Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.9 LAccepted-AOC 209 210 AGGARWAL TOWER PLOT NO 2 SECTOR 5 ROHINI NORTH WEST DELHI DELHI 110085 | DELHI | NORTH WEST DELHI | DELHI | 110085 | L1 | Accepted-AOC accepted | |
| 2 | L2₹7.4 L+₹52,720 (7.66%)Rejected-AOC DSS 194 POCKET A SEC 14 125001 | HISAR | HARYANA | 125001 | L2 | Rejected-AOC rejected |
Tender Value
₹6.0 L
EMD Value
₹12,720
Closing Date
20 Apr 2023, 5:00 pmClosed
VISHWNATH KHICHI
ED - Rohtak
The Government of Haryana has approved a scheme for the construction of subject cited building along with 2 nos. class-IV (550Sft.) residences. The work stands administratively approved amounting to Rs. 745.01 lakhs only vide the Additional Chief sec
2023_HRY_271618_1
2023B9A9E496 14E1 48A5 88BC DB525FA3B19C667BAR
Open Tender
Electrical Works
Works
180 days
PATODA
Technical documents as per approval DNIT conditions.
3 documents required · 3 mandatory
₹1,000
₹12,720
Yes
23 Jun 2023
6 Apr 2023
21 Apr 2023
6 Apr 2023
20 Apr 2023
6 Apr 2023
Amount
HSR Items
[23.7.6.2]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.2. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 25 mm dia.
NS Items
SITC of Micro processor based 2 wire fault tolerant, networkable type Fire Alarm / Detection Control Panel (having nos. of loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 characters LCD unit/ 5.7’’TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 80 LED Indicators. The Panel shall have 3 Serial Ports. The pane\l shall have a built in power supply and battery charger along with maintenance free 24 AH,2 x 12 volt SMF lead acid batteries capable of running for a minimum of 24 hours with battery charger complete as required. And conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS/ as per specifications complete in all respect up to the entire satisfaction of Engineer-in –charge of work. Make: Bosch FPA 1000 Series / Honeywell Morley DXE /Siemens Cerberus / GST 200
SITC of addressable multisensor detector with a combination of optical and thermal including base, auto addressing features as required. Detectors should have 2 as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elemnets in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance wiht EFSG agreement EFSG/F/97/005. EMC safety for detector shall be 50 V/m. shall be EN54/VDS/UL certification. ((Detectors without inbuilt isolators may be considered with an additional isolator module after 20 devices) Make: Bosch FPA 1000 Series / Honeywell Morley DXE /Siemens Cerberus / GST 200
SITC of UL/EN54/LPCB listed and FM approved line isloating for isolation the section of circuit in case of short in the addressable loop wiring Make: Bosch / Siemens Cerberus/ Morley / Edwards
SITC of intelligent analog addressable type Manual Call point having surface or flush mounting option fully compliant to EN54 having rotary decade switches for addressing with back box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect upto the entire satisfaction of Engineer-in-Chage of the work. Make Siemens cerberus/ Morely/ Edwards
SITC of addressable Loop powered hooter with strobe complete with mounting base as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required complete the ob in all respect upto the entire satisfaction of Engineer - in - charge of work. Make: Make Bosch/ Morley/ Siemens/ Cerberus/ Edward
SITC of minimum 1000 Mtr. Range Siren generator provided at the roof of the building with separate power supply relay etc. with all accessories required to complete the job in all respect upto the entire satisfaction of engineer-n-charge of the work. Make: National / Kheraj
SITC of Glow Type EXIT Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink sulphate as bare chemical class 1 material PSPA fixed on 3mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener Make: GLOLITE / PES / OMEX
Supply and erection of PVC unsheathed copper conductor cable Size 1.5 sq.mm two core 1100 volts grade in pipe of suitable size excluding cost and erection of pipe. Havells /Polycab/RR
INDIAN SECURITY AND FIRE SAFETY
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .