing of supports.350 mm width (Suitable for cable ducts of A, B & C type)
Lighting (outdoor):- Supply and erection of 14 Feet Height Street Light Pole 14 Feet
Height Street Light Pole on suitable cement concrete foundation with 2.5 Feet height dia 95 mm cast iron decorative...
Lighting (outdoor):-LED Streetlight 200 w
Earth Mat formation for Stand by Transformer bay.Excavation, formation, refilling for earth mat As per KPWD SR 2018-19 page no 06 (2)(2.4) Hord soil +10% area watage
Earth Mat formation for Stand by Transformer bay.Supplying and laying MS.Flat 50 x 6 mm flat welding and applying ACB paint to welded portion and covering with Sodium Bentonite Clay (SBC supplied by C...
Earth Mat formation for Stand by Transformer bay.Grounding of equipments with 50 x 6 mm G I flat and connecting equipments to the earth mat/ground pit including all connected works with all materials ...
Earth Mat formation for Stand by Transformer bay.Providing C.I. Pipe of 100mm ID 13mm thick 2.75 mtr. long with 2 part GI Flat 50x6mm clamp welded allround the pipe etc., including cost of excavation ...
Power Cables Termination Kit:-Termination kit suitable for 1 Core, 1000 Sq.mm. AL, XLPE, FRLS, PVC Sheathed armoured power Cable.
Power Cables Termination Kit:-Termination kit suitable for 3 Core, 240 Sq.mm. AL, XLPE, FRLS, PVC Sheathed armoured power Cable.
Power Cables Termination Kit:-Termination kit suitable for 3 Core, 400 Sq.mm. AL, XLPE, FRLS, PVC Sheathed armoured power Cable.
HT Switchgear (Indoor):- Design, engineering, procurement, installation, testing and commissioning of 6.6kV, 2000A, 25kA/3Sec Indoor HT Panel coupling with existing panle with comprising of 1No Income...
HT Switchgear (Indoor):- Design, engineering, procurement, installation, testing and commissioning of 6.6kV, 2000A, 25kA/3Sec Indoor HT Panel coupling with existing panle with comprising of 2Nos Bus C...
HT Switchgear (Indoor):- Design, engineering, procurement, installation, testing and commissioning of 6.6kV, 2000A, 25kA/3Sec Indoor HT Panel coupling with existing panle with comprising of 2Nos Adapt...
Capacitor bank Panel:-6.6kV, 965 KVR Capacitor bank Panel
Control and Relay Panel complete. 110 kV Transformer Control & Relay panel Simplex type
Fire extinguishing system for power transformer .Nitrogen Injection fire extinguishing system for power transformer below 100MVA.
Fire extinguishing system for power transformer.Sand type . G.I. Bucket 15 litres capacity
Fire extinguishing system for power transformer.Sand type, Steel stands for the above to have 4 Buckets to each stand.
Lightning System,7/3.15 mm G.I. Wire for ground conductor.
Lightning System,Ground Wire Clamp 7/3.15 mm, 2 bolt
Earth work excavation by manual means for drains, canals, waste weir, draft, approach channels, key trenches, foundation of Buildings & bridges and such simillar works in all kinds of soils, as per dr...
Earth work excavation by manual means for drains, canals, waste weir, draft, approach channels, key trenches, foundation of Buildings & bridges and such simillar works in all kinds of soils, as per dr...
Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS...
Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with supe...
Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with supe...
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by r...
Removal of Unserviceable Soil with Disposal upto a suitabledistance as directed by the Engineer incharge of work.
Supplying, fitting and placing TMT FE 550/550D Steel Reinforcement complete as per drawing and
technical specification.
Providing and fixing Structural Steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of appro...
Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/tra...
Providing Brick work with common burnt clay Non Modular bricks of class designation 3.5 in superstructure above plinth level in all shapes and sizes in Cement mortar 1:6 (1 cement : 6 coarse sand) inc...
Providing 20 mm cement plaster of mix :1:6 (1 cement: 6 fine sand) to brick/stone masonary including rounding off corners wherever required smooth rendering, providing and removing scaffolding, includ...
Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required...
Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/tra...
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direct...
jelly spredding (20-25mm) supply and providing jelly in the station yard of uniform thickness of 100mm including the cost of materials, labour charges, required tools and plants etc., complete work sh...
Dismantling and transportation from ALBC headwork to Kembhavi headwork and dismantling and transportation from Kembhavi headwork to ALBC headwork of 1x12.5MVA volt amp transformer and errection testin...
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
TN 1559.docx
Others - Tendet notification • 0.06 MB
Transformer Bay DTP.doc
Tender Document • 0.66 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .