| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹3.2 LAccepted-AOC | 1 | Accepted-AOC L1 | |
| 2 | 2₹3.3 L+₹505 (0.15%)Rejected-AOC | 2 | Rejected-AOC L2 | |
| 3 | 3₹3.4 L+₹4,995 (1.51%)Rejected-AOC | 3 | Rejected-AOC L3 | |
| 4 | Not Admitted-Fee/PreQual/Technical 15 THAHIPUR HARIHARGANJ RANIGANJ PRATAPGARH UTTAR PRADESH 230304 | PRATAPGARH | UTTAR PRADESH | 230304 | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| Sl No | Description | Qty | Unit | ELECTRO INDIA L1 | DEEPAK ENGINEERING L3 | HARE KRISHNA ENERGY PROJECTS L2 |
|---|---|---|---|---|---|---|
| 1.00Strengthing and maintenance of 02 no. 11 KV feeder along with supply and fixing of 11 KV CT & PT along with its connector and other associated work at 132KV Sub station Gyanpur(P.C.) under ETD-I Prayagraj ,with all cost of men & material (as per technical specification & sample) misc consumables T&P etc. required for satisfactory completion of work to be provided by conctrator for satisfaory completion of work as per technical specification and direction of the supervising engineer , details given below:- | ||||||
| 2.00 | Opening & Jumpering with Twin ACSR Moose Conductor of 11KV Bay CT & PT conductor of twin ACSR Moose Conductor to out going 11KV Bay Conductor to Bus PT & 11KV LV T/F Bushing to CB,CB to CTs to LV Bushing of in 11KV Side of 20MVA T/F-I&II by cutting & Bending of conductors and Tightening of the jumpers with P.G. Clamps/Equipment Terminal Connectors etc Along with shifting of the conductor etc. from store at the Sub Station to the switchyard (01 JOB for each Jumper) | 10 | Job | 395 ₹3,950 Lowest | 410 ₹4,100 | 400 ₹4,000 |
| 3.00 | Supply of 11 KV CT of ratio 1600/800/1-1 atleast having 2 no. core. One core suitable for protection having PS accuracy class and one no. core for metering of 0.2 S acc class, burden 15 VA. | 4 | No. | 30,995 ₹1,23,980 Lowest | 31,000 ₹1,24,000 | 31,000 ₹1,24,000 |
| 4.00 | Erection of 11KV CT 1600/800/1 Amp 0.2 accuracy class . Job inculdes dismantling of old 11 KV CT by opening of its all clamps/connectors, safely unloading of these and safely transportation from work place to store. Shifting of new 11 KV CTs having 0.2 Acc from store to working place, erection and proper connection along with fixing of CT junction box . Work includes opening of existing CT junction box , erection , earthing with 50x6 ms flat and connection of all cables using ferrule and cable glands. | 3 | Job | 490 ₹1,470 Lowest | 500 ₹1,500 | 500 ₹1,500 |
| 5.00 | Supply of CT junction box as per sample | 2 | No. | 9,990 ₹19,980 Lowest | 10,000 ₹20,000 | 10,000 ₹20,000 |
| 6.00 | Erection of CT junction box . Work includes opening of existing CT junction box , erection , earthing with 50x6 ms flat and connection of all cables using ferrule and cable glands. | 2 | Job | 490 ₹980 Lowest | 500 ₹1,000 | 500 ₹1,000 |
| 7.00 | Supply & fixing of 02 acc class 50 VA burden11KV PT as per sample | 2 | Job | 30,995 ₹61,990 Lowest | 31,000 ₹62,000 | 31,000 ₹62,000 |
| 8.00 | Erection of 02 acc class 50 VA burden11KV PT . Job inculdes dismantling of old 11 KV PT by opening of its all clamps/connectors, safely unloading of these and safely transportation from work place to store. Shifting of new 11 KV PTs having 0.2 Acc from store to working place, erection and proper connection and replacement of old PT junction box with new one if required. (01 JOB for each PT-02No.) | 2 | Job | 490 ₹980 Lowest | 500 ₹1,000 | 500 ₹1,000 |
| 9.00 | Supply of 11KV C.B. bushing clamp Connector duly made of LM-6 Aluminum Ally suitable for twin ACSR Moose conductor 1200Amp complete with chuck nut 18mm size Cu Bolts, Nuts, Spring & plane washer as per Technical Specification & as per Sample. | 10 | No. | 1,795 ₹17,950 Lowest | 1,800 ₹18,000 | 1,800 ₹18,000 |
| 10.00 | Supply of 11KV C.T. Stud clamp Connector duly made of LM-6 Aluminum Ally suitable for twin ACSR Moose conductor 1200 Amp complete with chuck nut 18mm size Cu Bolts, Nuts, Spring & plane washer as per Technical Specification & as per Sample. | 10 | Job | 1,795 ₹17,950 Lowest | 1,800 ₹18,000 | 1,800 ₹18,000 |
Tender Value
₹3.3 L
EMD Value
₹3,500
Closing Date
19 May 2025, 5:00 pmClosed
Suprintending Engineer
Superintending Engineer Electricity Transmission Circle I 57 George Town Prayagraj 211002 PH- 0532-2256499/9415311005
Strengthening and Maintenance of outgoing 11 KV Bay of 20 MVA T/F-I and II alongwith supply and fixing of 11 KV CT, PT, Clamp Connector and other associated works at 132 KV Substation Gyanpur Pump Canal under Electy. Trans. Division-I, Prayagraj.
2025_UPTCL_1035535_1
05-ETC-I(P)/ 2025-2026
Open Tender
Electrical Works
Item Rate
60 days
Prayagraj
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE ETC-I PRAYAGRAJ
₹3,500
11 Dec 2025
2 May 2025
20 May 2025
2 May 2025
19 May 2025
2 May 2025
Amount
Strengthing and maintenance of 02 no. 11 KV feeder along with supply and fixing of 11 KV CT & PT along with its connector and other associated work at 132KV Sub station Gyanpur(P.C.) under ETD-I Prayagraj ,with all cost of men & material (as per technical specification & sample) misc consumables T&P etc. required for satisfactory completion of work to be provided by conctrator for satisfaory completion of work as per technical specification and direction of the supervising engineer , details given below:-
Opening & Jumpering with Twin ACSR Moose Conductor of 11KV Bay CT & PT conductor of twin ACSR Moose Conductor to out going 11KV Bay Conductor to Bus PT & 11KV LV T/F Bushing to CB,CB to CTs to LV Bushing of in 11KV Side of 20MVA T/F-I&II by cutting & Bending of conductors and Tightening of the jumpers with P.G. Clamps/Equipment Terminal Connectors etc Along with shifting of the conductor etc. from store at the Sub Station to the switchyard (01 JOB for each Jumper)
Supply of 11 KV CT of ratio 1600/800/1-1 atleast having 2 no. core. One core suitable for protection having PS accuracy class and one no. core for metering of 0.2 S acc class, burden 15 VA.
Erection of 11KV CT 1600/800/1 Amp 0.2 accuracy class . Job inculdes dismantling of old 11 KV CT by opening of its all clamps/connectors, safely unloading of these and safely transportation from work place to store. Shifting of new 11 KV CTs having 0.2 Acc from store to working place, erection and proper connection along with fixing of CT junction box . Work includes opening of existing CT junction box , erection , earthing with 50x6 ms flat and connection of all cables using ferrule and cable glands.
Supply of CT junction box as per sample
Erection of CT junction box . Work includes opening of existing CT junction box , erection , earthing with 50x6 ms flat and connection of all cables using ferrule and cable glands.
Supply & fixing of 02 acc class 50 VA burden11KV PT as per sample
Erection of 02 acc class 50 VA burden11KV PT . Job inculdes dismantling of old 11 KV PT by opening of its all clamps/connectors, safely unloading of these and safely transportation from work place to store. Shifting of new 11 KV PTs having 0.2 Acc from store to working place, erection and proper connection and replacement of old PT junction box with new one if required. (01 JOB for each PT-02No.)
Supply of 11KV C.B. bushing clamp Connector duly made of LM-6 Aluminum Ally suitable for twin ACSR Moose conductor 1200Amp complete with chuck nut 18mm size Cu Bolts, Nuts, Spring & plane washer as per Technical Specification & as per Sample.
Supply of 11KV C.T. Stud clamp Connector duly made of LM-6 Aluminum Ally suitable for twin ACSR Moose conductor 1200 Amp complete with chuck nut 18mm size Cu Bolts, Nuts, Spring & plane washer as per Technical Specification & as per Sample.
Supply & Fixing of spacer suitable for 11KV Bus bar of Twin ACSR Moose Conductors with 250mm Spacing and duly made of LM-6 Aluminum Alloy Complete with 12mm distance HDG Bolts, Nuts, Spring & Plain washers as per Technical Specification &Sample.
Supply & fixing of 11KV PI clamp Connector duly made of LM-6 Aluminum Ally suitable for twin ACSR Moose conductor complete with chuck nut Bolts, Nuts, Spring & plane washer as per Technical Specification & as per Sample.
Supply of Blue color silica gel of size 10-12 mm for various transformer
Supply of CRC 500ML BOTTLE
Providing and fixing of 160 watt LED light make syska / Philips/ Bajaj etc. Along with MS bend pipe (2"dia 1.25 mm long) and fitting clamp at 132 KV S/S Handia. The job includes fixing of above light fitting with help of MS bend pipe and clamp then jointing with 1 phase supply after laying cable and complete with all respect. The job includes labour materials (ie 160 watt LED make syska /Philips/ Bajaj etc . MS bend pipe , fixing clamp etc) and T&P required for completion of all job will arrange by contractor to complete the job satisfactory
HARE KRISHNA ENERGY PROJECTS (BID ID -5200661)
DEEPAK ENGINEERING (BID ID -5200809)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .